11
Figure 19
Vertical flue set installation application
Implementation
L1
= 0.3 m.
L2
= 0.5 m. (45° bend equivalent length)
L3
= 1.0 m.
L4
= 0.5 m. (45° bend equivalent length)
L5
= 0.5 m.
L6
= 0.5 m.
L Total
= 3.3 m.
3.3 m. < Lmax = 5 m.
Correct in implementation
2.2.14. Hermetic Flue Type Use
2.2.15. Installation at Partially Protected Exteriors
Installation Instructions: This combi can be installed in partially protected
exteriors but not fitted in places at risk of atmospheric damage – and
protected against poor weather.(rain, snow, etc.).
Frost protection:
Combi device is equipped with a system that prevents
frost by automatically activating the pump and boiler when the internal
water is lower than 5°C.
Frost protection function only depends on below given conditions:
- If the combi is correctly connected to gas and electrical sources;
- If the combi is supplied from gas and electricity sources in a fixed
way;
- If the Combi is not in failure situation due to lack of ignition;
- If radiator installation pressure is full and radiator valves are open;
- Provided main components are not damaged, the combi is protected
against frost up to -5°C environment temperature.
Lowest Temperature -5°C.
In case the combi is installed in an
environment with a temperature lower than -5°C, and gas supply is
interrupted or passed into failure due to failing to make ignition, Frost
Prevention System shall not be activated and frost/failure shall occur in
the device. Following instructions should be followed for preventing the
risk of frost:
- Heating circuit; anti freeze may be used with caution according to
manufacturer's instructions.
In case of having flammable walls or passages in environments
with Hermetic Flue Type, fire resistant insulation material is
placed between the wall and exhaust gas relief pipe.
Materials used for manufacturing the combi are resistant against glycol
and propylene based anti-frost liquids. Follow warnings by supplier
companyinstructions for safe disposal..
- If the combi is correctly connected to the electrical source;
- If the main switch is on;
Under these conditions, the combi is protected against frost up to -5°C
temperature.
Implementation
L1
=0.2 m.
L2
=1.0 m. (90° bend equivalent length)
L3
=0.6 m.
L4
=1.0 m. (90° bend equivalent length)
L5
=0.8 m.
L6
=0.2 m.
L7
=1.0 m. (90° bend equivalent length)
L8
=0.5 m.
L9
=0.5 m. (45° bend equivalent length)
L10
=0.5 m.
L11
=1.0 m. (90° bend equivalent length)
L Total = 8.1 m.
8.1 m. < Lmax = 18 m.
Figure 20
Hermetic flue type installation
Содержание LAWA
Страница 1: ...CONVENTIONAL COMBI BOILERS INSTALLATION USER MANUAL LAWA LAWAPLUS...
Страница 2: ...Lawa LawaPlus Enerwa E24 EnerwaPLUSE24...
Страница 25: ...25...
Страница 26: ...26...
Страница 27: ...27...