54 8LS User’s Guide
Setup
Input Type
Use this menu to configure the input sensor for each loop as one of these
input types:
•
Thermocouple types (J, K, T, S, R, B, and N)
•
RTD. Two ranges: RTD1 (Platinum class A: DIN 43760-1980,
Alpha=.00385), and RTD2 (Platinum class B: DIN 43760-1980,
Alpha=.00385).
•
Linear and Pulse inputs.
•
Skip. Scanning display doesn’t show loops you set to Skip.
Selectable range:
See the table below for the input types and ranges
available for the 8LS.
he is editing. Character editing proceeds left to right one character at a time.
Input Type
Fahrenheit
Range
Celsius
Range
J
-350 to +1400
-212 to +760
K
-450 to +2500
-268 to +1371
T
-450 to +750
-268 to +399
S
0 to +3200
-18 to +1760
R
0 to +3210
-18 to +1766
B
+150 to +3200
+66 to +1760
N
-450 to +2370
-268 to +1299
RTD1
-148.0 to +572.0
-100.0 to +300.0
RTD2
-184 to +1544
-120 to +840
Pulse
0-20 KHz
Skip
Loop is not scanned or displayed
Linear
See
Linear scaling
section in this chapter
1
2
3
4
5
6
7
8
LOOP
PROCESS
UNITS
ALARM
SETPOINT
STATUS OUTPUT%
1 INPUT
TYPE? J
Содержание 8LS
Страница 8: ...vi 8LS User s Guide...
Страница 12: ...4 8LS User s Guide Overview...
Страница 91: ...Tuning and Control 8LS User s Guide 83...
Страница 92: ...84 8LS User s Guide Tuning and Control...
Страница 96: ...88 8LS User s Guide Troubleshooting...
Страница 128: ...120 8LS User s Guide Appendix B 8LS CP...
Страница 139: ...Glossary 8LS User s Guide 131...
Страница 140: ...Glossary 132 8LS User s Guide...