ENVISION AIR COILS INSTALLATION MANUAL

General Installation Information cont.

The installer should.

Remove the seal cap from the bottom of the valve.

1. 

Turn the adjustment screw counterclockwise to increase  

2. 
 

superheat and clockwise to decrease superheat. One  

 

complete 360° turn changes the superheat approximately  

 

3-4° F. You may need to allow as much as 30 minutes  

 

 

after the adjustment is made for the system to stabilize.
Once the proper superheat setting has been achieved  

3. 
 

replace and tighten the seal cap.

WARNING: There are a total of 8 (360°) turns on 
the superheat adjustment stem from wide open 
to fully close . When adjusting the superheat stem 
counterclockwise (superheat increase) and the 
stop is reached, any further counterclockwise 
turning adjustment will damage the valve .

Condensate Drain

To facilitate condensate removal the encased and uncased 
coils must be properly plumbed. The drain line contains 
cold water and should be insulated in unconditioned 
spaces to avoid drain line condensation from dripping on 
ceiling, etc. The drain pan has a primary and auxiliary drain 
connection. The coil drain connection must be connected 
to a drain line pitched away from the unit a minimum of 
1/8” per foot to allow the condensate to flow away from 
the coil. A trap must be installed in the drain below the 
bottom of the pan to ensure free condensate flow (encased 
coils are not internally trapped). The primary condensate 
drain must be terminated to an open drain or sump. Do not 
connect the condensate drain to a closed waste system. 
An open vertical air vent should be installed to overcome 
line length, friction, and static pressure. It is recommended 
that the auxiliary drain be connected to a drain line for all 
units. The auxiliary drain should be run to an area where the 
homeowner will notice it draining. The drain line should not 
be smaller than the drain connection at the condensate pan. 
If the coil is located in an unconditional space, water in the 
trap may freeze. It is recommended that the trap material 
be of a type that will allow for the expansion of water when 
it freezes. Drain lines must be in conformance with local 
codes.

Charging the System

Refer to the installation manual supplied with the 
compressor section unit for amount of refrigerant charge 
and other important information pertaining to the charging 
of the system.

Figure 4 - 
Decrease Superheat: Open Valve 
Increase Superheat: Close Valve

1.5"

3.0"

3/4" PVC
Coupling

Vent (if needed)

3/4" PVC

1/8" per foot

Содержание Envision NHAC026

Страница 1: ...IM1618 09 09 Envision Air Coils Installation Manual Dimensional Data Installation Information Maintenance Geothermal Water Source Heat Pumps R 410A Refrigerant 2 5 Ton ENCASED UNCASED AIR COILS...

Страница 2: ......

Страница 3: ...AIR COILS INSTALLATION MANUAL Table of Contents Model Nomenclature 3 Initial Inspection 3 Safety Considerations 3 Dimensional Data 4 5 General Installation Information 6 9 Hydronic Models 10 11 Maint...

Страница 4: ...nching cloth for brazing operations and have a fire extinguisher available NOTE Local codes and regulations take precedent over any recommendations by the manufacturer In addition to conforming to man...

Страница 5: ...4 1 23 4 16 8 2 1 2 0 cm 52 8 66 0 73 9 2 2 2 2 1 9 48 3 61 2 59 4 42 7 5 3 5 1 Encased Models Refrigerant Water Connections Condensate Connections Miscellaneous J K L M N O P Q R S T U V W X Y Z AA A...

Страница 6: ...ls A B C Suction Liquid Condensate D E F G H I J K L Width Depth Height Sweat Sweat FPT NRAC026 036U in 20 0 24 9 20 7 5 8 3 8 3 4 15 0 17 5 0 7 1 3 10 0 3 0 1 7 7 0 13 3 cm 50 8 63 3 52 6 1 6 1 0 1 9...

Страница 7: ...ace air circulators may have to be replaced with multispeed blowers to upgrade the air delivery CFM when an add on coil is installed Refer to the Encased and Uncased Coil Specification table for recom...

Страница 8: ...lications follow the steps shown below Remove all access panels Remove the A coil assembly 1 and the horizontal drain pan From the vertical upflow position rotate the top of the 2 cabinet 90 to the ri...

Страница 9: ...NRAC036 5 8 OD 3 8 OD 3 4 OD 3 8 OD 3 4 OD 1 2 OD NRAC048 3 4 OD 3 8 OD 7 8 OD 3 8 OD 7 8 OD 1 2 OD NRAC060 7 8 OD 1 2 OD 7 8 OD 1 2 OD 1 1 8 OD 1 2 OD Encased and Uncased Refrigerant Line Sizing NOT...

Страница 10: ...to a drain line pitched away from the unit a minimum of 1 8 per foot to allow the condensate to flow away from the coil A trap must be installed in the drain below the bottom of the pan to ensure fre...

Страница 11: ...must be equipped with an expansion tank to allow room for the heated liquid to expand A system is considered closed when a check valve or backflow prevention valve is installed in the cold water pipe...

Страница 12: ...on the coil Filter Maintenance The air filter installed with the system must be cleaned or replaced to obtain maximum performance They should be inspected monthly under normal operating conditions an...

Страница 13: ...12 ENVISION AIR COILS INSTALLATION MANUAL Notes...

Страница 14: ...13 ENVISION AIR COILS INSTALLATION MANUAL Notes...

Страница 15: ......

Страница 16: ...9 Manufactured by WaterFurnace International Inc 9000 Conservation Way Fort Wayne IN 46809 www waterfurnace com 2009 WaterFurnace International Inc 9000 Conservation Way Fort Wayne IN 46809 9794 Water...

Отзывы: