32

warmhaus.com

Error

Code

Description of the Error

Malfunction

Probable Cause

Solution(s)

E 15

Fan failure (feedback/

supply)

Boiler does not work,

E15 error code flashing
on the screen

> Fan harness

1-) Call for authorised service at first

2-) Check intermittent contacts or open contacts on harness carefully 
on fan main supply, if main supply not connected then fan will not 

operate and boiler will not ignite
3-) Check intermittent contacts or open contacts on harness carefully 

on fan PWM connection, if PWM connection not connected then fan will 

work at %100 capacity
4-) Reset & Restart boiler

E 16

Central heating 
temperature RETURN 

sensor faulty

Boiler does not work,
E10 error code flashing

on the screen

> Central heating RETURN 
temperature sensor faulty

1-) Call for authorised service at first
2-) Check intermittent contacts or open contacts on harness carefully

3-) Check RETURN Central heating temperature sensor ressistance 
according to page 93 at section 4.28 if its out of tolerance replace NTC
4-) Check cabeling and connectors between RETURN NTC and board

5-) Reset & Restart boiler

E 17

Temperature difference

between FLOW and LIMIT 
NTC (Double Heating 
Probe) faulty

FLOW and LIMIT sensor

(DOUBLE NTC) 
malfunction

> FLOW and LIMIT Sensor

( double NTC ) faulty

1-) Reset & Restart boiler

2-) Call for authorised service at first

E 19

Water flow selection with
water flow meter input 

reading

Lack of domestic heating
water on request

Wrong parameters settled on TsP 
menu

1-) Call for authorised service at first
2-) Only authorised service must adjust TsP Parameter P01=0 with 

defalut value

E 20

CH Overtemperature,

Temperature Central

Heating > TSP 81 value °C

Boiler does not work,

E81 error code flashing

on the screen

> Lack of water on the system

> Pump blockage

> Pump failiure
> Pump harness
> Installation blockage

1-) RESET boiler at first check if problem removed

2-) Check boiler central heating valves are open if they are closed open 
of all

3-) Check all radiator valves are open if they are closed open of all 
minimum 3 meters of radiator must be open
4-) RESET boiler and check if problem removed
5-) Call for authorised service at first

E 21

Delta Temperature
Central Heating flow

and Return > TSP 82 
value °C

Boiler does not work,
E21 error code flashing

on the screen

> Lack of water on the system
> Pump blockage
> Pump failiure
> Pump harness
> Installation blockage

1-) RESET boiler at first check if problem removed
2-) Check boiler central heating valves are open if they are closed open 
of all
3-) Check all radiator valves are open if they are closed open of all 

minimum 3 meters of radiator must be open
4-) RESET boiler and check if problem removed
5-) Call for authorised service at first

E 28

Maximum allowed 
consecutive lock-out reset 
reached

Usable RESET number
reached.

Too many consecutive lock-out 
failures (followed by reset) due to 
other possible causes

1-) Removing power supply reset will be allowed
2-) Check the root cause of Error code to solve
3-) If fault still persists call for authorised service

E 37

Low voltage anomaly

Boiler does not work,
E37 error code flashing
on the screen

Low voltage < 165 VAC +/- 5%
on the supply network operatio
mode OR During Au-TO calibration
mode < 182 VAC +/- 5%

1-) Call for Electrical supply network provider
2-) Error will remove if supply voltage > 170 VAC +/- 5%
3-) If you seen seen this E37 during calibration calibration can not be 

complete unless supply voltage > 188 VAC +/- 5%

E 40

Wrong network frequency
survey

Boiler does not work,
E40 error code flashing
on the screen

Wrong frequency survey out of
tolererance 50 Hz +/- 5% on the

supply net work

1-) Call for Electrical supply network provider

2-) Error will remove if supply frquency 50 Hz +/- 5%

E 41

Loose of flame more than
6 successive times

Boiler does not work,
E41 error code flashing
on the screen

> Too many domestic heat water

request in short period ( 1 min )
> Low gas pressure

1-) Call for authorised service at first

E 42

Buttons anomaly

Boiler does not work,
E42 error code flashing

on the screen

Wrong parameters settled on
TsP menu

1-) Call For service

E 43

Opentherm ommunication
error

Boiler does not work,
E43 error code flashing
on the screen after 1
minute of communucation 
error

Opentherm line disconnected

1-) Remove energy from boiler and re energised E43 will be removed 
and boiler & buttons will get back to funcitional
2-) Replace the room unit batteries with the fresh ones and reset from 
room unit
3-) Check cabeling between boiler and room unit and re connect if any 

disconnection, if connection set up succesfully then connection symbol 

page 37 symbol 19 will be activated on the screen
4-) Call for authorised service to re connect openterm connection

rE 44

Cumulated intermittent
ignition without reaching
burner ignition.

