WIRING SUPPLY, SIGNAL AND FEEDBACK

1

2

TB4

NEUTRAL

LINE

120 Vac

F3 & F4 MOTORS

120 VAC (SINGLE-PHASE 50/60 HZ)

Locate the green case-grounding wire inside the motor case and connect 

it to the earth ground lead from the power source.  Connect the neutral 

(typically white) wire to terminal one (1) on terminal block TB4.  Connect 

the “hot” (typically black) wire to terminal two (2). This terminal block was 

identified as TB5 on earlier builds of these motors.

F5 & F6 MOTORS

220 VAC (SINGLE-PHASE 50/60 HZ)

Locate the green case-grounding wire inside the motor case and connect 

it to the earth ground lead from the power source.  Connect one “hot” wire 

to each of the two terminals on terminal block TB4. This terminal block 

was identified as TB5 on earlier  builds of these motors. 

1

2

TB4

LINE

LINE

220 Vac

EARTH GROUND

1

2

TB1

COMMON (-)

(LINE)

24 VAC OR 

30 VDC

3

4

5

F3 & F4 MOTORS

24 VAC OR  30 VDC  

(24 VDC - W / Special Considerations)

If the actuator is to be powered by 24 VAC or 30 VDC, connect the nega-

tive or common wire to terminal ONE (1) and the positive (or "hot" wire) 

to Terminal TWO (2) on TB1. When powered by (24 VDC, Special Consider-

ation) voltage, motor torque will be reduced by approximately 10% which 

will reduce close off capability. Contact the factory for questions.

If the control signal is 4 - 20 mA, connect the control wires to 
TB1 as shown. Dipswitch #3 MUST be in the ON position.

EARTH GROUND

IMPORTANT: The AmurAct actuator is precision calibrated at the factory. 
Confirm that the control signal at the site is 4-20 mAdc. The control signal 
minimum must reach 4.00 mAdc. If the control signal minimum does not 
reach 4.00 mAdc, the actuator may not reach its end of travel in that direc-
tion and the valve may not shut-off tightly. The control signal maximum 

must reach 20.00 mAdc. If the control signal maixmum does not reach 
20.00 mAdc the actuator may not reach its end of travel in that direction 
and the valve may not fully open (2-way valve) or shut-off (3-way valve). 
 

Preferred Calibration Accuracy:  

+ 2.5  A, (Typ)

1

2

TB1

COMMON (-)

 (+) CONTROL 4-20 mA DC  

3

4

5

This signal is an output signal and not required for operation. The sole 
function is to provide a verified feedback signal. The actuator can be set 
to provide a 4-20 mA feedback signal (factory default) or a 2-10 Vdc feed-
back signal. For 4-20 mA feedback dipswitch #4 must be in the OFF po-
sition. For 2-10 Vdc feedback, dipswitch #4 must be in the ON position. 
Connect the feedback wires to TB1 as shown. If the actuator is set for CCW 
rotation on  increasing signal (factory default) and the actuator is at 90º 
rotation (facing the motor) the feedback will be 4 mA or 2 Vdc, and at 0º 

If the control signal is 2 - 10 Vdc, connect the control wires to 
TB1 as shown. Dipswitch #3 MUST be in the OFF position.

IMPORTANT: The AmurAct actuator is precision calibrated at the factory. 
Confirm that the control signal at the site is 2-10 Vdc. The control signal 
minimum must reach 2.00 Vdc. If the control signal minimum does not 
reach 2.00 Vdc, the actuator may not reach its end of travel in that direc-
tion and the valve may not shut-off tightly. The control signal maximum 

must reach 10.00 Vdc. If the control signal maixmum does not reach 10.00 
Vdc the actuator may not reach its end of travel in that direction and the 
valve may not fully open (2-way valve) or shut-off (3-way valve).
 

Preferred Calibration Accuracy:  

+ 1.5 mV, (Typ)

SUPPLY VOLTAGE

CONTROL SIGNAL - Current (milliamp) <DEFAULT>

CONTROL SIGNAL - VOLTAGE

1

2

TB1

COMMON (-)

 (+) CONTROL 2-10 VDC  

3

4

5

FEEDBACK SIGNAL

1

2

TB1

COMMON (-)

 (+) OUTPUT

3

4

5

rotation (facing the motor) the feedback will be 20 mA or 10 Vdc.  If 
the actuator is set for CW rotation on increasing signal the direction 
of the feedback signal will be reversed.

Содержание AmurAct Linkage LS Series

Страница 1: ...3 way valves Otherwise in all other circumstances the Linear Stem Lift factory default will be the desired setting In either case correct control valve sizing is critical to good operation See indivi...

Страница 2: ...e and applies it to the input shaft of the second component the AmurAct linkage The link age converts rotary force and motion to linear force and motion to operate the reciprocating stem of an attache...

