5.1.2. 

Scaling Data

 

 
 
 
 
 
 
 
 
 
 

5.1.3. 

Comparator Data 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.2. Display and Character Representation 

 

 

 

5.3. Parameter Types and Protect Levels 

The A7000 series parameters are classified into the following groups   

depending on the main objective:   

Condition data: A group of parameters that set basic actions such 

as sampling rate and operation type of each control   

Scaling  data:  A  group  of  parameters  relating  to  measurements 

such as a measurement range and scaling   

Comparator  data:  A  group  of  parameters  relating  to  comparison 

output  such  as  the  comparison  output  operation 

type or judgment values   

Shift  data:  A  group  of  parameters  relating  to  the  function  that 

forcibly shifts an indicated value   

Linearize  data:  A  group  of  parameters  relating  to  the  function  that 

corrects the linearity of an input value and indicated 

value

 

 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Each parameter has a protect level that has been set up. Setting the 

protect  level  of  condition  data  allows  the  settable  protect  level  of 

parameters  to  be  limited.  (For  the  settable  protect  level  of  each 

parameter, see P.L for the list of parameters in 5.1.)   

For the protect levels, the higher the level value, the more the number 

of parameters whose setting is disabled increases. If the protect level 

is  set  to  LV3,  which  is  the  highest  level,  all  parameters are  disabled 

from being set with the exception of protect level change.   

* At factory shipment, the protect level is set to LV1. (In this case, only 

settings  relating  to  display  color,  scaling,  or  judgment  values  can  be 

made).

 

 
 
 
 
 
 
 
 
 
 
 
 

 

0 1 2 3 4 5 6 7 8 9

A B C D E F G H I J K L M N O P Q R S T U V W X Y Z

- /

Instruction Manual for MODEL A7X14,5,6-X(AC Voltage and Current Measurement)                                5/12   

Parameter Name

Menu Display

P.L.

Initial 

Value

(FSC)

(FIN)

(OFS)

(OIN)

(DLHI)

(DLLO)

(AOHI)

(AOLO)

(DP)

Full-scale indicated value 

Full-scale input value 

Offset indicated value 

Offset input value 

Digital limiter HI 

Digital limiter LO

Analog output HI

Analog output LO

Decimal point 

2

2

2

2

0

0

1

1

2

(RANG) Input range

1

(A.OUT) Analog output type

1

Settable Range or Alternatives

Set to any digit 

1

1

(large current)

 (small current)

 (voltage)

Selects the input range. *Note that the input terminal changes depending on the input range. 

Sets the relationship between an input signal and indicated value. 
   *In the case of AC input, please use it by 

+

 setting by all means.

    It is not displayed normally when I use it by 

-

 setting.

For the voltage measurement's 15 ranges, the full-scale input value becomes "9999" when an input is 700 V. 
For the large-current measurement's 26 ranges, the full-scale input value becomes "9999" when an input is 5 A. 

Sets the high limit of the displayable range. (A value exceeding the digital limiter HI setpoint is not updated and is held at the set value.) 

Selects the analog output's output range. * Only when analog output is provided 

Sets the relationship between display and analog output. * Only when analog output is provided 

Sets the decimal-point display position. 

Main Setting Target and Precautions

Sets the low limit of the displayable range. (A value lower than the digital limiter LO setpoint is not updated and is held at the set value.) 

LO logic 

0

Sets LO output logic (N.O: normally open, N.C: normally closed). 
* When power is OFF, output is always open (OFF). 

(LO-L)

GO logic 

0

Sets GO output logic (N.O: normally open, N.C: normally closed). 
* When power is OFF, output is always open (OFF). 

(GO-L)

HI logic 

0

Sets HI output logic (N.O: normally open, N.C: normally closed). 
* When power is OFF, output is always open (OFF). 

(HI-L)

(ER1.H)

1

Sets tolerance-1 hysteresis (applied to the inner side of a setpoint). * Only when COM.T is in ERR

(LO-H) LO hysteresis

1

Sets LO-side hysteresis (applied to the inner side of a setpoint). * Only when COM.T is in O/U

(HI-H) HI hysteresis 

1

Sets HI-side hysteresis (applied to the inner side of a setpoint). * Only when COM.T is in O/U

Tolerance 1

(ERR1)

2

Sets tolerance 1. * Only when COM.T is in ERR

Nominal value 

(N.VAL)

2

Sets the nominal value. * Only when COM.T is in ERR

(LO-S) LO judgment value 

2

Sets LO-side judgment value. * Only when COM.T is in O/U 

(HI-S) HI judgment value 

2

Sets HI-side judgment value. * Only when COM.T is in O/U 

COM.T

Comparison output

1

Selects high and low judgments (O/U) or tolerance judgments (ERR) for comparison action type. 

Parameter Name

Menu Display

P.L.

