Instance ID 

 

Packed parameters from Instance ID 1-7 

Attribute ID 

Description 

Type 

Value 

1 Name 

Byte-String 

“Packed 

Parameters” 

2 Data-type 

double 

integer 

3 Elements 

4 Access 

Read/Write 

Data values 

Double Integers 

Last Write values 

Max. values 

Double Integers 

Max. values  

Min. values 

Double Integers 

Min. values  

Read 

 

Default values 

Double Integers 

Default values  

Write 

Data values 

Double Integers 

>= Min and <= max values 

 
Data structure for Instance 8: 

Double Integer 

 

1  

Volume 

 

 Tube  

  Speed 

3  

Acceleration 

 

Reverse 

4  

Density 

5  

Reserved 

6  

Reserved  

Reserved 

 
 

Instance  

 

Versions- and Alarm strings 

Attribute ID 

Description 

Type 

Value 

Name 

Byte-String 

“Versions / Alarms / Warnings” 

2 Data-type  - 

4 (char) 

String of (1-39) (char) 

3 Elements  - 

39 

4 Access  - 

Read 

Only 

MC100 Version 

char 

MC100 Version 

Pump version 

Char 

Pump version  

Alarm Type 

Char 

Alarm-string (Read at alarm) 

Read 

 

Warning Type 

char 

Warning-string (Read at warning)

 
 

Instance  

10 

 Alarm 

number 

Attribute ID 

Description 

Type 

Value 

1 Name 

Byte-String “Alarm 

number” 

2 Data-type  - 

Integer 

3 Elements  - 

4 Access  - 

Read 

Only 

5 Data 

value 

Integer 

Alarm number 

5

 

6 N.A. 

Integer 

 

7 N.A. 

Integer 

 

Read 

 

8 N.A. 

Integer 

 

 

                                                 

5

 Alarm – number is a reference to the Alarm list (Chapter 8).The text-string can also be read from Instance

 9

, Attribute 

7

.The number is also flashing on the 2-digit display [AL][number]

 

Содержание MC100

Страница 1: ...User s Manual MC100 MC100 DeviceNet OM 1 01 EN doc Version 1 01 Page 1 of 36 MC100 Pump Control Module User s Manual DeviceNet...

Страница 2: ...m and warning display 13 5 3 4 Dipswitch 13 6 Configuring the fieldbus network to the MC100 14 6 1 Connecting the MC100 and the pumps for the first time 14 6 2 Configuring the DeviceNet network 15 7 O...

Страница 3: ...Users Manual MC100 MC100 DeviceNet OM 1 01 EN doc Version 1 01 Page 3 of 36 12 Declaration of Conformity 36...

Страница 4: ...1 to 16 pumps Pumps All Watson Marlow Flexicon pumps types that communicates on Flexnet WMF Watson Marlow Flexicon 1 2 Precautions This manual should be read thoroughly before using the MC100 It is s...

Страница 5: ...intended for mounting inside the control cabinet of the filling line The MC100 is designed with the purpose of integrating Watson Marlow Flexicon pumps into a filling line The MC100 has no physical o...

Страница 6: ...DeviceNet OM 1 01 EN doc Version 1 01 Page 6 of 36 MC100 holds no recipes historical data or audit trail only current runtime parameters for the filling system is stored internally 3 Technical specif...

Страница 7: ...able communicate with MC100 via FlexNet protocol Material and surface treatment Mounting box made from aluminium All aluminium parts anodised conductive Environmental Ingress protection according to I...

Страница 8: ...check that all ordered items have been received and that no items were damaged during transport In case of any defects or omissions please contact WMF or your supplier immediately Please verify that t...

Страница 9: ...to mount the MC100 The MC100 must be mounted in an environment that adheres to the specifications in 3 2 Be sure that the MC100 is also protected from the following conditions Rain and moistures Corro...

Страница 10: ...3 ST 2 5 The Flexnet connector should be connected to the corresponding terminals on all the pumps establishing a multidrop network and the last pump should be terminated with a 120 ohm resistor betw...

Страница 11: ...or Connect with 1 RS485 A I O 2 TxD OUT 3 RxD IN 4 N C 5 GND 6 NC 7 CTS OUT 8 RTS IN 9 RS485 B I O 9 pole SubD Male 9 pole SubD female X4 Fieldbus Interface DeviceNet Connect with for example 1 OV Bla...

Страница 12: ...d connecting to the network for the first time but if the address is change after power up the new address will flash on P4 P5 display for 5 seconds where it is possible to change back to the old addr...

Страница 13: ...lay is showing the network node address 5 3 3 Alarm and warning display The node address is replaced by a flashing AL and the alarm number XX when and alarm is present see 8 1 1 Alarms Er and the warn...

Страница 14: ...bits even parity and 1 stop bit When applying power to the MC100 it will identify itself by printing the line MC100 MFSC Ver x yy x yy will be the current version The MC100 will then try to identify...

Страница 15: ...s se support support asp PID 324 ProductType Anybus CompactCom In section 4 4 Configuring the I O size and Mapping in the document please use the examples below in stead for configuration Example 1 Th...

