Version 1.0
PN: 2042-8198
Page 55 of 75
DN: 10-32813
•
The battery voltage may be monitored periodically via communications, but should not be logged or
actively accessed. This may pre-maturely drain the battery.
•
Keeps track of the power-off time (seconds) in battery-backed RAM.
Real-Time Clock 36 (0x24), Instance 1
Member ID
Member Name
Data Type
Access
NV
Min
Max
Default
Comments / Description
1
0x01
Time of Day (s)
UINT32
R
0
86399
3
0x03
Hour
UINT8
RW
B
0
23
0
4
0x04
Minute
UINT8
RW
B
0
59
0
5
0x05
Seconds
UINT8
RW
B
0
59
0
6
0x06
Month
UINT8
RW
B
1
12
1
7
0x07
Day
UINT8
RW
B
1
31
1
8
0x08
Year
UINT16
RW
B
2000
2135
2018
9
0x09
Current Time
STRING
R
Format "HH:MM:SS AM|PM"
10
0x0A
Current Date
STRING
R
Format "Day Month DD, YYYY"
13
0x0D
Power Off Time (s)
UINT32
R
15
0x0F
GUI Location X
UINT16
RW
F
0
65535
0
Object X location on GUI canvas
16
0x10
GUI Location Y
UINT16
RW
F
0
65535
0
Object Y location on GUI canvas
17
0x11
Time Zone Offset (hrs)
SINT8
RW
F
-12
12
0
18
0x12
DST
ENUM16
RW
F
62
62: Off
63: On
19
0x13
Timestamp
UINT32
R
Number of seconds elapsed since
00:00 hours, January 1, 2000 (TZ
= UTC±00:00)
20
0x14
Time Zone Offset (min)
UINT8
RW
F
0
59
0
Only: 0, 15, 30, 45
21
0x15
Battery Voltage (V)
FLOAT
R
1.65
3.6
LED
The LED object is new with the RMA PLUS. There are four user-defined, bi-color LEDs on the face of the
device. By default, three of the LEDs indicate the state of a USBD MSC drive. This may be changed to
suit the application.
Functions
1.
Off
: The LED will be OFF.
2.
Output
: Choose a source, color (red, green or yellow), and fixed time-base to indicate the state of
any produced data point connected to the high-speed Watbus system. NOTE: Analog values are a
percentage. Anything greater than 100 will be full ON.
3.
C
: Choose a color for the LED. It will be ON if the display units are °C, OFF otherwise.
4.
F
: Choose a color for the LED. It will be ON if the display units are °F, OFF otherwise.
5.
State
: Choose a source, color and value for each of the eight states (if desired) and fixed time-base.
If the source value equals the value in one of the states, the LED will be assigned the state color.
6.
MICRO SD
7.
NOR FLASH
8.
RAM DISK
USBD MSC LED States
LED
MSC State
Description
GRN
Disconnected
Disconnected from host
RED Flashing
Start
Start the LUN (request lock)
RED
Ready
LUN ready (host locked)
YEL Flashing
Stop
Stop the LUN (request unlock)
YEL
Stopped
LUN stopped / ejected (firmware locked)
Содержание RMA PLUS RMAP-2A Series
Страница 1: ...Version 1 0 PN 2042 8198 Page 1 of 75 DN 10 32813 RMA PLUS User Manual...
Страница 8: ...Version 1 0 PN 2042 8198 Page 8 of 75 DN 10 32813...
Страница 11: ...Version 1 0 PN 2042 8198 Page 11 of 75 DN 10 32813 Figure 3 Ground Wire Location...
Страница 24: ...Version 1 0 PN 2042 8198 Page 24 of 75 DN 10 32813 Figure 20 RMA PLUS via USBD Eject start selected drive...
Страница 26: ...Version 1 0 PN 2042 8198 Page 26 of 75 DN 10 32813 Figure 22 RMA PLUS via USBD MICRO SD root...
Страница 27: ...Version 1 0 PN 2042 8198 Page 27 of 75 DN 10 32813 Figure 23 RMA PLUS via USBD NOR FLASH root...
Страница 29: ...Version 1 0 PN 2042 8198 Page 29 of 75 DN 10 32813 Figure 25 RMA PLUS via USBD Eject stop selected drive...
Страница 42: ...Version 1 0 PN 2042 8198 Page 42 of 75 DN 10 32813 Figure 37 Default web page Index html...
Страница 75: ...Version 1 0 PN 2042 8198 Page 75 of 75 DN 10 32813...