4.8.1 Installation
The rectifier has to be installed at the final destination as following:
Compare dimensional drawings in appendix.
Place the rectifier carefully at the planned location and fix it at the socle.
For maintenance the rectifier needs a distance of at least 80cm in front of the device.
The rectifier is cooled by air inlets in front door of the cabinet. For unhindered air-exchange these areas must be
free.
The rectifier has to be installed in a dry and clean room with a sufficient air-exchange. If this is not guaranteed, the
room has to be adequately air-conditioned.
For the installation dimensions see the diagrams in the appendix.
The rectifier is designed to be installed for wall mounting.
4.8.2 Cabinet
interconnections
The rectifier should be interconnected per drawing ‘Terminal Board’ in annex.
The suitable diameters of cables and the sizes of the fuses are to be de-signed with regard to the environmental
temperature, the cable grouping and length of cables according to the local rules and according to VDE!
CAUTION:
Works on electrical equipment are to be done only by qualified personnel. The corresponding safety-
rules has to be fulfilled. The marking of wires has to be done in accordance to DIN 40705, 02.80 and
DIN EN 60445, 09.91!
-
Connect rectifier mains supply to X1.
-
The earth connection is made at terminal PE.
-
The battery is internal wired!
-
Connect the floating loads according to requirements to X2. The cable cross-sections for the output cables
should be selected on the basis of the output currents.
-
Connect signalisation lines to X3 according to requirements (refer to circuit- and terminal diagram in
annex).
The following faults and operating conditions are made available for further processing:
-
X3.1-X3.3
: Rectifier 1 fault
-
X3.3-X3.6
: Rectifier 2 fault
-
X3.7-X3.9
: Mains failure
-
X3.10-X3.12 :
DC-overvoltage
-
X3.13-X3.15 :
DC-undervoltage
-
X3.16-X3.17 : Insulation failure
-
X3.18-X3.19
: Output circuit breaker tripped
4.8.3 General
information
The wire diameters have to be calculated concretely considering the actual environmental conditions! At larger
distances the permissible voltage drop, the surrounding temperature and the cable grouping have to be
dimensioned according to VDE. Local rules for the protection earth-wires have to be considered.
5 Putting into operation
-
Before switching on the rectifiers make sure, that the battery fuses F4 have been removed.
-
Switch on rectifier 1 or rectifier 2 with the rotary-switch S1, the corresponding lamp H1 or H2 will light up.
-
A value of 136,2V must be displayed by the corresponding voltmeter P1 or P3.
-
Insert the battery fuses.