Initial 

Value

Settable Range or Alternatives

Main Setting Target and Precautions

(HH-S) HH judgment value 

2

Sets HH-side judgment value. * Only when COM.T is in O/U 

(LL-S) LL judgment value 

2

Sets LL-side judgment value. * Only when COM.T is in O/U 

Tolerance 2

(ERR2)

2

Sets tolerance 2. * Only when COM.T is in ERR

(HH-H) HH hysteresis 

1

Sets HH-side hysteresis (applied to the inner side of a setpoint). * Only when COM.T is in O/U

(LL-H) LL hysteresis

1

Sets LL-side hysteresis (applied to the inner side of a setpoint). * Only when COM.T is in O/U

(ER2.H)

1

Sets tolerance-2 hysteresis (applied to the inner side of a setpoint). * Only when COM.T is in ERR

HH logic 

0

Sets HH output logic (N.O: normally open, N.C: normally closed). 
* When power is OFF, output is always open (OFF). 

(HH-L)

LL logic

0

Sets LL output logic (N.O: normally open, N.C: normally closed). 
* When power is OFF, output is always open (OFF). 

(LL-L)

Tolerance-2 hysteresis

Tolerance-1 hysteresis 

Содержание A7X14-X

Страница 1: ...ge due to product improvements without notice 4 Every effort has been made to ensure accuracy in the presentation of this manual However should you have any questions or should any errors or omissions come to your attention please contact your sales representative or our sales office directly 5 After reading keep this manual nearby so that you can refer to it as needed CAUTIONS 96 mm or more 0 6 0...

Страница 2: ...a contact output terminal of HH output relay COM terminal for HH and HI output relays OFF OFF ON ON OFF OFF ON OFF ON OFF ON ON OFF ON OFF ON Start Hold terminal Enabled when it has the same potential as or is shorted with terminal COM Peak Hold terminal Enabled when it has the same potential as or is shorted with terminal COM Digital Zero terminal Enabled when it has the same potential as or is s...

Страница 3: ...l of HI output photocoupler Collector output terminal for GO output photocoupler Collector output terminal of LO output photocoupler Collector output terminal of LL output photocoupler Emitter terminal of GO output photocoupler Common emitter terminal for LO and LL output photocouplers Common terminal for analog outputs Voltage Output terminal 0 to 1 V 0 to 10 V 1 to 5 V Current Output terminal 4 ...

Страница 4: ...a display change width to limit variations in display If this parameter is set to 5 the least significant digit displays only 0 or 5 Selects display color Only when no meter relay is available Selects either automatic setting red for HI and LO and green for GO or manual setting for display color type Only when a meter relay is available Selects red or green for display color applied during HI judg...

Страница 5: ...rge current measurement s 26 ranges the full scale input value becomes 9999 when an input is 5 A Setsthehighlimit of thedisplayablerange Avalueexceedingthedigital limiter HI setpoint isnot updatedandisheldat theset value Selects the analog output s output range Only when analog output is provided Sets the relationship between display and analog output Only when analog output is provided Sets the d...

Страница 6: ...tting Press the Increment key several times to set a desired value this setting example sets the number of moving averaging times to 4 Measurement operation Pressing for a prolonged time or Press the Increment key to move to moving averaging setting Press the Enter key to return to measurement operation If the Mode key is pressed you will be returned to the setting menu press the Increment key to ...

Страница 7: ...rement key Press the Enter key to return to measurement operation If the Mode key is pressed you will be returned to the setting menu press the Increment key to move to the next parameter Next the following describes the concept of analog output scaling Analog output sets an output value in relation to the indicated value The operation procedure is the same as that of a full scale indicated value ...

Страница 8: ...e Mode key the comparison output type setting content appears O U high and low limit judgment Err tolerance judgment Press the Increment key several times to move to the comparator data menu Press the Mode key to display comparison output type To change the pattern use the Increment key Press the Mode key to return to the setting menu In this setting example the display returns to comparison outpu...

Страница 9: ... function regards display at any timing as zero and indicates varying width from this point on This function can be activated or deactivated by terminal control or front panel key based operation which is selected according to the setting of condition data For terminal control the DZ and COM terminals are short circuited or made to have the same potential to activate the digital zero function caus...

Страница 10: ...ication Printout command signal PC Positive pulse output after completion of measurement PC width depends on sampling Output logic Switchable PC logic not switchable Output signal TTL level fan out 2 COMS compatible Open collector output NPN type Measured data Transistor ON when negative logic is logic 1 Polarity signal Transistor ON for negative indication Excess signal Transistor ON for excess i...

Страница 11: ...ts Connected Line Length Delimiter E M H H H I G O L L R E P H D Z P 1 P 2 P 3 M E L O 33 68 80 87 72 7 118 36 3 delay time 1 x 2 500 μs 3 delay time 1 x 2 500 μs 4 Internal sampling Set sampling S H terminal P C BCD defined 1 2 3 Comparison output updating 4 Start hold type A Start hold type B Delay time 1 x 2 500 μs Delay time 1 x 2 500 μs 4 Internal sampling Set sampling S H terminal P C BCD de...

Страница 12: ...miter HI and digital limiter LO of scaling data have the samevalue Indicates that analog output HI and analog output LO of scaling data have the samevalue Linearizedataerror Turning power ON with the Enter key and Mode key held down causes all the parameters to return to the initial values defaults Display Memoryswitcharea checksumerror of mainmemory Calibrationdataarea checksumerror of mainmemory...

Отзывы: