15
|
217
Product Overview
Operation
AQUIS ULTRAFLOW Industrial Foam Proportioner System
Subsystem
Subsystem
Description
Description
4 Concentrate pump
These components support, control, and power the concentrate pump. The components in this subsystem include:
•
Hydraulic concentrate pump—this circulates the foam concentrate through the system.
•
Hydraulic motor—this drives the concentrate pump.
•
Hydraulic pump—this drives the hydraulic motor.
•
Hydraulic ATF reservoir—this contains the hydraulic oil supply.
•
Hydraulic ATF filter—this filters the hydraulic oil.
•
Hydraulic ATF cooler—this cools the hydraulic oil.
•
Hydraulic ATF temperature sensor—this monitors the hydraulic ATF temperature.
•
Hydraulic ATF level sensor—this monitors the hydraulic oil level in the reservoir.
•
Pressure sensor—this monitors the pressure in the concentrate line.
•
Pressure relief valve—this opens when the pressure in the line reaches a predetermined set-point.
5 Concentrate supply
This contains components that contain or supply foam concentrate for the system. The components in this subsystem
include:
•
Foam concentrate supply tank—this contains the on-board foam concentrate supply.
•
Tank-full sensor—this indicates a tank full condition to the system.
•
Tank-low sensor—this indicates a tank low condition to the system.
•
Tank level sensor—this is an installer supplied sensor and display that indicates the supply level in the tank.
•
Concentrate pump intake select valve—this is an installer supplied, 2 position valve, and additional components that
sources concentrate from an on-board tank or an off-board supply. A signal is provided to the system to ignore the on-
board tank
sensors when sourcing concentrate from an off-board supply
.
•
Concentrate strainer—this collects debris that would otherwise flow through the system.
6 Supply tank fill line
This allows you to fill the on-board tank from an external source. The components in this subsystem include:
•
Node controller—this connects to the fill valve and flowmeters.
•
Fill line control valve—this controls the flow of concentrate.
•
Magnetic flowmeter—this measures the flow of concentrate.
•
CANbus splitter and cable—this connects the node controllers to one another
•
Check valve—this prevents improper fluid flow in the line.
Содержание AQUIS ULTRAFLOW
Страница 2: ......
Страница 8: ......
Страница 216: ...Notes ...
Страница 217: ...Waterous Company 125 Hardman Avenue South South Saint Paul MN 55075 651 450 5000 www waterousco com ...