Страница 16: ...e empty 7 1 1 Process control bits for MC100 There is allocated one word 2 bytes for MC100 control bits as shown below Word 0 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 B1 7 B1 6 B1 5 B1 4 B1 3 B1 2 B1 1 B...

Страница 17: ...t 0 B1 1 Mode status bit 1 MC100 mode status Mode status bit 0 Mode status bit 1 Individuel 1 0 Parallel 0 1 Seriel 1 1 B1 2 3 Reserved for future use B1 4 Ready to receive acyclic ADI parameters expl...

Страница 18: ...P START Bit 0 START Starts a single Dispense cycle when the Pump is set in Dispense mode Bit 1 This bit must be cleared upon receiving the BUSY bit in the status byte for the pump see below Bit 1 DISP...

Страница 19: ...P9 P8 P7 P6 P5 P4 P3 P2 P1 Bit mapping in the status byte 7 6 5 4 3 2 1 0 ALARM Direction DONE Pump Dispense Tube Br BUSY READY Bit 0 READY Pump is ready self check is OK Bit 1 BUSY 1 Indicate that th...

Страница 20: ...able to use the MC100 with PLC s without floating point capability The data type is a double word type where there is a hidden fixed decimal point position with 5 decimals Examples Floating point valu...

Страница 21: ...nteger 10 elements 80 17 Tubes steps ml Double integer 10 elements 127 18 Misc Status bits Integer 1 element Not described 19 Misc Diagnostics Integer 8 elements Not described 20 Reserved for Balance...

Страница 22: ...r 0 01000 Read 8 Default value Double Integer 100 00000 Write 5 Data value Double Integer Min and max value Instance 2 Tube Attribute ID Description Type Value 1 Name Byte String Tube 2 Data type Inte...

Страница 23: ...alue Double Integer 0 Write 5 Data value Double Integer Min and max value Instance 6 Density Attribute ID Description Type Value 1 Name Byte String Density 2 Data type double integer 3 Elements 1 4 Ac...

Страница 24: ...5 Reserved 6 Reserved Reserved Instance 9 Versions and Alarm strings Attribute ID Description Type Value 1 Name Byte String Versions Alarms Warnings 2 Data type 4 char String of 1 39 char 3 Elements...

Страница 25: ...ly 5 Data value Integer MC100 Firmware version 6 Data value Integer MC100 Firmware build no 7 Data value Integer Pump HW and SW Read 8 N A Integer The data value for attribute 5 is 4 BCD digits 3 MSB...

Страница 26: ...be 8 5 Tube 9 Tube 10 The values in the table are the inner diameter of the tube multiplied by 10 Example Tube 3 32 equals an inner diameter of 3 2 mm NB Tube diameter 0 denotes no tube in that entry...

Страница 27: ...in and max values Data structure for Instance 15 Double Integer 1 Volume 2 Tube 3 Speed 4 Acceleration 5 Reverse 6 Density Instance 16 Tube table diameters Attribute ID Description Type Value 1 Name B...

Страница 28: ...Byte String Tubes Steps ml 2 Data type Integer Integer 3 Elements 10 4 Access Read Only 5 Data value See Table below 6 N A Integer 7 N A Integer Read 8 N A Integer Data structure for Instance 17 Doub...

Страница 29: ...gation or new initialization must be done 4 Attempt to access not connected pump 5 Reverse direction not available Pump command Bit 5 Direction set for one direction pump 6 Unstable FlexNet Check pump...

Страница 30: ...d serial mode 8 2 1 Warnings Warning no Warning description Action 0 No pending warnings 1 Fill volume out of range 2 Tube number is not in table 3 Speed setting is out of range 4 Acceleration setting...

Страница 31: ...with the Alarm but shortly after starts the reset sequence and starts up again without the alarm 03 3 Turn power OFF and turn dipswitch 8 back to OFF 4 Turn power ON again and confirm that the alarm...

Страница 32: ...PCB s 1 Power OFF for the 24V to the Module 2 Remove all cables attached the MC100 3 To access the 2 circuit boards remove the front cover by removing the 4 countersunk pozidrive screws and the front...

Страница 33: ...con dk 10 3 The WEEE system WEEE stands for Waste Electrical and Electronic Equipment and the term is used commonly throughout the EU for waste from electrical and electronic equipment EEE The WEEE Di...

Страница 34: ...d i e all Pumps use same volume tube size speed etc Calibration must be carried out for the individual Pumps by first selecting the pump number via MC100 control bits as in Individual Mode and then se...

Страница 35: ...36 12 Appendix 2 12 1 Tube tables 12 1 1 1 PD12 Tube Number Inner Diameter mm 1 0 8 2 1 6 3 3 2 4 4 8 5 6 0 6 8 0 7 1 2 8 0 5 12 1 1 2 PD22 Tube Number Inner Diameter mm 1 3 0 2 5 0 3 6 5 4 8 0 5 10...

Страница 36: ...EN61000 6 2 Electromagnetic compatibility EMC Part 6 2 Generic standards Immunity for industrial environments EN55022 Information technology equipment Radio disturbance characteristics Limits and met...

Отзывы: