Wärtsilä JOVYREC D600 G120/10
150254_10_BA
- 4 –
1 Technical
Data
Mains supply (X1)
Voltage
: 3 x 600VAC ±10%
Frequency
: 50Hz ±5%
Rated current
: 3 x 5A
Output
Nominal Output Voltage
: 136,2VDC ±1% (2,27V per cell)
Ripple
: 5%RMS
Current
: 10A ±2% limited
General
Operating mode
: Continuous operation
Protective system
: IP 54
Ambient temperature
: 0°C...+40°C
Noise level
: <60dBA
Widht x Height x Depth UPS
: 800mm x 2000mm x 600mm
Waight UPS
: Approximate 200kg
Varnishing
: RAL 7035
Indicating- and operating elements
Voltmeter P1 0...150VDC
: Output voltage rectifier 1
Voltmeter P3 0...150VDC
: Output voltage rectifier 2
Ampere meter P2 0...15ADC
: Output current rectifier 1
Ampere meter P4 0...15ADC
: Output current rectifier 2
Rotary switch S1
: 1 - Rectifier 1 ON
: 0 – OFF
: 2 – Rectifier 2 ON
Rotary switch S2 (inside)
: Reset low discharge protection
Signal lamp H1
: Rectifier 1 ON
Signal lamp H2
: Rectifier 1 ON
Remote indication
Potential free contacts for:
-
Rectifier 1 fault
-
Rectifier 2 fault
-
Mains failure
-
DC – overvoltage
-
DC - undervoltage
-
Insolation failure
--
Fuse failure Distriburion