WPMZ Series Modbus communication instruction manual
IM-0862-02
Number of pages:109
56
value
11E0 H
A
6
Analog input, linearize 21st point input value
4
R/W
※Refer to “Pattern 1”
11E2 H
A
6
Analog input, linearize 21st point output
value
4
R/W
※Refer to “Pattern 1”
11E4 H
~
11EDH
~
~
Reserve
~
~
11EE H
A
7
Analog input, input range
2
R/W
※Refer to “Pattern 1”
11EF H
A
7
Analog input, sensor power supply
2
R/W
※Refer to “Pattern 1”
11F0 H
A
7
Analog input, Low cut% value
4
R/W
※Refer to “Pattern 1”
11F2 H
A
7
Analog input, simple average
2
R/W
※Refer to “Pattern 1”
11F3 H
A
7
Analog input, moving average
2
R/W
※Refer to “Pattern 1”
11F4 H
A
7
Analog input, mantissa part of
instantaneous value display coefficient
4
R/W
※Refer to “Pattern 1”
11F6 H
A
7
Analog input, exponent part of
instantaneous value indication coefficient
2
R/W
※Refer to “Pattern 1”
11F7 H
A
7
Analog input, Instantaneous value Decimal
point position
2
R/W
※Refer to “Pattern 1”
11F8 H
A
7
Analog input, instantaneous value display
unit
2
R/W
※Refer to “Pattern 1”
11F9 H
A
7
Analog input, instantaneous value display
Custom unit 1st character
2
R/W
※Refer to “Pattern 1”
11FA H
A
7
Analog input, instantaneous value display
Custom unit 2nd character
2
R/W
※Refer to “Pattern 1”
11FB H
A
7
Analog input, instantaneous value display
Custom unit 3rd character
2
R/W
※Refer to “Pattern 1”
11FC H
A
7
Analog input, instantaneous value display
Custom unit 4th character
2
R/W
※Refer to “Pattern 1”
11FD H
A
7
Analog input, instantaneous value display
Custom unit 5th character
2
R/W
※Refer to “Pattern 1”
11FE H
A
7
Analog input, instantaneous value display
Custom unit 6th character
2
R/W
※Refer to “Pattern 1”
11FF H
A
7
Analog input, instantaneous value display
step
2
R/W
※Refer to “Pattern 1”
1200 H
A
7
Analog input, mantissa part of totalized
value display coefficient
4
R/W
※Refer to “Pattern 1”
1202 H
A
7
Analog input, exponent part of totalized
value display coefficient
2
R/W
※Refer to “Pattern 1”
1203 H
A
7
Analog input, time unit of totalized unit time.
2
R/W
※Refer to “Pattern 1”
1204 H
A
7
Analog input, mantissa part of integration
initial value
4
R/W
※Refer to “Pattern 1”
1206 H
A
7
Analog input, exponent part of integration
initial value
2
R/W
※Refer to “Pattern 1”
1207 H
A
7
Analog input, total calculation direction
2
R/W
※Refer to “Pattern 1”
1208 H
A
7
Analog input, totalized value Decimal point
position
2
R/W
※Refer to “Pattern 1”
1209 H
A
7
Analog input, totalized value display unit
2
R/W
※Refer to “Pattern 1”
120A H
A
7
Analog input, totalized value display Custom
unit 1st character
2
R/W
※Refer to “Pattern 1”
120B H
A
7
Analog input, totalized value display Custom
unit 2nd character
2
R/W
※Refer to “Pattern 1”
120C H
A
7
Analog input, totalized value display Custom
unit 3rd character
2
R/W
※Refer to “Pattern 1”
120D H
A
7
Analog input, totalized value display Custom
unit 4th character
2
R/W
※Refer to “Pattern 1”
120E H
A
7
Analog input, totalized value display Custom
unit 5th character
2
R/W
※Refer to “Pattern 1”
120F H
A
7
Analog input, totalized value display Custom
unit 6th character
2
R/W
※Refer to “Pattern 1”
1210 H
A
7
Analog input, totalized over operation
2
R/W
※Refer to “Pattern 1”
1211 H
A
7
Analog input, linearize function
2
R/W
※Refer to “Pattern 1”
1212 H
A
7
Analog input, linearize 1st point input value
4
R/W
※Refer to “Pattern 1”
1214 H
A
7
Analog input, linearize 1st point output
value
4
R/W
※Refer to “Pattern 1”
1216 H
A
7
Analog input, linearize 2nd point input value
4
R/W
※Refer to “Pattern 1”
1218 H
A
7
Analog input, linearize 2nd point output
value
4
R/W
※Refer to “Pattern 1”