104 8LS User’s Guide
Appendix A: Ramp Soak
Continuing a profile
If a profile is holding and you want it to run, you can put it in Continue
mode.
•
Press RAMP/SOAK key repeatedly until you see the R/S mode
menu
•
While the profile is holding, the only mode you will be able select is
Cont (Continue).
•
Press YES to continue the profile, and then ENTER to advance to the
next menu.
Resetting a profile
Use this menu to reset a profile. When you reset a profile, the following
happens:
•
The profile returns to the ready segment. The PV goes to the ready
setpoint, and the ready segment events go to the state you specified
in the Edit Ready Event State menu.
•
The controller shows you the Assign Profile menu in case you would
like to assign a different profile to the loop.
To reset a profile, follow these steps:
1. Press RAMP/SOAK key repeatedly until you see the R/S mode menu
2. Press the NO key. You should see the menu below.
3. Press YES to reset the profile, and then ENTER to confirm your
choice.
1
2
3
4
5
6
7
8
LOOP
PROCESS
UNITS
ALARM
SETPOINT
STATUS OUTPUT%
1A00/20S
RESET? A
Содержание 8LS
Страница 8: ...vi 8LS User s Guide...
Страница 12: ...4 8LS User s Guide Overview...
Страница 91: ...Tuning and Control 8LS User s Guide 83...
Страница 92: ...84 8LS User s Guide Tuning and Control...
Страница 96: ...88 8LS User s Guide Troubleshooting...
Страница 128: ...120 8LS User s Guide Appendix B 8LS CP...
Страница 139: ...Glossary 8LS User s Guide 131...
Страница 140: ...Glossary 132 8LS User s Guide...