WPMZ Series Modbus communication instruction manual
IM-0862-02
Number of pages:109
27
007CH
-
Digital zero A & B instruction
2
R/W
0000H:Disable、0001H:Enable
007DH
~
03E7H
~
Reserve
~
~
03E8H
AL1
Compare output instruction
2
R/W
0000H:Disable、0001H:Enable
03E9H
AL1
Comparative output indication value
2
R/W
0000H:OFF、0001H:ON
03EAH
~
0419H
~
Reserve
~
~
041AH
AL2
Compare output instruction
2
R/W
※AL1 reference
041BH
AL2
Comparative output indication value
2
R/W
※AL1 reference
041CH
~
044BH
~
Reserve
~
~
044CH
AL3
Compare output instruction
2
R/W
※AL1 reference
044DH
AL3
Comparative output indication value
2
R/W
※AL1 reference
044EH
~
047DH
~
Reserve
~
~
047EH
AL4
Compare output instruction
2
R/W
※AL1 reference
047FH
AL4
Comparative output indication value
2
R/W
※AL1 reference
0480H
~
0513H
~
Reserve
~
~
0514H
A
Pulse output indication
2
R/W
0000H:Disable、0001H:Enable
0515H
A
Pulse output indication value
2
R/W
0000H:OFF、0001H:ON
0516H
~
0545H
~
Reserve
~
~
0546H
B
Pulse output indication
2
R/W
※Pulse output A reference
0547H
B
Pulse output indication value
2
R/W
※Pulse output A reference
0548H
~
0BB7H
~
Reserve
~
~
Setting parameters
The setting parameters are as follows.
Refer to "4-1-3. Change setting parameters" when changing the setting parameters.
Table 5.3 Setting parameters
Communi
cation
address
CH
Pattern
Contents
size
(byte)
R/W
The data
0BB8H
-
-
Setting permission / save instruction
4
W
3333 CCCCH:Setting permission、
0000 0000H:Save instruction
0BBAH
-
-
Setting error contents
2
R
0000H: No error,
Other than 0000H: There is an error
※Error code Refer to "
reference
" for details
0BBBH
~
0BC1H
~
~
Reserve
~
~
-
0BC2H
A
1
Pulse Input, input type
2
R/W
In case of general purpose pulse input type
0000H:Open collector、
0001H:Logic、
0002H: Zero cross,
0003 H: 2 Wire,
0004H: 2-PhaseOpen Collector * 1, 2,
0005H: 2-Phase Logic * 1, 2,
0006H: 2-Phase 2 Wire* 1, 2
In case of line driver pulse input type
0000H:Line driver
*1 It can not be set when the input B