background image

 

 

Installation Procedure 

1. 

Identify installation location for NitraMAX system. 

Piping should be such that all house-

hold water, with the exception of outside hydrants, flows through NitraMAX. This system 

and installation must comply with state and local laws and regulations. Always install Nitra-

MAX down stream of any other water treatment equipment. 

2. 

Connect water piping. 

This unit has been supplied with a manually operated bypass device 

which enables the softener to be isolated from the water service lines for maintenance and 

service,  and  also  maintain  a  constant  water  supply  when  the  NitraMAX  is  disconnected.

 

Important: Make all sweat-solder connections within 6 inches of NitraMAX before applying 
threaded fittings to supplied bypass valve. Overheating may cause damage to valve. 

Turn 

supplied bypass valve to “Bypass” position and make connections to household water lines. 

Leave unit in “Bypass” position until startup procedure. 

3. 

Connect drain line. 

Remove barbed drain line fitting from parts bag. Apply thread seal 

tape to threads and install into the female threaded opening on the back side of the control 

valve. Connect 5/8” drain line (supplied in parts bag) to barbed end of drain line fitting and 

run to a nearby drain.  

IMPORTANT: It is highly recommended that a hose clamp be used to secure tubing to 
drain fitting to ensure tubing from being removed during elevated pressure situations

.

 

Be sure not to submerse drain line end into drain, as an 1 1/2” minimum air gap must be 

maintained to prevent potential backflow hazard. Firmly secure at drain, while maintaining 

a minimum 1 1/2” air gap (See detailed drawing on back side of piping diagram). 

4. 

Connect brine line. 

Connect 3/8” brine line (supplied in parts bag) to fitting on brine tank 

and on the control valve. Tighten both fittings with an adjustable wrench. 

5. 

Install brine tank overflow line. 

Install overflow fitting (supplied in parts bag) into hole in 

side of brine tank. An owner-supplied overflow line should then be attached and run to a 

nearby drain. 

Failure to run overflow line could cause flooding and water damage should 

the brine tank overflow. 

 

6. 

Connect to electrical power source. 

Connect power cord to a separate 120VAC, 15Amp, 

ground fault interrupt (GFI) outlet.  

7.  Add 1—2 bags of sodium chloride or potassium chloride to the brine tank.  WCC recom-

mends pellet salt from manufacturers such as Morton or Diamond. 

Proceed to start-up procedure. 

 
 
 

Note:   This system is not intended to be used for treating water that is microbiologically  

 

unsafe or of unknown quality without disinfection before or after the system. 

Содержание Brassmaster Plus+ NitraMAX Series

Страница 1: ...e paid test bottles included To reorder visit watercontrolinc com nitramax nitrate removal or scan this QR code BrassMaster and BrassMaster Plus Technical Video Library https watercontrolinc com residential technical support residential technical videos BrassMaster technical videos demonstrate how to set up or remove the control module If replacing your control module please use the downloadable M...

Страница 2: ...etpoints are established based on water hardness levels unless combined ni trate nitrite levels exceed 50 PPM mg L If nitrate nitrite levels exceed 50 PPM please con tact Water Control Corporation for proper system setpoints Specifications NM 75 NM 125 Softening capacity grains 24 000 40 000 Cation softening media cu ft 0 75 1 25 Nitrate Nitrite Sulfate capacity raw water PPM or mg L 100 100 Anion...

Страница 3: ...ain line fitting and run to a nearby drain IMPORTANT It is highly recommended that a hose clamp be used to secure tubing to drain fitting to ensure tubing from being removed during elevated pressure situations Be sure not to submerse drain line end into drain as an 1 1 2 minimum air gap must be maintained to prevent potential backflow hazard Firmly secure at drain while maintaining a minimum 1 1 2...

Страница 4: ...and let go display will indicate BF Brine Fill cycle Allow timer to fill the brine tank for the entire time on the display The unit will advance to the service position when completed Push extra cycle button for 5 seconds this will start a manual regeneration from start to finish This will take approximately two hours Start up procedure is now complete The unit is now pressurized with water and re...

Страница 5: ...egeneration periods In areas where nitrates range between 0 50 PPM this setting should not exceed 6 days If nitrate lev els exceed 50 PPM please contact Water Control for a setpoint recommendation Setting Current Time Day 1 Press either the Up or Down button to adjust current time of day by one digit Press and hold either the up or down button to adjust current time of day display by several digit...

Страница 6: ...r Gal lon to this setting This will determine the amount of water usage allowed between regenera tion cycles NOTE If combined Nitrate Nitrite levels exceed 50 PPM contact Water Con trol for additional setpoint instructions 5 Set Fixed Reserve Capacity Press the Extra Cycle button to advance to next option Set the Fixed Reserve Capacity for the household This is the amount of water needed in reserv...

Страница 7: ...n from forming which will not allow the NitraMAX to regenerate properly The NitraMAX will regenerate but not recondition the media A salt bridge can be broken up using a broom handle or similar rod Carefully pound it into the salt and the pellets will collapse After loosening the salt pellets wait 2 hours and start a manual regeneration A second system regen eration may be needed to fully recondit...

Страница 8: ... FITNESS FOR A PARTICULAR PURPOSE WHAT IS NOT COVERED BY THESE WARRANTIES 1 Conditions damages and health effects resulting from any of the following Wear or malfunction caused by unfavorable water conditions Improper installation delivery or maintenance Any repair modification alteration or adjustment not authorized by the manufacturer or an authorized servicer Misuse abuse accidents or unreasona...

Отзывы: