Installation and Servicing
SECTION 2 - INSTALLATION
Outdoor flusher
Condensate Water Drainage Pump
(Refer to detailed instructions of the pump manufacturer)
Min Ø 19 mm
Inner
Pipe
75
Min Ø 19 mm
Inner pipe
Min Ø 30 mm
Inner pipe
Air hole
Combined waster
and rain water
drainage pipe
43 mm 90º
male/female bend
Water / Air
proof
insulation
68 mm Ø PVCU
Fitting
Min Ø 19 mm
Min Ø 30 mm
Drainage pipe with water
and air insulation
Maximum length of
the outer pipe
shall be 3 m.
Insert the drainage pipe
at least 25 mm into the tube
located outdoors
Pebble
≥ 500
≥ 25
Required
distance for
minimum 3-storey
buildings
Drainage and
Ventilation Pipe
Min Ø 19 mm
Water / Air proof
insulation
Outdoor flusher
Min Ø 19 mm
Inner pipe
75 mm flusher
bathroom/shower
drainage combined
with other drainage
lines
Minimum 30 mm
Inner pipe
Water / Air
proof
insulation
≥ 25 Distance under grid
45º pipe
termination
75
≥ 100
Figure 2.25
Connection of a Condensate Pump Typical
Method (see manufacturers detailed instructions)
Figure 2.26
Connection of condensate Drainage Pipe to
External Soil & Vent Stack
Figure 2.27
Connection of a Condensate Drainage Pipe to an
External Rainwater Downpipe (only combined foul/rainwater
drain)
Figure 2.29
Connection of a Condensate Drainage Pipe to an
External Purpose Made Soak Away.
Figure 2.28
Connection of Condensate Drainage Pipe
Upstream of a Sink, Basin, Bath or Shower Waste Trap to
External Drain, Gulley or Rainwater Hopper
INS
T
ALL
A
TION
CONDENSATE............ CONT’D
45º cross-
sectional drainage
pipe outlet
Open air flusher
Figure 15
Outside Connection of Condensate Water Drainage Pipe
27
Installation and Servicing
SECTION 2 - INSTALLATION
Outdoor flusher
Condensate Water Drainage Pump
(Refer to detailed instructions of the pump manufacturer)
Min Ø 19 mm
Inner
Pipe
75
Min Ø 19 mm
Inner pipe
Min Ø 30 mm
Inner pipe
Air hole
Combined waster
and rain water
drainage pipe
43 mm 90º
male/female bend
Water / Air
proof
insulation
68 mm Ø PVCU
Fitting
Min Ø 19 mm
Min Ø 30 mm
Drainage pipe with water
and air insulation
Maximum length of
the outer pipe
shall be 3 m.
Insert the drainage pipe
at least 25 mm into the tube
located outdoors
Pebble
≥ 500
≥ 25
Required
distance for
minimum 3-storey
buildings
Drainage and
Ventilation Pipe
Min Ø 19 mm
Water / Air proof
insulation
Outdoor flusher
Min Ø 19 mm
Inner pipe
75 mm flusher
bathroom/shower
drainage combined
with other drainage
lines
Minimum 30 mm
Inner pipe
Water / Air
proof
insulation
≥ 25 Distance under grid
45º pipe
termination
75
≥ 100
Figure 2.25
Connection of a Condensate Pump Typical
Method (see manufacturers detailed instructions)
Figure 2.26
Connection of condensate Drainage Pipe to
External Soil & Vent Stack
Figure 2.27
Connection of a Condensate Drainage Pipe to an
External Rainwater Downpipe (only combined foul/rainwater
drain)
Figure 2.29
Connection of a Condensate Drainage Pipe to an
External Purpose Made Soak Away.
Figure 2.28
Connection of Condensate Drainage Pipe
Upstream of a Sink, Basin, Bath or Shower Waste Trap to
External Drain, Gulley or Rainwater Hopper
INS
T
ALL
A
TION
CONDENSATE............ CONT’D
45º cross-
sectional drainage
pipe outlet
Open air flusher
Figure 16
Typical Connection Method of a Condensate Water Drainage Pipe (refer to
detailed instructions of the pump manufacturer)
27
Installation and Servicing
SECTION 2 - INSTALLATION
Outdoor flusher
Condensate Water Drainage Pump
(Refer to detailed instructions of the pump manufacturer)
Min Ø 19 mm
Inner
Pipe
75
Min Ø 19 mm
Inner pipe
Min Ø 30 mm
Inner pipe
Air hole
Combined waster
and rain water
drainage pipe
43 mm 90º
male/female bend
Water / Air
proof
insulation
68 mm Ø PVCU
Fitting
Min Ø 19 mm
Min Ø 30 mm
Drainage pipe with water
and air insulation
Maximum length of
the outer pipe
shall be 3 m.
