background image

Installation  procedure 

1. 

Identify installation location for water softener. 

Piping should be such that all    

household water, with the exception of outside hydrants, flows through softener. A hard 
water line may be run to a kitchen tap if so desired. This system and installation must 
comply with state and local laws and regulations. 

2. 

Connect water piping. 

This unit has been supplied with a manually operated bypass 

device which enables the softener to be isolated  from  the  water  service  lines  for       
maintenance and service, and also maintain the continuity of the water supply when the 
softener is disconnected.

 Important: Make all sweat-solder connections within 6 inches 

of softener before applying threaded fittings to supplied bypass valve. Overheating may 
cause damage to valve. 

Turn supplied bypass valve  to “Bypass” position and make  

connections to household water lines. Leave unit in “Bypass” position until startup    
procedure. 

3.  Connect drain line. 

Remove barbed drain line fitting from parts bag. Apply Teflon tape 

to threads, and turn into the female threaded opening on the back side of the control 
valve. Connect 5/8” drain line (supplied in parts bag) to barbed end of drain line fitting, 
and run to a nearby drain. Be sure not to submerse drain line end into drain, as an 1 1/2” 
minimum air gap must be maintained to prevent potential backflow hazard. Firmly se-
cure at drain, while maintaining a minimum 1 1/2” air gap (See detailed drawing on back 
side of piping diagram).

 

4.  Connect brine line (two-tank models only).

 Connect 3/8” brine line (supplied in parts 

bag) to fitting on brine tank, and on the control valve. Tighten both fittings with an     
adjustable wrench.

 

5.  Install brine tank overflow line.  

Install overflow fitting (supplied in parts bag) into 

hole in side of brine tank. An owner-supplied overflow line should then be attached and 
run to a nearby drain. 

Failure to run overflow line could  cause  flooding  and  water     

damage should the brine tank overflow. 

 

 

6.  Connect to electrical power source. 

Connect power cord to a dedicated 120v, 15 amp, 

ground fault interrupt (GFI) outlet. 

 

Proceed to start-up procedure 

 

Note: This system is not intended to be used for treating water that is microbiologically  
          unsafe or of unknown quality without disinfection before or after the system. 

Содержание BrassMaster

Страница 1: ...Time clock water softener Installation Operation manual WI Manufactured by Water Control Corporation 7150 143rd Ave NW Ramsey MN 55303 Tel 763 427 9635 Fax 763 427 5665 ...

Страница 2: ...rn into the female threaded opening on the back side of the control valve Connect 5 8 drain line supplied in parts bag to barbed end of drain line fitting and run to a nearby drain Be sure not to submerse drain line end into drain as an 1 1 2 minimum air gap must be maintained to prevent potential backflow hazard Firmly se cure at drain while maintaining a minimum 1 1 2 air gap See detailed drawin...

Страница 3: ... in the brine tank 3 Setting the current time of day Depress red time set button on left side of control While holding button turn outer dial 24 hour gear until the current time of day appears in the time of day window This step should be repeated periodically to insure adjustment for power outages 4 Setting number of desired regeneration days Slide the pins on the skipper wheel outward for each d...

Страница 4: ...le control knob 360 degrees through complete cycle to relieve water pressure Remove the stainless steel retainer pins at the base of the module loosen the clips at the bypass valve and disconnect the drain line and brine line The module will now completely separate from the tank Please contact your dealer or the factory for module support Limited Warranty Please see enclosed Official Warranty for ...

Отзывы: