background image

DIN-A-MITE Style A

, solid-state power controller

Part Num

b

er 

D A 1 0

-  __   __  __   __  - 0 __  __  __

Phase

1  = 1-phase, 1 controlled leg

Cooling & Current Rating

0  = Natural convection current rating

18A @ 50°C

Note: See derating curve for current rating

at other temperatures.

Line & Load Voltage

02 = 24 to 48

V

Å

(ac)

24 = 120 to 240

V

Å

(ac)

60 = 277 to 600

V

Å

(ac)

Input Type

C0 = 4.5 to 32

V

Î

(dc) contactor

K1 = 24 to 48

V

Å

(ac) contactor

K2 = 100 to 120

V

Å

(ac) contactor

K3 = 200 to 240

V

Å

(ac) contactor

F0 = 4 to 20 mA

Î

(dc) proportional

Manual Language

0  = English
1  = German
2  = Spanish
3  = French

Custom Parts Designation

00 = Standard parts

Output Rating Curve

30

25

20

15

10

5

0

25 30 35 40 45 50 55 60 65 70 75 80 85

Current (Amps) into 

a Resistive Load

Maximum Ambient Temperature (

°

C)

Ratings at 100% on

Specifications

Ordering Information

Operator Interface

Command signal input

Input indicator LED

Amperage

Single-phase, 18 A output maximum at 50°C (122°F) into a resistive
load. See the output rating curve.

Maximum I

2

t for fusing: 4,000 A

2

sec

Holding current: 100 mA minimum

Latching current: 200 mA minimum

Power dissipation: 1.2 watts per amp switched

200KA SCCR with recommended fusing

Line Voltage

24 to 48

V

Å

(ac) units: 20

V

Å

(ac) minimum to 53

V

Å

(ac) maximum

120 to 240

V

Å

(ac) units: 48

V

Å

(ac) minimum to 

265 

V

Å

(ac) maximum

277 to 600

V

Å

(ac) units: 85

V

Å

(ac) minimum to 660

V

Å

(ac)

maximum

Off-state leakage: 1 mA at 25°C (77°F) maximum

50/60 Hz. independent

Control Mode, Zero Cross

Input Control Signal Type C: 

V

Î

(dc) input contactor.

To increase service life, the cycle time should 

b

e less

than 3 seconds.

Input Control Signal Type K: 

V

Å

(ac) input contactor. To increase

service life, the cycle time should 

b

e less than 3 seconds.

Input Control Signal Type F: 4 to 20 mA

Î

(dc)

proportional varia

b

le time 

b

ase control.

Input Command Signal

AC contactor

24 

V

Å

±10%, 120

V

Å

+10%/-25%, 240

V

Å

(ac) +10%/-25% @ 25 mA

maximum per controlled leg

Do not use the DIN-A-MITE 

V

ac-input models with a temperature

controller that includes an RC snu

bb

er circuit across its output.

Remove the RC snu

bb

er circuit 

b

efore placing the DIN-A-MITE into

service.

DC Contactor

4.5 to 32

V

Î

(dc): maximum  current @ 4.5

V

Î

(dc) is 8 mA per leg.

Loop powered linear current

4 to 20 mA

Î

(dc): loop-powered. Input Type F0 option only.

(Re

q

uires current source with 8.0

V

Î

(dc) availa

b

le. No more than two

DIN-A-MITE inputs can 

b

e connected in series.) 

Agency Approvals

ROHS

UL® 508-listed and C-UL® File E73741

CE with proper filter:
EN 61326 Industrial Immunity Class A Emissions
EN 50178 Safety re

q

uirements

Input Terminals

Compression: Will accept 0.2 to 1.5 mm

2

(24 to 16 AWG) wire

Tor

q

ue to 0.5 Nm (4.4 in-l

b

) maximum with a 3.5 mm (1/8 in) 

b

lade

screwdriver

Strip 5.5 mm (0.22 in)

Line and load wire insulation rating must 

b

e 75C or higher, copper

conductor only

Line and Load Terminals

Compression: Will accept 0.75 to 10 mm

2

(18 to 8 AWG) wire

Tor

q

ue to 1.4 Nm (12 in-l

b

) with a 6.4 mm (1/4 in) 

b

lade screwdriver,

or Type 1A #2 Pozi driver

Retor

q

ue after 48 hours to minimize wire cold flow

Retor

q

ue line and load terminals every 3 to 6 months

Strip 6.4 mm (0.25 in)

Operating Environment

Up to 80°C. See the output rating curve chart for your application.

0 to 90% RH (relative humidity), non-conden sing

6  

WATLOW DIN-A-MITE Style A User's Guide

Installation only tested to 3,000 meters

Units are suita

b

le for “Pollution degree 2”

Contactor 

V

(ac/dc) To increase service life, the cycle time should 

b

e less

than three seconds

Mounting

Options include DIN rail or standard 

b

ack panel mounting.

The DIN rail specification is: DIN EN 50022, 35 mm 

b

y 7.5 mm

Minimum clipping distance: 34.8 mm (1.37 in)

Maximum clipping distance: 35.3 mm (1.39 in)

Mount the cooling fins vertically

Weight

323 grams (11.40 oz)

Recommended Fuse and Fuse Holder

Fuse

Watlow

Semiconductor

Bussmann

Semiconductor

Watlow

Combination

Bussmann

Combination

20A

17-8020

FWC20A10F

0808-0325-0020

DFJ20

25A

17-8025

FWC25A14F

0808-0325-0025

DFJ25

32A

17-8030

FWP32A14F

0808-0325-0030

DFJ30

40A

17-8040

FWP40A14F

- - - -

- - - -

Holders (single)

Fuse

Watlow

Bussmann

Ferraz

Bussmann

Combination

20A

17-5110

- - - -

USM1i

- - - -

25A

17-5110

- - - -

USM1i

- - - -

32A

17-5114

- - - -

USM141i

- - - -

40A

17-5114

- - - -

USM141i

- - - -

15 to 30A

0808-0326-1530

- - - -

- - - -

CH30J1i

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Содержание DIN-A-MITE A

Страница 1: ...ion to verify that your selections are consistent with your application inputs outputs alarms limits etc If the problem persists after checking the configuration of the controller you can get technica...

Страница 2: ...failure 2 WATLOW DIN A MITE Style A User s Guide 4 Top 98 mm 3 87 in 50 mm 1 97 in 13 mm 0 50 in Side by side clearance for wire routing DIN EN 50022 35 mm by 7 5 mm Rail Clipping Distance 34 7 mm 1...

Страница 3: ...ized and qualified personnel should be allowed to install and perform preventive and corrective maintenance on this unit Failure to do so could result in damage to equipment and personal injury or dea...

Страница 4: ...4 PM6C2CA ALAJAAA 98 99 CC CA CB B5 D6 D5 X1 W1 Y1 T1 S1 R1 L4 K4 T2 S2 R2 Coil L1 Neutral DA10 24C0 0000 5 6 7 8 9 10 Heater System Wiring Example 1 2 3 www GlobalTestSupply com Find Quality Product...

Страница 5: ...230V ac 1F25 14 0019 Table 1 DIN A MITE EMI Filters WARNING The tank filters specified may suppress desirable communications carried on power lines in the 150 to 250 kHz region The filters may suppre...

Страница 6: ...ircuit before placing the DIN A MITE into service DC Contactor 4 5 to 32V dc maximum current 4 5V dc is 8 mA per leg Loop powered linear current 4 to 20 mA dc loop powered Input Type F0 option only Re...

Страница 7: ...2009 Harmonic Current Emissions Reviewed to IEC 61000 3 2 2014 EN 61000 3 3 2013 Voltage Fluctuations and Flicker3 NOTES 1 Use of an external filter is required to comply with conducted emissions lim...