Insert the drainage pipe
at least 25 mm into the tube
located outdoors
Pebble
≥ 500
≥ 25
Required
distance for
minimum 3-storey
buildings
Drainage and
Ventilation Pipe
Min Ø 19 mm
Water / Air proof
insulation
Outdoor flusher
Min Ø 19 mm
Inner pipe
75 mm flusher
bathroom/shower
drainage combined
with other drainage
lines
Minimum 30 mm
Inner pipe
Water / Air
proof
insulation
≥ 25 Distance under grid
45º pipe
termination
75
≥ 100
Figure 2.25
Connection of a Condensate Pump Typical
Method (see manufacturers detailed instructions)
Figure 2.26
Connection of condensate Drainage Pipe to
External Soil & Vent Stack
Figure 2.27
Connection of a Condensate Drainage Pipe to an
External Rainwater Downpipe (only combined foul/rainwater
drain)
Figure 2.29
Connection of a Condensate Drainage Pipe to an
External Purpose Made Soak Away.
Figure 2.28
Connection of Condensate Drainage Pipe
Upstream of a Sink, Basin, Bath or Shower Waste Trap to
External Drain, Gulley or Rainwater Hopper
INS
T
ALL
A
TION
CONDENSATE............ CONT’D
45º cross-
sectional drainage
pipe outlet
Open air flusher
Figure 17
Connection of Condensate Drainage to Drainage and Ventilation Pipe
27
Installation and Servicing
SECTION 2 - INSTALLATION
Outdoor flusher
Condensate Water Drainage Pump
(Refer to detailed instructions of the pump manufacturer)
Min Ø 19 mm
Inner
Pipe
75
Min Ø 19 mm
Inner pipe
Min Ø 30 mm
Inner pipe
Air hole
Combined waster
and rain water
drainage pipe
43 mm 90º
male/female bend
Water / Air
proof
insulation
68 mm Ø PVCU
Fitting
Min Ø 19 mm
Min Ø 30 mm
Drainage pipe with water
and air insulation
Maximum length of
the outer pipe
shall be 3 m.
Insert the drainage pipe
at least 25 mm into the tube
located outdoors
Pebble
≥ 500
≥ 25
Required
distance for
minimum 3-storey
buildings
Drainage and
Ventilation Pipe
Min Ø 19 mm
Water / Air proof
insulation
Outdoor flusher
Min Ø 19 mm
Inner pipe
75 mm flusher
bathroom/shower
drainage combined
with other drainage
lines
Minimum 30 mm
Inner pipe
Water / Air
proof
insulation
≥ 25 Distance under grid
45º pipe
termination
75
≥ 100
Figure 2.25
Connection of a Condensate Pump Typical
Method (see manufacturers detailed instructions)
Figure 2.26
Connection of condensate Drainage Pipe to
External Soil & Vent Stack
Figure 2.27
Connection of a Condensate Drainage Pipe to an
External Rainwater Downpipe (only combined foul/rainwater
drain)
Figure 2.29
Connection of a Condensate Drainage Pipe to an
External Purpose Made Soak Away.
Figure 2.28
Connection of Condensate Drainage Pipe
Upstream of a Sink, Basin, Bath or Shower Waste Trap to
External Drain, Gulley or Rainwater Hopper
INS
T
ALL
A
TION
CONDENSATE............ CONT’D
45º cross-
sectional drainage
pipe outlet
Open air flusher
Figure 18
Connection of Condensate Drainage to Rain Water Drainage
Min Ø 19 mm
Min Ø 19 mm
Drainage and Ventilation Pipe
≥ 100
Figure 2.23
Connection of Condensate Drainage Pipe to
Internal Soil & Vent Stack
Figure 2.24
Connection of a Condensate Drainage Pipe
Downstream of a Sink, Basin, Bath or Shower Water Trap to
Internal Soil Vent Stack
Minimum
connection
height
up to 3
storeys
Sink/basin/
bath or
shower
Drainage and Ventilation Pipe
Figure 13
Connection of the Condensate Water Drainage Pipe to Internal Drainage
and Ventilation Pipe
Min Ø 19 mm
Min Ø 19 mm
Drainage and Ventilation Pipe
≥ 100
Figure 2.23
Connection of Condensate Drainage Pipe to
Internal Soil & Vent Stack
Figure 2.24
Connection of a Condensate Drainage Pipe
Downstream of a Sink, Basin, Bath or Shower Water Trap to
Internal Soil Vent Stack
Minimum
connection
height
up to 3
storeys
Sink/basin/
bath or
shower
Drainage and Ventilation Pipe
Figure 14
Connection of Condensate Water Drainage Pipe at Indoor Bathroom
Drainage Lower Level