Wärtsilä JOVYREC D600 G120/10
150254_10_BA
- 12 –
ATTENTION:
Observe the centre of gravity!
The lifting arms must be sufficiently long and sufficiently far apart.
Proceed as follows:
•
Insert the lifting arms between the transport pallet and the rectifier.
•
Carefully lift the rectifier and transport the unit to its intended location.
•
Lower the rectifier carefully without jolting the unit.
•
Retract the forklift or lowlift truck.
•
Refit the base covering with the securing bolts.
4.5 Site
Conditions
Suitable floor surfaces are:
•
double floors,
•
above cable ducts or
•
directly on a level surface.
Ensure that the weight of the rectifier device does not exceed the maximum floor bearing capacity.
The site must also:
•
be free from conductive dust,
•
free from corrosive or acid fumes
•
the intake air temperature must not exceed 45°C
•
the ventilation openings on the rectifier should not be obstructed by any constructional features or other
measures.
Rectifier devices are suitable for installation in confined spaces. It must be ensured that a 800mm space is
provided in front of the device to ensure an escape route and 100mm above the unit to ensure unobstructed air
venting.
4.6 Floor
Mounting
Four bores are provided in the base frame of the rectifier for the securing bolts. The spacing and diameter of the
bores are contained in the Dimensional drawing in annex.
Before securing the unit to the floor ensure that it is vertically aligned in or-der to compensate for any unevenness
(e.g. using metal wedges).
4.7 Storage
Rectifier units may only be stored for a maximum period of six months in the original packaging in dry, ventilated
rooms with a permanent roof. The permissible ambient temperature range is from -35°C to +70°C and a relative
humidity of
≤
95 % is mandatory.
If the device is stored for longer than six months the rectifier units must be provided with normal desiccants and
welded into airtight plastic covering.
4.8 Installation and Cabinet Interconnections
CAUTION:
Verify that all power has been removed.
From external cables prior to installation. Secure and tag out external power sources where
applicable.