THE OSPREY POWER SHOWER MUST BE CONNECTED TO EARTH
ELECTRICAL HAZARD IF NOT CORRECTLY EARTHED
Use 3 core cable, 0.5mm2 area, double insulated. Access to the connecting
terminals must be made via the cable entr y as shown in Fig 11.
Connect the brown wire to
terminal marked L.
Connect the blue wire to
terminal marked N.
Cut and strip 5mm of wire,
inser t into terminal and secure with
screwdriver.
The ear th wire
must
be stripped about 12mm, carefully inser t into copper
wire securing washers; the nut and lock washer must then be firmly tightened.
Secure cable thoroughly with the cable restraint.
The Osprey power shower must be connected to a 230 Volt 50/60 Hz supply
with a switched spur fused at 3A. The switch must have a double pole disconnection
with a separation gap of at least 3mm.
Alternatively, a standard 13A plug (fused at 3A) can be used with a
switched
13A socket.
Ensure compliance with I.E.E. Wiring Regulations (BS 7671). If in doubt, seek
professional advice or assistance from a qualified electrician.
In the interests of safety it is recommended that a residual current device
(RCD) be installed in the supply circuit.
8. ELECTRICAL CONNECTIONS
Fig. 11
6
9. ELECTRICAL CONNECTIONS – Low Voltage Model
THIS IS A LOW VOLTAGE INTEGRAL POWER SHOWER (USE TRANSFORMER). DO
NOT CONNECT DIRECTLY TO 240 VOLTS. ELECTRICAL HAZARD WILL RESULT AND
THE UNIT WILL BE IRREPARABLY DAMAGED.
The low voltage unit has added electrical protection via a safety isolating
transformer. The safety isolating transformer
must
be located
outside
the bathroom
or shower area.
Do not
locate 230 Volt connections, plugs or switches within the
“wet’ area.
The safety isolating transformer can be connected to a 230 Volt 50Hz supply
with a switched spur fused at 5A. The switch must have a double pole disconnection
with a separation gap of at least 3mm. Alternatively, a standard 13A plug (fused 5A)
can be used with a switched 13 Amp socket.
Ensure compliance with I.E.E. Wiring Regulations (BS 7671).