26
5.
Address Map
Write the address map of each model.
5-1.
WPMZ-5/6
This section describes the WPM-5/6 of the address map.
5-1-1.
Setting and control parameters
1.
Holding register
The hold register command is shown in the table below.
Table 5.1 Holding register command
Read command
03H
Write command
06H
Continuous write command
10H
Control parameters
The control parameters are as follows.
Please refer to "4-1-2. Change control parameters" when making mock input / output instruction
from control parameters.
Table 5.2 Control parameters
Communi
cation
address
CH
Contents
size
(byte)
R/W
The data
0000H
~
0065H
~
Reserve
~
~
0066H
-
Pattern select indication
2
R/W
0000H:Disable、0001H:Enable
0067H
-
Pattern select indication value
2
R/W
0000H:pattern 1、0001H:pattern 2、
0002H:pattern 3、0003H:pattern 4、
0004H:pattern 5、0005H:pattern 6、
0006H:pattern 7、0007H:pattern 8
0068H
-
Relay reset indication
2
R/W
0000H:Disable、0001H:Enable
0069H
-
Integration reset A indication
2
R/W
0000H:Disable、0001H:Enable
※Automatically return to 0000H after
execution
006AH
-
Integration reset B indication
2
R/W
0000H:Disable、0001H:Enable
※Automatically return to 0000H after
execution
006BH
-
Integration reset A & B instruction
2
R/W
0000H:Disable、0001H:Enable
※Automatically return to 0000H after
execution
006CH
-
Measurement prohibited A indication
2
R/W
0000H:Disable、0001H:Enable
006DH
-
Measurement prohibited B indication
2
R/W
0000H:Disable、0001H:Enable
006EH
-
Measurement prohibited A & B indication
2
R/W
0000H:Disable、0001H:Enable
006FH
-
Present value holding A indication
2
R/W
0000H:Disable、0001H:Enable
0070H
-
Present value holding B indication
2
R/W
0000H:Disable、0001H:Enable
0071H
-
Current value holding A & B instruction
2
R/W
0000H:Disable、0001H:Enable
0072H
-
Maximum value holding A indication
2
R/W
0000H:Disable、0001H:Enable
0073H
-
Maximum value holding B indication
2
R/W
0000H:Disable、0001H:Enable
0074H
-
Maximum value holding A & B instruction
2
R/W
0000H:Disable、0001H:Enable
0075H
-
Minimum value holding A indication
2
R/W
0000H:Disable、0001H:Enable
0076H
-
Minimum value holding B indication
2
R/W
0000H:Disable、0001H:Enable
0077H
-
Minimum value holding A & B instruction
2
R/W
0000H:Disable、0001H:Enable
0078H
-
Display switching instruction
2
R/W
0000H:Disable、0001H:Enable
※Automatically return to 0000H after
execution
0079H
-
Trend holding instruction
2
R/W
0000H:Disable、0001H:Enable
007AH
-
Digital zero A instruction
2
R/W
0000H:Disable、0001H:Enable
007BH
-
Digital zero B instruction