Specifications
20
8.2 Home and Professional - Plus
Model
VH410M
VH410M-V*
VP600M
VP950M
Flow Rate
1
*
NSF Class B Certified
16mJ/cm
2
@ 70% UVT
14 gpm (53 lpm) (3.2 m
3
/hr)
-
-
US Public Health 16 mJ/
cm
2
@ 95% UVT
34 gpm (130 lpm) (7.8 m
3
/hr)
40 gpm (150 lpm) (9.0 m
3
/hr)
60 gpm (230 lpm) (13.7 m
3
/hr)
VIQUA Standard 30 mJ/
cm
2
@ 95% UVT
18 gpm (70 lpm) (4.2 m
3
/hr)
24 gpm (91 lpm) (5.5 m
3
/hr)
34 gpm (130 lpm) (7.8 m
3
/hr)
NSF/EPA 40mJ/cm
2
@
95% UVT
14 gpm (54 lpm) (3.3 m
3
/hr)
18 gpm (68 lpm) (4.1 m
3
/hr)
26 gpm (97 lpm) (5.8 m
3
/hr)
Dimension
s
Chamber
57.9 cm x 8.9 cm (22.8” x 3.5”)
78 cm x 8.9 cm (30.7” x 3.5”)
114 cm x 8.9 cm (45.0” x 3.5”)
Controller 100-250 VAC
22.3 cm x 8.1 cm x 6.4 cm
(8.8” x 3.2” x 2.5”)
22.3 cm x 8.1 cm x 6.4 cm
(8.8” x 3.2” x 2.5”)
22.3 cm x 8.1 cm x 6.4 cm
(8.8” x 3.2” x 2.5”)
Inlet/Outlet Port Size
2
Combo 3/4” FNPT/1” MNPT
1” MNPT
1.5” MNPT
Shipping Weight
7.7 kg (17 lbs)
8.6 kg (19 lbs)
13.1 kg (29 lbs)
Electrical
Voltage
3
100-240 V / 50/60 Hz
100-240 V / 50/60 Hz
100-240 V / 50/60 Hz
Max. Current
2.5 A
2.5 A
2.5 A
Power Consumption
60 W
78 W
110 W
Lamp Watts
46 W
58 W
90 W
Maximum Operating Pressure
125 psi (861 kPa)
125 psi (861 kPa)
125 psi (861 kPa)
Minimum Operating Pressure
15 psi (103 kPa)
15 psi (103 kPa)
15 psi (103 kPa)
Ambient Water Temperature
2-40 ºC (36-104 ºF)
2-40 ºC (36-104 ºF)
2-40 ºC (36-104 ºF)
Lamp Type
HO (high-output)
HO (high-output)
HO (high-output)
Visual “Power-On”
Yes
Yes
Yes
Audible Lamp Failure
Yes
Yes
Yes
Lamp Replacement Reminder
Yes
Yes
Yes
Visual Lamp Life Remaining
Yes
Yes
Yes
Total Running Time
Yes
Yes
Yes
254nm UV Monitor
Yes
Yes
Yes
Chamber Material
304 SS
304 SS
304 SS
Solenoid Output
Yes
Yes
Yes
4-20 mA Output
Yes (Optional 260134)
Yes (Optional 260134)
Yes (Optional 260134)
1
Flow rates based on End of Lamp Life; 20ºC.
2
Units ending in “2B” have BSPT connections.
3
Units ending in “/2” are for 230V applications.
4