COMMISSIONING INSTRUCTIONS
TR05A140.B1107
41
Parameter 21 – Ignition sequence fan speed
Access the parameters menu as described in Section 5.7.1.
Use the
&
buttons to adjust the parameter value:
Minimum value determined by Parameter 17
Maximum value determined by Parameter 18
Note: Factory preset to 110 = 110 Hz
Press and release the
S
button.
The parameter number (21) will appear on the display.
To store your changes, switch the appliance off then on again using
the
ON/OFF
button.
Parameter 22 – Fan speed display mode
Access the parameters menu as described in Section 5.7.1.
Use the
&
buttons to adjust the parameter value:
00 = Off
01 = On (Fan speed displayed for 10 minutes)
Press and release the
S
button.
The parameter number (22) will appear on the display.
To store your changes, switch the appliance off then on again using
the
ON/OFF
button.