Instruction Manual MODEL AM-756
12/20
6-5
Group
Menu Display Parameter Name
Setting Range
Default
Value
Description
Display
Conditions
Comparative
Output Type
NRML: Normal output
ZONE: Zone output
NRML
Selects comparative output type.
* Condition data group
Comparative
output:
Relay,
photocoupler
Comparative
Output Latch
OFF: Latch function off
ON: Latch function on
OFF
Holds status (latches) when comparative output judgment is a
judgment other than GO. Latch can be cancelled with the following
procedure:
1. Go to parameter settings mode.
2. Turn the relay reset control terminal ON.
* Condition data group
Comparative
Output Delay
0 to 99 [CNT]
0
Sets the length of time actually taken for comparative judgment output
to deactivate when comparative judgment switches from ON to OFF.
Delay time (msec) = Set value × 20msec
* Condition data group
to
Comparative
Output Patterns
1 to 8
-
-
Switches to the parameter settings for comparative output patterns 1 to
8
・
Comparative Output Pattern 1 to 8 Parameters
Menu Display
Parameter Name
Setting Range
Default
Value
Description
Display
Conditions
to
HH Comparison
Set Values
1 to 8
-199999 to 199999
N.B.) Settings may be made within
identical patterns under the
following conditions.
S-HH > S-HI > S-LO > S-LL
100000
Measurement value >= HH set value
→
HH output ON
* Decimal point position depends on the decimal point
position in identical patterns.
Comparative
output:
Relay,
photocoupler
to
HI Comparison
Set Values
1 to 8
50000
Measurement value >= HI Set value
→
HI output ON
* Decimal point position depends on the decimal point
position in identical patterns.
to
LO Comparison
Set Values
1 to 8
-50000
Measurement value <= LO set value
→
LO output ON
* Decimal point position depends on the decimal point
position in identical patterns.
to
LL Comparison
Set Values
1 to 8
-100000
Measurement value <= LL set value
→
LL output ON
* Decimal point position depends on the decimal point
position in identical patterns.
to
HH Hysteresis
1 to 8
0 to 9999
0
Measurement value < (HH set value
–
HH Hysteresis)
→
HH output OFF
* Decimal point position depends on the decimal point
position in identical patterns.
to
HI Hysteresis
1 to 8
Measurement value < (HI set value
–
HI Hysteresis)
→
HI
output OFF
* Decimal point position depends on the decimal point
position in identical patterns.
to
LO Hysteresis
1 to 8
Measurement value > (LO set value + LO Hysteresis)
→
LO output OFF
* Decimal point position depends on the decimal point
position in identical patterns.
to
LL Hysteresis
1 to 8
Measurement value > (LL set value + LL Hysteresis)
→
LL
output OFF
* Decimal point position depends on the decimal point
position in identical patterns.
6-6
Group
Menu Display
Parameter Name
Setting Range
Default
Value
Description
Display
Conditions
Analog Output Type
0-10: 0 to 10V output
1-5: 1 to 5V output
0-1: 0 to 1V output
4-20: 4 to 20mA output
0-10
Selects output type when analog output selected.
Option: Analog
output
Analog Output 100%
Display Value
-19999 to 199999
199999
Sets display value when analog output is 100%.
Analog Output 0%
Display Value
-19999 to 199999
0
Sets display value when analog output is 0%.
BCD Output Logic
NEG: Negative logic
POS: Positive logic
NEG
Selects BCD output logic.
* Open collector is normal.
Option: BCD
output
6-7
Group
Menu Display Parameter Name
Setting Range
Default Value
Description
Display Conditions
Linearize Point
OFF: Linearize Off
2: 2-point correction
4: 4-point correction
8: 8-point correction
16: 16-point correction
OFF
Selects Linearize function ON/OFF and number of
correction points.
-