Boiler does not work,
E44 error code flashing
on the screen

> Intermittent contacts on harness
> Hammer effect on water net
> Too many request from in shotr

time from out side room units or
thermosad bridge etc.

1-) Reset & Restart boiler
2-) Call for authorised service at first

E 62

Calibration request

Boiler does not work,
E62 error code flashing on
the screen

> Calibration not done
> Replacing board but not service
key from the board dismantled
> Service key damaged or
disconnected
> Updating Software (probable)

1-) Call For service

E 72

Delta T heating at ignition 
not occurred

Boiler does not work,
E72 error code flashing on
the screen

> FLOW OR RETURN Sensor not on
position

1-) Call for authorised service at first
2-) Check RETURN and FLOW sensor on position.

Содержание EWA 24

Страница 1: ...CONDENSING COMBI BOILERS INSTALLATION USER MANUAL EWA24 EWA28 EWA33...

Страница 2: ...EWA 24 EWA 28 EWA 33...

Страница 3: ...mptying Radiator Installation 13 2 3 3 Circulation Pump 15 2 3 4 Controls for Initial Operation of Combi 15 2 3 5 Parts Comprising the Combi 16 2 4 COMBI FLUE CONNECTIONS 16 2 4 1 Exhaust Gas Flue Pip...

Страница 4: ...and instructions provided by the manufacturer under any circumstances during installation use or maintenance operations and device warranty shall also be void Only the authorized Warmhaus Service is...

Страница 5: ...YES II 2E 3P Natural Gas 20 mbar 25 mbar G20 Available Available Not Available BE FR YES II 2H3B P Natural Gas 20 mbar G20 Available Available Not Available AT CH CY CZ DK EE FI GR IT LT NO RO SE SI...

Страница 6: ...es operating with natural gas and your gas meter Immediately evacuate the place with gas odour Natural Gas Emergency Line from your neighbour or another suitable place Do not make any intervention on...

Страница 7: ...Figure 2 User s Guide Figure 5 Exhaust gas flue set 471 1000 GAS G3 4 G3 4 G3 4 80 mm 65 mm 65 mm 64 mm 725 mm 592 mm 422 mm G1 2 G1 2 75 mm 73 mm 110 m m 114 mm OPTIONAL Ewa Priwa ERP Priwa ERP Plus...

Страница 8: ...r semi full brick wall according to installation scheme and with connection screws and not to be used for other purposes In case of using different materials for installation combi shall be out of the...

Страница 9: ...2 2 7 In Case of Using LPG Tank LPG use is recommended for heat requirements over 24 kW New LPG stock tanks may contain settled gas residues nitrogen however that pauperises the mixture assigned to t...

Страница 10: ...ceptable to use gas and water connection pipes for earthing WARMHAUS A cannot be held as responsible for any damages and losses on individuals or commodities arising from failing to provide earth conn...

Страница 11: ...ensor is activated when connected as independent from the used room thermostat typology and functions as common with room thermostats The relation between installation input temperature and exterior w...

Страница 12: ...0 600021 WT RF03 Large Screen Modulated Weekly Program Scheduled Wireless room thermostat Product code 153 11 660 600022 150 cm Min 30 cm Room thermostat shall be mounted 1 25 to 1 5 m above the groun...

Страница 13: ...d in the hot tap water Hydrophore should be used if required Prior to filling the radiator installation it must be flushed and all wastes must be cleaned Warning In order to prevent invalidity of devi...

Страница 14: ...mum 3 storey buildings Drainage and Ventilation Pipe Min 19 mm Water Air proof insulation Figure 2 26 Connection of condensate Drainage Pipe to External Soil Vent Stack Connection of Condensate Draina...

Страница 15: ...ppointment request Gas opening approval certificate should be taken from the local gas company for your gas line Combi electricity connection should be made via 2 or 3 Amps fuse Figure 22 Ewa 28 Ewa 3...

Страница 16: ...on of hermetic combi should be original Warmhaus flue sets and they should be used by considering measurements and restrictions given in installation instructions In case of using exhaust gas pipe and...

Страница 17: ...ontent 10 00 tolerance 0 5 0 5 maximum allowable draught and maximum allowable pressure difference between combustion air inlet and flue gas outlet including wind pressures 120 Pa characteristics and...

Страница 18: ...t are given technical table c combustion product mass flow rate at minimum heat input allowed by the controls are given technical table d G20 CO2 or O2 content of the combustion products at nominal op...