Страница 3: ...ECTORisthreadedontothevalvestemandattachedto the LEVER by two connecting links Upward movement of the LEVER draws the VALVE STEM upward The articulated link connection reduces side loading on the valv...

Страница 4: ...or you must first follow steps 1 5 of this procedure and when finished perform the Auto Calibration procedure on page 8 Failure to remove power AND de energize the Enerdrive system first prior to de c...

Страница 5: ...15 mA Slow Blow with T41 terminations Contact the factory at 610 317 0800 before attempting to reconfigure or reposition an AmurAct actuator Improperly rotating the linkage on the valve bonnet adverse...

Страница 6: ...may not shut off tightly The control signal maximum must reach 20 00 mAdc If the control signal maixmum does not reach 20 00 mAdc the actuator may not reach its end of travel in that direction and the...

Страница 7: ...tionship between the control signal and valve stem lift When Switch 5 is in the OFF position a non linear relationship is established between the control signal and valve stem lift This is uniquely ap...

Страница 8: ...ress the RESET pushbutton or vary the control signal These actions may result in the actuator programming being changed If the actuator progamming is changed the actuator may not respond correctly to...

Страница 9: ...sition ______________________________________ 6 If the same motor is to be reinstalled proceed to step 7 If it is to be replaced label field wires for reconnection then discon nect and remove them ___...

Страница 10: ...before applying a control signal Important A small phase error in re clamping the motor without initiating an AUTOSTROKE CALIBRATION CYCLE will cause severe damage to the motor by overrunning the cycl...

Страница 11: ...ct with the top jam nut _______________________________________ 3 Lower the linkage assembly over the valve stem and bonnet then slide the bonnet nut over the connector and loosely thread the nut onto...

Страница 12: ...d linkage and full seating force is now present on the valve plug LEAVE THE CLAMP IN PLACE UNTIL MOTOR INSTALLATION IS COMPLETE ________________________________________ 8 Calibrate and install the mot...

Страница 13: ...bration is complete push the crank firmly against its support column to fully extend the linkage input shaft Install a clamp onto the lower end of the crank and the crank support column Draw the crank...

Страница 14: ...ose off force Remember to press the motor RESET pushbutton after installation and calibration are complete and the motor is energized but before the system is placed into service Verify Dip Switch 5 i...

Страница 15: ...is installed correctly 10 Initate an AUTOSTROKE CALIBRATION CYCLE STOP You must wait for the AUTOSTROKE CALIBRATION CYCLE to finish before going on to the next step 11 Reset the actuator programming...

Страница 16: ...F WARREN CONTROLS INCORPORATED THIS DRAWING IS FOR REFERENCE PURPOSES ONLY POSSESSION OF IT DOES NOT IN ITSELF CONVEY ANY RIGHT OR LICENSE TO MAKE MANUFACTURE USE AND OR SELL THE DEVICE PROCESS METHOD...

Страница 17: ...AmurAct AMURACT_IOM_RevK_0415 17 D3400007...

Страница 18: ...F WARREN CONTROLS INCORPORATED THIS DRAWING IS FOR REFERENCE PURPOSES ONLY POSSESSION OF IT DOES NOT IN ITSELF CONVEY ANY RIGHT OR LICENSE TO MAKE MANUFACTURE USE AND OR SELL THE DEVICE PROCESS METHOD...

Страница 19: ...AmurAct AMURACT_IOM_RevK_0415 19 D3400011...

Страница 20: ...F WARREN CONTROLS INCORPORATED THIS DRAWING IS FOR REFERENCE PURPOSES ONLY POSSESSION OF IT DOES NOT IN ITSELF CONVEY ANY RIGHT OR LICENSE TO MAKE MANUFACTURE USE AND OR SELL THE DEVICE PROCESS METHOD...

Страница 21: ...AmurAct AMURACT_IOM_RevK_0415 21 D3400014...

Страница 22: ...F WARREN CONTROLS INCORPORATED THIS DRAWING IS FOR REFERENCE PURPOSES ONLY POSSESSION OF IT DOES NOT IN ITSELF CONVEY ANY RIGHT OR LICENSE TO MAKE MANUFACTURE USE AND OR SELL THE DEVICE PROCESS METHOD...

Страница 23: ...AmurAct AMURACT_IOM_RevK_0415 23 D3400015...

Страница 24: ...Act Actuator Linkage and Motor AMURACT_ IOM_RevK_0415 92500060 Rev K 2600 EMRICK BLVD BETHLEHEM PA 18020 USA 800 922 0085 WWW WARRENCONTROLS COM DEPENDABLE RUGGED PRECISION CONTROL VALVES AND ACCESSOR...

Отзывы: