Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E
- 26 -
9.3
USB port (optional)
Connection of the UPS to a computer is also possible by means of the USB interface at the rear of the UPS
unit. If the USB interface is to be used then simultaneous use of the RS 232 interface is not possible.
Communication between the UPS and the computer takes place via a conventional USB connection cable
(PC: plug -A / UPS unit: plug -B) and can only be used with the software “
UPSMON
“delivered as standard
and the optionally obtainable JUMP software.
10.
Special equipment
10.1
Electronic STOP function
The UPS is fitted with an integrated electronic STOP function. This function is
deactivated as standard by measn of a short-circuit-bridge at the rear of the
UPS unit. If the electronic STOP functionality is to be used then the bridge
should be removed on the plug and an external switch (opener) clamped to the
rear plug. Actuation of the external electronic STOP switch causes the output of
the UPS unit to be switched to voltage-free and the UPS unit shuts down. In
order to provide the consumers with a voltage again the electronic STOP switch
must be reset and the UPS restarted. There is still a
voltage
inside and at the
terminals even after the electronic STOP function was activated.
Figure 6: Electronic STOP
11.
Manual bypass (optional)
For these UPS – Devices an optional External Manual Bypass is available.
Please refer to manual BAX 3945 for further explanations!
P L E A S E N O T E!
The following conversion work or extension to the unit may only be performed by
trained personnel and with the UPS unit in a deenergised condition.
Observe the relevant safety regulations!!