background image

L1

L2

3

Limit Control

Contacts

(if req

u

ired)

Semicond

u

ctor

F

u

ses

4

Phase-to-phase
200V

Å

 (ac)

and abo

v

e

Heater

2

1

5

6

7

8

9

10

+

Gro

u

nd

Tank

Filter

5A

5A

N

e

u

tral

Phase-to-ne

u

tral

100V

Å

 (ac)

and abo

v

e

L1

Limit Control

Contact

(if req

u

ired)

Single-phase Output and Input Wiring

ç

WARNINGS:

Ó

1

WARNING: Use National Electric (NEC) or other country-specific standard wiring practices to install and operate the DIN-A-MITE.
Failure to do so may result in damage to equipment and property, and/or injury or loss of life.

Ó

2

WARNING: Wiring examples show L2 in phase-to-phase, 200 V

Å

(ac) and above configuration. In phase-to-neutral, 100 V

Å

(ac) and

above  applications, L2 is neutral and must not be fused or switched. Failure to follow this guideline could result in personal injury or
death.

Ó

3

WARNING: Only authorized and qualified personnel should be allowed to install and perform preventive and corrective maintenance on
this unit. Failure to do so could result in damage to equipment, and personal injury or death.

4 WARNING: Hot surface, do not touch the heat sink. Failure to follow this guideline could result in personal injury.

Ó

1

Ó

2

Ó

3

4

WATLOW DIN-A-MITE Style A User's Guide

3

NOTE:

Grounding

Use a grounding conductor 
terminal plate (fork terminal) 
having upturned lugs or the 
equivalent to hold the wire in 
position. Maximum 6 mm

2

(10 

AWG) wire.

Fusing

Recommended fusing options (see 
page 6) to meet 200KA SCCR, type 
1 and 2 approved.  All other fuse 
and SCR combinations are defaulted 
to 5KA SCCR per UL508A and NEC 
guidelines.

Torque Guidelines

• Properly torque line and load 

terminals to 1.4 Nm (12 in-lb).

• Retorque after 48 hours to 

minimize wire cold flow.

• Retorque line and load terminals 

every 3 to 6 months.

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Содержание DIN-A-MITE A

Страница 1: ...ion to verify that your selections are consistent with your application inputs outputs alarms limits etc If the problem persists after checking the configuration of the controller you can get technica...

Страница 2: ...failure 2 WATLOW DIN A MITE Style A User s Guide 4 Top 98 mm 3 87 in 50 mm 1 97 in 13 mm 0 50 in Side by side clearance for wire routing DIN EN 50022 35 mm by 7 5 mm Rail Clipping Distance 34 7 mm 1...

Страница 3: ...ized and qualified personnel should be allowed to install and perform preventive and corrective maintenance on this unit Failure to do so could result in damage to equipment and personal injury or dea...

Страница 4: ...4 PM6C2CA ALAJAAA 98 99 CC CA CB B5 D6 D5 X1 W1 Y1 T1 S1 R1 L4 K4 T2 S2 R2 Coil L1 Neutral DA10 24C0 0000 5 6 7 8 9 10 Heater System Wiring Example 1 2 3 www GlobalTestSupply com Find Quality Product...

Страница 5: ...230V ac 1F25 14 0019 Table 1 DIN A MITE EMI Filters WARNING The tank filters specified may suppress desirable communications carried on power lines in the 150 to 250 kHz region The filters may suppre...

Страница 6: ...ircuit before placing the DIN A MITE into service DC Contactor 4 5 to 32V dc maximum current 4 5V dc is 8 mA per leg Loop powered linear current 4 to 20 mA dc loop powered Input Type F0 option only Re...

Страница 7: ...2009 Harmonic Current Emissions Reviewed to IEC 61000 3 2 2014 EN 61000 3 3 2013 Voltage Fluctuations and Flicker3 NOTES 1 Use of an external filter is required to comply with conducted emissions lim...

Отзывы: