Active if Output 3 hardware is
present (97 _ _-_ _ D _-_ _ _ _),
Output 3 (Output 3 Menu) is
set to
[``AL]
(Alarm) and
Setup Page Lock (Lockout
Menu) is not set to
[hide]
.
741 r/w
[Al`O]
[Al`O]
alarm condition
de-energizes output
(fail safe operation)
(0)
[Al`C]
alarm condition
energizes output (1)
[Lgc3]
Alarm Logic 3
Selects alarm 3
output condition in
the alarm state.
Active if Output 3 hardware is
present (97 _ _-_ _ D _-_ _ _ _),
Output 3 (Output 3 Menu) is
set to
[``AL]
(Alarm) and
Setup Page Lock (Lockout
Menu) is not set to
[hide]
.
740 r/w
[both]
[both]
both (0)
[hi``]
high (1)
[lo``]
low (2)
[Sid3]
Alarm Active
Sides 3
Selects alarm 3 side
option.
Active if Output 3 hardware is
present (97 _ _-_ _ D _-_ _ _ _),
Output 3 (Output 3 Menu) is
set to
[``AL]
(Alarm) and
Setup Page Lock (Lockout
Menu) is not set to
[hide]
.
739 r/w
[``no]
[``no]
no action (0)
[`yes]
silence 3
enabled (1)
[SiL3]
Silencing 3
Enables Silence 3.
Active if Output 3 hardware is
present (97 _ _-_ _ D _-_ _ _ _),
Output 3 (Output 3 Menu) is
set to
[``AL]
(Alarm) and
Setup Page Lock (Lockout
Menu) is not set to
[hide]
.
738 r/w
[``no]
[``no]
no action (0)
[`Yes]
latching
enabled (1)
[Lat3]
Latching 3
Enables Alarm 3
Latching.
Active if Output 3 hardware is
present (97 _ _-_ _ D _-_ _ _ __ ,
Output 3 (Output 3 Menu) is
set to
[``AL]
(Alarm) and
Setup Page Lock (Lockout
Menu) is not set to
[hide]
.
737 r/w
3
1 to 9999
[hys3]
Alarm Hysteresis 3
Sets the switching
hysteresis for the
alarm output. This
defines a band on
the inside of the
alarm set point.
When the process
temperature is in
this band, the alarm
state will not
change.
Active if Output 3 hardware is
present (97 _ _-_ _ D _-_ _ _ _),
Output 3 (Output 3 Menu) is
set to
[``AL]
(Alarm) and
Setup Page Lock (Lockout
Menu) is not set to
[hide]
.
734 r/w
[`OFF]
[`OFF]
off (0)
[``AL]
alarm (1)
[Ot`3]
Output 3
Selects type of
output 3.
[Out3]
Output 3 Menu
[`set]
Setup Page
Display
Parameter
Range
Default
Modbus
Conditions for
Address
Parameters to Appear
read/write
Wa t l o w S e r i e s 9 7
P a r a m e t e r s
■
6 . 1 1
Setup Page / Output 3 Menu
NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.