F

1031, Section 2414

Page 7 of 8

Calibration

Aquis

t

 Foam Pump

The Aquis

t

 system is able to be field calibrated using the con­

trol function buttons on the operating interface terminal (OIT),
see Figure 8.

Only units of measure, water flow and the foam percent­
age default can be field set.

A. Entering Calibration Mode

1.

Entering calibration is accomplished by using the con­
trol unit functions buttons.

2.

To enter this function, press and hold the 

SELECT 

but­

ton for minimum of five (5) seconds. The OIT will dis­
play “5 SEC”.

3.

Continue to hold the 

SELECT 

button.

4.

While the 

SELECT 

button is depressed, push the 

UP

and 

DOWN 

arrow buttons at the same time. The display

will show 

CAL 

for two (2) seconds and then display 

F1

.

5.

Use the 

UP 

button to advance to the next parameter

(F2, F3, F4).

6.

Use the 

DOWN 

button to back up to a previous para­

meter (F2, F1).

7.

To edit a parameter, press the 

SELECT 

button at the

associated Fn prompt.

B. F1 - Default Mix Percentage

1.

At the 

F1

 prompt, press the 

SELECT

 button.

2.

Use the 

UP 

and 

DOWN

 arrow buttons to select the de­

fault 

FOAM %

. The only foam % selections will be .1%,

.2%, .3%, .4%, .5%, .6%, .7%, .8%, .9%, 1.0%, 3.0%
and 6.0%.

3.

When finished, press the 

SELECT

 button to save the

displayed value.

C. F2 - Units of Measurement

The units of measurement must be selected prior to any
calibration functions. Units of measurement are U.S. Gal­
lons, Imperial Gallons and Liters.

1.

Push the 

SELECT

 button at the 

F2

 prompt. The display

will show the current setting.

2.

Use the 

UP 

and 

DOWN

 arrow buttons to select one of

the following measurement units:

·

GAL 

will select U.S. Gallons

·

IPL 

will select Imperial Gallons

·

LTR 

will select Metric Liters

3.

Pushing the 

SELECT 

button will save the displayed

selection. This will allow for calibration of the water flow
in the units of measurement selected.

D. F3 - Flow Rate Calibration

1.

Press the 

SELECT

 button at the 

F3

 prompt. The

current measured flow rate will be displayed. Es­
tablish a flow using an accurate flow measuring
device.

2.

Once this is established, press the 

UP 

 or 

 DOWN

 but­

ton to advance to the calibration step. If the displayed
flow rate is correct, press the 

SELECT

 button to return

back to the 

F3

 prompt. If there is insufficient flow, the

display will show 

LoFL

 for two (2) seconds, then return

back to the 

F3

 prompt.

3.

The display will now display 

50

 (starting value) or the

last calibration value entered.

4.

Use the 

UP 

and 

DOWN

 arrow buttons to change the

displayed value to match the actual flow rate according
to the flow measuring device. If the button is only
pressed momentarily, the display increments or decre­
ments by one (1). If the button is held, the display will
increment or decrement by five (5).

5.

Once the correct flow is achieved, pushing the 

SELECT

will save the setting and return to the 

F3

 prompt.

E. F4 - System Lock

System can be locked out after calibration and setup to
avoid accidental changing.

 WARNING

A locked out system can only be unlocked at a quali­
fied Waterous Service Center.

1.

Press the SELECT button at the F4 prompt and “EnAb”
(enabled) will be displayed.

2.

Pressing the UP button will toggle between “LoC”
(locked) and “EnAb” (enabled). Settings will not be per­
manent until the calibration settings are saved.

3.

Press the SELECT button and “F4” will be displayed.

4.

Pressing the FOAM button saves the settings, locks the
system and cannot be unlocked except at a qualified
Waterous Service Center.

F. Saving Calibration

To save all the calibration settings to flash memory, press
the 

FOAM

 button while at the 

Fn

 (n=1-4) prompt. The data

will be stored and the unit will return to normal operation.

Figure 8. Operator Interface Terminal

IL3437

Содержание Aquis Foam Manager

Страница 1: ...ice and Maintenance 6 Maintenance Schedule 6 Location of Maintenance Items 6 Advantus Foam Pump 6 Oil Fill and Drain 6 In line Foam Concentrate Strainer 6 Calibration 7 Aquis Foam Pump 7 Troubleshooting Guide 8 Foam Manager with Advantus Waterous Company 125 Hardman Avenue South South St Paul Minnesota 55075 USA 651 450 5000 Instructions subject to change without notice Visit us at www waterousco ...

Страница 2: ... with pump intake or pump discharge connec tions relieve pressure by opening drains or bleeder valves Bleeder valves should also be used while filling a hose connected to an intake with water WARNING Scalding Water Hazard May result in serious burns When operating the pump be sure to open at least one discharge valve slightly to prevent the pump from overheating If the pump runs for a few minutes ...

Страница 3: ...he ideal water to concentrate ratio for superior foam Foam Pump The 12 or 24 volt electric motor driven positive displace ment triplex plunger foam pump is equipped with an alu minum crankcase ball bearings forged brass pump body and manifold solid ceramic plungers stainless steel check valves and piston guides Buna packing and preset thermal and pressure relief valves The foam pump is rated at 2 ...

Страница 4: ...able Operation A pumper equipped with a Foam Managert foam unit can be operated in water only and or foam modes It is pos sible to pump water from one discharge and foam solution from another discharge Water Only Operations All unit operations begin with pumping water See the fol lowing instruction for details on how to operate and pump water from your Waterous fire pump F 1031 Section 2114 Operat...

Страница 5: ...P and DOWN simultaneously when the Total Product is displayed resets the Total Product accumulator to Zero Pressing both UP and DOWN simultaneously for two 2 seconds when the Flow Rate is displayed enters the MANUAL mode of operation See Manual Mode operation below Pressing both UP and DOWN simultaneously while in Mix will go to the preset default FOAM Pressing the FOAM button will alternately sta...

Страница 6: ... Flushing System Change Foam Pump Model Level from Top of Oil Fill Port Capacity Required for Oil Change Use Oil Daily or After Each Use Annually Aquis 2 5 1 4 inch 6 mm 90 quarts Total capacity is 1 0 quart Synthetic 10W 30 Mobil 1 recommended Monthly Depending on the corrosiveness of the foam concentrate to be used flushing of the foam injection circuit may be necessary Most Class A foam concen ...

Страница 7: ...ill allow for calibration of the water flow in the units of measurement selected D F3 Flow Rate Calibration 1 Press the SELECT button at the F3 prompt The current measured flow rate will be displayed Es tablish a flow using an accurate flow measuring device 2 Once this is established press the UP or DOWN but ton to advance to the calibration step If the displayed flow rate is correct press the SEL...

Страница 8: ...dition applies to tanks utilizing a common wall s between the foam tank and the water tank If a leak is confirmed repair the foam tank and flush the water tank and pump until foam is cleared Foam proportioning manifold check valve mal function If the above conditions have been corrected the final cause for foam in the water tank may be the result of a malfunctioning foam manifold check valve To tr...

Отзывы: