background image

F

1031, Section 2414

Page 2 of 8

Safety Information

Read through the safety information and operating instructions before using your Waterous Foam

Manager.

 WARNING

!

Death or serious personal injury might occur if proper

operating procedures are not followed. The pump op-

erator, as well as individuals connecting supply or dis-

charge hoses to the apparatus must be familiar with

these pump operating instructions as well as other

operating instructions and manuals for the apparatus,

water hydraulics and component limitation.

 WARNING

!

Pressure Hazard. May result in personal injury.

Prior to connection or removal of hoses, caps or other

closures with pump intake or pump discharge connec-

tions, relieve pressure by opening drains or bleeder

valves. Bleeder valves should also be used while filling

a hose connected to an intake with water.

 WARNING

!

Scalding Water Hazard. May result in serious burns.

When operating the pump, be sure to open at least

one discharge valve slightly to prevent the pump from

overheating.  If the pump runs for a few minutes com-

pletely closed, it may heat the water enough to scald

someone when the valve is opened. Overheating can

damage the packing, seals and other pump parts. If

the apparatus builder has installed a by

pass system

or other provision designed to prevent overheating,

opening a discharge valve may be unnecessary.

 WARNING

!

Hose Pressure Hazard.

May cause serious personal injury.

Use only fire hose that is rated at 200 PSI or higher

working pressure.

Содержание Aquis Foam Manager

Страница 1: ...ice and Maintenance 6 Maintenance Schedule 6 Location of Maintenance Items 6 Advantus Foam Pump 6 Oil Fill and Drain 6 In line Foam Concentrate Strainer 6 Calibration 7 Aquis Foam Pump 7 Troubleshooting Guide 8 Foam Manager with Advantus Waterous Company 125 Hardman Avenue South South St Paul Minnesota 55075 USA 651 450 5000 Instructions subject to change without notice Visit us at www waterousco ...

Страница 2: ... with pump intake or pump discharge connec tions relieve pressure by opening drains or bleeder valves Bleeder valves should also be used while filling a hose connected to an intake with water WARNING Scalding Water Hazard May result in serious burns When operating the pump be sure to open at least one discharge valve slightly to prevent the pump from overheating If the pump runs for a few minutes ...

Страница 3: ...he ideal water to concentrate ratio for superior foam Foam Pump The 12 or 24 volt electric motor driven positive displace ment triplex plunger foam pump is equipped with an alu minum crankcase ball bearings forged brass pump body and manifold solid ceramic plungers stainless steel check valves and piston guides Buna packing and preset thermal and pressure relief valves The foam pump is rated at 2 ...

Страница 4: ...able Operation A pumper equipped with a Foam Managert foam unit can be operated in water only and or foam modes It is pos sible to pump water from one discharge and foam solution from another discharge Water Only Operations All unit operations begin with pumping water See the fol lowing instruction for details on how to operate and pump water from your Waterous fire pump F 1031 Section 2114 Operat...

Страница 5: ...P and DOWN simultaneously when the Total Product is displayed resets the Total Product accumulator to Zero Pressing both UP and DOWN simultaneously for two 2 seconds when the Flow Rate is displayed enters the MANUAL mode of operation See Manual Mode operation below Pressing both UP and DOWN simultaneously while in Mix will go to the preset default FOAM Pressing the FOAM button will alternately sta...

Страница 6: ... Flushing System Change Foam Pump Model Level from Top of Oil Fill Port Capacity Required for Oil Change Use Oil Daily or After Each Use Annually Aquis 2 5 1 4 inch 6 mm 90 quarts Total capacity is 1 0 quart Synthetic 10W 30 Mobil 1 recommended Monthly Depending on the corrosiveness of the foam concentrate to be used flushing of the foam injection circuit may be necessary Most Class A foam concen ...

Страница 7: ...ill allow for calibration of the water flow in the units of measurement selected D F3 Flow Rate Calibration 1 Press the SELECT button at the F3 prompt The current measured flow rate will be displayed Es tablish a flow using an accurate flow measuring device 2 Once this is established press the UP or DOWN but ton to advance to the calibration step If the displayed flow rate is correct press the SEL...

Страница 8: ...dition applies to tanks utilizing a common wall s between the foam tank and the water tank If a leak is confirmed repair the foam tank and flush the water tank and pump until foam is cleared Foam proportioning manifold check valve mal function If the above conditions have been corrected the final cause for foam in the water tank may be the result of a malfunctioning foam manifold check valve To tr...