Setup
8LS User’s Guide 63
Output Type
Use this menu to to set the output type.
Selectable values:
The next table shows the available output types.
Cycle Time
Use this menu to set the Cycle Time for the TP outputs.
Selectable values:
1-255 seconds.
NOTE
This menu appears only if you set the output type
to TP.
Display
Code
Output Type
Definition
TP
Time Proportioning
Percent output is con-
verted to a percent duty
cycle over the pro-
grammed cycle time.
DZC
Distributed Zero Cross-
ing. Available only on
secondary (50 pin Ribbon
output).
Output On/Off state calcu-
lated for every AC line
cycle.
O/F
On/Off
Output either full On or full
Off.
ANA
Analog 0-5 Vdc or 4-20
mAdc.
Available only on pri-
mary (terminal).
Output is proportional over
the range of the voltage or
current output selected by
Dip switch setting.
1
2
3
4
5
6
7
8
LOOP
PROCESS
UNITS
ALARM
SETPOINT
STATUS OUTPUT%
1 OUTPUTS
TYP
H
T
?
TP
1
2
3
4
5
6
7
8
LOOP
PROCESS
UNITS
ALARM
SETPOINT
STATUS OUTPUT%
1 OUTPUTS
CT ? 10
H
T