DIN-A-MITE Style A
, solid-state power controller
Part Num
b
er
D A 1 0
- __ __ __ __ - 0 __ __ __
Phase
1 = 1-phase, 1 controlled leg
Cooling & Current Rating
0 = Natural convection current rating
18A @ 50°C
Note: See derating curve for current rating
at other temperatures.
Line & Load Voltage
02 = 24 to 48
V
Å
(ac)
24 = 120 to 240
V
Å
(ac)
60 = 277 to 600
V
Å
(ac)
Input Type
C0 = 4.5 to 32
V
Î
(dc) contactor
K1 = 24 to 48
V
Å
(ac) contactor
K2 = 100 to 120
V
Å
(ac) contactor
K3 = 200 to 240
V
Å
(ac) contactor
F0 = 4 to 20 mA
Î
(dc) proportional
Manual Language
0 = English
1 = German
2 = Spanish
3 = French
Custom Parts Designation
00 = Standard parts
Output Rating Curve
30
25
20
15
10
5
0
25 30 35 40 45 50 55 60 65 70 75 80 85
Current (Amps) into
a Resistive Load
Maximum Ambient Temperature (
°
C)
Ratings at 100% on
Specifications
Ordering Information
Operator Interface
•
Command signal input
•
Input indicator LED
Amperage
•
Single-phase, 18 A output maximum at 50°C (122°F) into a resistive
load. See the output rating curve.
•
Maximum I
2
t for fusing: 4,000 A
2
sec
•
Holding current: 100 mA minimum
•
Latching current: 200 mA minimum
•
Power dissipation: 1.2 watts per amp switched
•
200KA SCCR with recommended fusing
Line Voltage
•
24 to 48
V
Å
(ac) units: 20
V
Å
(ac) minimum to 53
V
Å
(ac) maximum
•
120 to 240
V
Å
(ac) units: 48
V
Å
(ac) minimum to
265
V
Å
(ac) maximum
•
277 to 600
V
Å
(ac) units: 85
V
Å
(ac) minimum to 660
V
Å
(ac)
maximum
•
Off-state leakage: 1 mA at 25°C (77°F) maximum
•
50/60 Hz. independent
Control Mode, Zero Cross
•
Input Control Signal Type C:
V
Î
(dc) input contactor.
To increase service life, the cycle time should
b
e less
than 3 seconds.
•
Input Control Signal Type K:
V
Å
(ac) input contactor. To increase
service life, the cycle time should
b
e less than 3 seconds.
•
Input Control Signal Type F: 4 to 20 mA
Î
(dc)
proportional varia
b
le time
b
ase control.
Input Command Signal
•
AC contactor
24
V
Å
±10%, 120
V
Å
+10%/-25%, 240
V
Å
(ac) +10%/-25% @ 25 mA
maximum per controlled leg
•
Do not use the DIN-A-MITE
V
ac-input models with a temperature
controller that includes an RC snu
bb
er circuit across its output.
Remove the RC snu
bb
er circuit
b
efore placing the DIN-A-MITE into
service.
•
DC Contactor
4.5 to 32
V
Î
(dc): maximum current @ 4.5
V
Î
(dc) is 8 mA per leg.
•
Loop powered linear current
4 to 20 mA
Î
(dc): loop-powered. Input Type F0 option only.
(Re
q
uires current source with 8.0
V
Î
(dc) availa
b
le. No more than two
DIN-A-MITE inputs can
b
e connected in series.)
Agency Approvals
•
ROHS
•
UL® 508-listed and C-UL® File E73741
•
CE with proper filter:
EN 61326 Industrial Immunity Class A Emissions
EN 50178 Safety re
q
uirements
Input Terminals
•
Compression: Will accept 0.2 to 1.5 mm
2
(24 to 16 AWG) wire
•
Tor
q
ue to 0.5 Nm (4.4 in-l
b
) maximum with a 3.5 mm (1/8 in)
b
lade
screwdriver
•
Strip 5.5 mm (0.22 in)
•
Line and load wire insulation rating must
b
e 75C or higher, copper
conductor only
Line and Load Terminals
•
Compression: Will accept 0.75 to 10 mm
2
(18 to 8 AWG) wire
•
Tor
q
ue to 1.4 Nm (12 in-l
b
) with a 6.4 mm (1/4 in)
b
lade screwdriver,
or Type 1A #2 Pozi driver
•
Retor
q
ue after 48 hours to minimize wire cold flow
•
Retor
q
ue line and load terminals every 3 to 6 months
•
Strip 6.4 mm (0.25 in)
Operating Environment
•
Up to 80°C. See the output rating curve chart for your application.
•
0 to 90% RH (relative humidity), non-conden sing
6
WATLOW DIN-A-MITE Style A User's Guide
•
Installation only tested to 3,000 meters
•
Units are suita
b
le for “Pollution degree 2”
•
Contactor
V
‡
(ac/dc) To increase service life, the cycle time should
b
e less
than three seconds
Mounting
Options include DIN rail or standard
b
ack panel mounting.
•
The DIN rail specification is: DIN EN 50022, 35 mm
b
y 7.5 mm
•
Minimum clipping distance: 34.8 mm (1.37 in)
•
Maximum clipping distance: 35.3 mm (1.39 in)
•
Mount the cooling fins vertically
Weight
•
323 grams (11.40 oz)
Recommended Fuse and Fuse Holder
Fuse
Watlow
Semiconductor
Bussmann
Semiconductor
Watlow
Combination
Bussmann
Combination
20A
17-8020
FWC20A10F
0808-0325-0020
DFJ20
25A
17-8025
FWC25A14F
0808-0325-0025
DFJ25
32A
17-8030
FWP32A14F
0808-0325-0030
DFJ30
40A
17-8040
FWP40A14F
- - - -
- - - -
Holders (single)
Fuse
Watlow
Bussmann
Ferraz
Bussmann
Combination
20A
17-5110
- - - -
USM1i
- - - -
25A
17-5110
- - - -
USM1i
- - - -
32A
17-5114
- - - -
USM141i
- - - -
40A
17-5114
- - - -
USM141i
- - - -
15 to 30A
0808-0326-1530
- - - -
- - - -
CH30J1i
www.
GlobalTestSupply
.com
Find Quality Products Online at: