background image

 

                        

RUI/Gateway & Modbus

®

 TCP  

 

      Configuration & Programming Example  

 

                 Using KEPServerEX 4.0 

Watlow  
1241 Bundy Blvd 
Winona, MN 55987 
Telephone: 507-494-5656 
© 2008 Watlow Electric Mfg Co                                16 

FM 4/08 

 

 

34.  To better understand the following discussion and examples download and read the section 

entitled “User Programmable Memory Blocks” found in the EZ-ZONE

®

 PM Communications 

user manual. 

 

 

 

 

 

When using the RUI/Gateway equipped with Modbus

® 

TCP or Modbus

®

 RTU and while 

communicating with EZ-ZONE

®

 

*

PM controls a block of 40 pointers or 80 words has been 

created to serve as the “Assembly Definition Addresses” and another group of 40 elements or 
80 words has been defined as the “Assembly Working Addresses”. The Assembly Definition 
Addresses are user configurable. Once configured with the Modbus

®

 registers of choice, the 

corresponding Assembly Working Addresses assume that particular parameter as 
programmed, and will then reflect that parameters actual value. What this means then is that 
the user can configure a contiguous block of 40 elements or 80 words to any available 
parameter of their liking. It is recommended that when doing this configuration that the 
parameters data type be considered. It is much easier to set up a contiguous block of words 
of the same data type.  

 

 

Note: 

 

If the user sets any of the EZ-ZONE

®

 PM controls back to factory defaults this assembly for 

that control will set to the factory defaults as well.  

 
 

 

  

 

 
 
35.  In step 24 we defined the maximum number of words that can be read as 32. The maximum 

number of words Modbus

® 

allows to be read at one time is 120 or 240 bytes, so all 80 words 

could be read and or written to if so desired. Due to this previous entry (step 24) in order to 
read the low order 40 words there were two read tags configured, 20 words each defining 
them as “Low order Assembly 1 & Low order assembly2”. Likewise, the same was done for 
the upper 40 words where they are defined as “High order Assembly 1 & High order 
Assembly2”. The screen shot below was duplicated 3 more times simply changing the names 
and addresses to create the tags mentioned above.

 

  
 
 
 
 

* The EZ-ZONE

®

 ST does not support programmable memory blocks. However, any 

ST parameter that is available over Modbus

®

 can be accessed in a similar manner 

as was described in step 29. 

Содержание RUI/Gateway

Страница 1: ...ady been done in two other published EZ ZONE user manuals For instance if needing assistance in setting the RUI Gateway IP Internet Protocol address or if you are simply looking for general informatio...

Страница 2: ...ettings will need to be entered Further explanation of these prompts and their associated enumerated values will follow 6 After completing the configuration as shown above as well as your Com 1 settin...

Страница 3: ...ramming Example Using KEPServerEX 4 0 Watlow 1241 Bundy Blvd Winona MN 55987 Telephone 507 494 5656 2008 Watlow Electric Mfg Co 3 FM 4 08 9 Provide a name for the channel 10 In this example the device...

Страница 4: ...ple Using KEPServerEX 4 0 Watlow 1241 Bundy Blvd Winona MN 55987 Telephone 507 494 5656 2008 Watlow Electric Mfg Co 4 FM 4 08 11 Select the appropriate hardware network adapter used on the network 12...

Страница 5: ...94 5656 2008 Watlow Electric Mfg Co 5 FM 4 08 13 The next selection allows for multiple masters on the network When multiple masters exist on a network talking reading writing to the same slaves possi...

Страница 6: ...ample Using KEPServerEX 4 0 Watlow 1241 Bundy Blvd Winona MN 55987 Telephone 507 494 5656 2008 Watlow Electric Mfg Co 6 FM 4 08 15 Once the channel configuration is complete it is now time to configur...

Страница 7: ...7 FM 4 08 17 Recall that in steps 1 3 it was said that there are other configuration steps that need to be addressed that are not covered in this paper As an example of those parameters that need to b...

Страница 8: ...g KEPServerEX 4 0 Watlow 1241 Bundy Blvd Winona MN 55987 Telephone 507 494 5656 2008 Watlow Electric Mfg Co 8 FM 4 08 19 If communications fail between KEPServerEX and RUI Gateway stop polling device...

Страница 9: ...ration Programming Example Using KEPServerEX 4 0 Watlow 1241 Bundy Blvd Winona MN 55987 Telephone 507 494 5656 2008 Watlow Electric Mfg Co 9 FM 4 08 21 Use the defaults for port number and IP protocol...

Страница 10: ...6 2008 Watlow Electric Mfg Co 10 FM 4 08 23 The graphic below shows the default Modbus word order which also represents the default Modbus word order for the RUI Gateway Low High 24 Coil access is not...

Страница 11: ...xample Using KEPServerEX 4 0 Watlow 1241 Bundy Blvd Winona MN 55987 Telephone 507 494 5656 2008 Watlow Electric Mfg Co 11 FM 4 08 25 KEPServerEX allows for imported tags via a text file 26 Any tag ret...

Страница 12: ...tant to keep in mind that there is a unique Modbus address set aside for that member As an example note that as found in the EZ ZONE PM Communications user manual under the Operations Page Process Val...

Страница 13: ...61 offset 10000 PV1 of PM4 415361 offset 15000 29 Now that we know the finer details of the Modbus offset prompts lets go back to KEPServerEX and look closer at the tag configuration and properties As...

Страница 14: ...bles are configured and made available to KEPServerEX a similar screen as shown below should be displayed 32 The above examples represent tags for inputs where a similar procedure beginning at step 29...

Страница 15: ...e addresses given in defining the CLSP for each of the four PM controls 33 In the screen shot above we now see a series of inputs and outputs that have been configured within KEPServerEX To test the l...

Страница 16: ...or 80 words to any available parameter of their liking It is recommended that when doing this configuration that the parameters data type be considered It is much easier to set up a contiguous block...

Страница 17: ...ve as well the enumerated values shown in each of these Modbus registers represents the actual Modbus registers for each of the 80 corresponding Assembly Working Addresses To find what these Modbus re...

Страница 18: ...sing KEPServerEX 4 0 Watlow 1241 Bundy Blvd Winona MN 55987 Telephone 507 494 5656 2008 Watlow Electric Mfg Co 18 FM 4 08 38 Changing an element in the assembly is EZ A new tag was created as shown be...

Страница 19: ...f User Programmable Memory Blocks Again focus on the address below This particular address represents the Assembly Working Address for pointer 12 40 Now that the tags are created execute the OPC quick...

Страница 20: ...Telephone 507 494 5656 2008 Watlow Electric Mfg Co 20 FM 4 08 42 Lastly in the screen shot below notice that the 12th pointer has indeed been changed to Idle Set Point circle and the tag created to re...

Отзывы: