Installation
04.12.2015
16 / 48
Copyright
2014 by: WATERKOTTE GmbH. Subject to changes.
6
Installation
Installation of the heat pump must be performed on a flat and horizontal
surface.
The unit should not be installed on a floating screed (structure-born
noise).
We recommend a concrete base.
Wall clearance left, right and on top must be at least 300 mm.
Wall clearance in rear must be at least 300 mm.
Wall clearance in front: at least 1,000 mm.
6.1
Environmental conditions for installation
Note the minimum volume of the installation room and consider the type of
the refrigerant (EN 378-1).
The room must be dry. Room temperature should be b5 °C and
+25 °C.
To facilitate maintenance, the use of a base plate is recommended. The
housing frame is to be completely supported. If support is only provided at
points, operating noise increases. To compensate for minor unevenness,
we recommend use of an approx. 10 mm thick rubber mat. Acoustics in in-
stallation rooms with rigid walls can noticeably increase operating noise.
Counter measure: acoustic insulation of one of the opposite wall or ceiling
surfaces.