Страница 19: ...H C R A I J K I L S B T U Likely flue positions requiring a flue terminal guard Figure 32 Environmental locations of flue Terminal Position with Minimum Distance mm A1 Directly below an opening air br...

Страница 20: ...5 mm when compared with the external pipe For security purposes combi suction discharge flue should not blocked even temporarily 1 90 bend 2 Sealing gasket 3 Sealing gasket 4 Centering wire 5 Exterio...

Страница 21: ...sed for 80 intake and exhaust pipes is 30 metres regardless from whether they are used for intake or exhaust Figure 41 Vertical flue set installation application Figure 42 Hermetic flue type installat...

Страница 22: ...rill fitted The air pipe can be situated at the side or beneath the flue pipe to a minimum dimension of 140 mm see Table 1 It must not be sited above the flue pipe The flue and air pipes must extend b...

Страница 23: ...apter L 1533 153 11 660 600013 60 100 Condensed Flue Extension L 500 mm 153 11 660 600014 60 100 Condensed Flue Extension L 1000 mm 153 11 660 600015 60 100 Condensed Flue Extension L 2000 mm 153 11 6...

Страница 24: ...m 153 11 660 600092 80 Condensed Twin Flue Extension Pipe L 1000 mm 153 11 660 600093 80 Condensed Twin Flue Extension Pipe L 2000 mm 153 11 660 600094 80 Twin Flue Bend 90 153 11 660 600095 80 Twin F...

Страница 25: ...minals For GB recommendations are given in BS 5440 Pt 1 For IE recommendations are given in the current edition of I S 813 Domestic Gas Installations 2 If the terminal discharges onto a pathway or pas...

Страница 26: ...ut is not blocked If a room thermostat or control device is connected ensure that it is at ON position If you will shut off the combi for a long period perform below written operations Discharge the r...

Страница 27: ...he combi and eliminating the failure in case of combi failure MODE Winter Summer OFF mode is used for position adjustment Operating positions and related notifications POSITION EXPLANATIONS CLOSED or...

Страница 28: ...re adjustment buttons see Figure 39 between 25 80 C screen lights when buttons are pressed and C symbol flashes besides the radiator temperature value If you have a ground heating system as our Author...

Страница 29: ...ght turns off Analogue manometer is located near to right bottom side of the combi Installation pressure should be seen in this manometer even in the absence of electricity If you have a ground heatin...

Страница 30: ...ment of installation place Thus the combi automatically operates with variable gas flow rates depending on heat load of installation between the minimum and maximum power P21 Lowe temperature region s...

Страница 31: ...4 RESET boiler and check if problem removed 5 Call for authorised service at first E 07 Safety thermostat intervention Boiler does not work E07 error code flashing on the screen Lack of water on the...

Страница 32: ...removed 5 Call for authorised service at first E 28 Maximum allowed consecutive lock out reset reached Usable RESET number reached Too many consecutive lock out failures followed by reset due to other...

Страница 33: ...ssure Aging or rust on the electrode Recirculation on fluegas path Blokage on flue or wrong flue Electrode position Cabeling disconnections Combustion calibration Electronic board Gas valve failiure 1...

Страница 34: ...lve failiure Electronic board 1 Call for authorised service at first 2 Check wrong flue OR flue gas blockage 3 Check recirculation flue gas leak from flue gas path to fresh air side check flue gas sea...

Страница 35: ...least execute maintenance operations on a yearly basis in compliance with what is stated in the relative point at annual check and maintenance of the appliance in compliance with national regional or...

Страница 36: ...400 2400 2400 Pump Energy Efficiency Index EEI 0 20 0 20 0 20 Domestic Hot Water Circuit Maximum DHW Heat Input kW 25 8 29 7 34 2 Minimum DHW Heat Input kW 3 5 3 75 4 35 Max Domestic Hot Water flow ra...

Страница 37: ...on was determined by applying the spesifications of the relevant European directives Differences to product information listed elsewhere may result in different test conditions Only the data that is c...

Страница 38: ...ual electricity consumption AEC kWh 26 37 34 39 42 Water Heating Energy Efficiency hwh 81 84 83 84 82 Daily fuel consumption Qfuel kWh 14 809 23 152 23 615 23 078 29 317 Annual fuel consumption AFC GJ...

Страница 39: ...been carefully prepared but we reserve the right to make changes and improvements in our products which may affect the accuracy of the information contained in this leaflet All goods are sold subject...

Страница 40: ...Ewa Installation User Manual code 150 11 606 000075 Revision Date R00 05 2019 EWA24 EWA28 EWA33 CONDENSING COMBI BOILERS INSTALLATION USER MANUAL...

Отзывы: