Watlow D4T Data Logger
•
90
•
Chapter 5 Function Reference
Signals
Direction
Label
Type
Function
Receivers
- - - - Digital
Input to logic function
- - - - Digital
Input to logic function
- - - - Digital
Input to logic function
- - - - Digital
Input to logic function
- - - - Digital
Input to logic function
- - - - Digital
Input to logic function
- - - - Digital
Input to logic function
- - - - Digital
Input to logic function
Transmitter - - - - Digital
True when all the inputs are true, otherwise false
Function
To detect when all the inputs are true, set Function to
And
.
Error Handling
Use Error Handling to select the output's value and error status when the function cannot de-
finitively determine the result.
Options:
• True Good
: output's value is true (on) with no error
• True Bad
: output's value is true (on) and has an error
• False Good
: output's value is false (off) with no error
• False Bad
: output's value is false (off) and has an error
Nand
If any input is false (off, 0%), the output is true (on, 100%). If all
inputs are true (on, 100%), the output is false (off, 0%).
Only connected inputs are considered by the logic operation; in-
puts that are not connected are ignored. The truth table at the
right illustrates the outcomes for three inputs.
Inputs
Output
FFF
T
FFT
T
FTF
T
FTT
T
TFF
T
TFT
T
TTF
T
TTT
F
F = False (0%, off)
T = True (100%, on)