background image

 

Instructions condensing  Air heaters type XR version XR-GB-4001-a 

 

 

 

 

Page 9/25 

 

4.2  Gas connection 

The gas supply line has to meet the national valid requirements and possibly the local 
requirements of the building inspector, police or fire brigade. (In GB it must comply with Gas 
Engineers publication UP-1 and UP-2 together with BS 6891. 
A manual isolation valve in the supply line must be placed within reach of the heater, and all gas 
lines must be mounted without any mechanical tension.  
When  testing the supply lines with pressures above 60 mbar, this manual valve at the heater 
must be closed. 
The working and standing  supply pressure must be a minimum of 17 mbar, and a maximum of 
30 mbar ,measured at the inlet pressure nipple of the gas control in the heater  
In case the heater needs to be converted to another gas type contact your supplier. It can only 
be converted by the manufacturer or its representative. 

4.3  Electrical connection 

4.3.1 230Vac supply 

The installation must comply with local and 
national requirements, ( as well as IEE 
regulations) 
Never use a room thermostat to interrupt the 
electrical supply to the heater!  
Make provisions to completely isolate the heater for maintenance purposes. This can be an 
isolation switch (min.3mm contact opening gap) , a power plug or a non-switched fuse spur.  
The wiring diagram for the heater can be found towards the end this manual. 
The supply is 230Vac. with earth. The control circuit is a two wire low voltage bus 
communication. 

4.3.2 Room thermostat 

The heater can only be controlled by special modulating Winterwarm room thermostats: 

The Multi Therm Comfort

; modulating digital clock thermostat with optimiser. It can control 1 to 

8 air heaters HR10 up to HR60 or 1 to 4 air heaters HR80 up to 120. 

The Multi Therm Standard

; modulating digital thermostat. It can control 1 to 8 air heaters 

HR10 up to HR60 or 1 to 4 air heaters HR80 up to 120. 

The Interface printboard

; special designed interface module for connecting the air heaters with 

Building Mangagement Systems. (0-10V (modulating input) signal, high/low signal, 
external reset and other different in and outputs. 

ON/OFF thermostat 

The heater cannot be controlled with a simple on/off thermostat.  

 
In all cases the communication between heater and thermostat is based on a two wire, low-
voltage connection. In the appliance the wire for the thermostat has to be connected to 
connection 4 and 5 (see also electrical wiring diagram) Attention: This also needs a change in 
the settings on the print board. 

4.3.3 Thermostat installation 

When mounting the thermostat, take attention to the following items: 

  Mount the thermostat in a place where the air can circulate free pass the thermostat. Take 

notice that the sun does not shine directly upon the thermostat (in the winter). Do not 
place the thermostat on a cold wall. Place the thermostat on an inner wall free from 
draught.  

  Never place the thermostat within the throw of the heater.  

  Never mount the thermostat near aerials of internal communication networks. These emit 

radiation that could lead to disturbance of the thermostat. Always keep some meters 
distance. 

Содержание XR Series

Страница 1: ...on from 2019 THIS DOCUMENT MUST ABSOLUTELY BE READ BEFORE STARTING THE INSTALLATION INSTRUCT USER AND LEAVE THIS DOCUMENT WITH HEATER FOR REFERENCE Date 01 02 2019 Instruction manual version XR GB 400...

Страница 2: ...L 11 5 FUNCTIONING OF THE UNIT 14 5 1 GENERAL 14 5 2 BURNER CYCLE 14 5 3 DELTA T REGULATION TEMPERATURE CONTROLLED DE STRATIFICATION FAN 14 5 4 SUMMER VENTILATION 14 5 5 HIGH LIMIT PROTECTION 15 5 6 F...

Страница 3: ...switch The main gas switch should be situated upstream in the gas line near the heater Turn off all electric power to the appliance After working on the heater always check for gas leaks Close the doo...

Страница 4: ...be prevented that chlorine or other corrosive containing vapours are sucked into the air intake These vapours will result in corrosion of the heat exchanger and a leakage of condensate and flue gas De...

Страница 5: ...0 450 0 450 0 600 Electrical Power stand by kW 0 004 0 004 0 004 0 004 0 004 0 004 Electrical Current max A 1 1 1 1 1 1 2 0 2 0 2 6 Emission efficiency s flow 96 1 93 3 90 6 91 7 91 2 90 8 Seas space...

Страница 6: ...Instructions condensing Air heaters type XR version XR GB 4001 a Page 6 25...

Страница 7: ...of the heater The heater can be installed horizontally or on an angle of maximum 45 degrees downwards When the heater is installed other than horizontal Always re adjust the CO2 setting from the gas...

Страница 8: ...001 a Page 8 25 Available suspensions Standard bracket Design bracket Horizontal or vertical horizontal vertical rotatable XR10 30 GA 8610 XR10 30 GA 8630 XR40 60 GA 8620 Suspension kit vertical Suspe...

Страница 9: ...w voltage bus communication 4 3 2 Room thermostat The heater can only be controlled by special modulating Winterwarm room thermostats The Multi Therm Comfort modulating digital clock thermostat with o...

Страница 10: ...roof or wall terminal and also for the piping between the heater and the terminal Only so the installation is approved Do not use terminals for condensing appliances This can lead to water inside the...

Страница 11: ...tem This however will evaporate if the heater is operating for a longer period of time If the straight length of the discharge flue is longer than 4 meters this condensation will not evaporate again a...

Страница 12: ...the clamp yet 9 Fit the gasket and the twin tube connection Make sure that the gasket is not damaged Ensure that the flue tube and the air inlet tube are not exchanged the flue tube is the pipe in the...

Страница 13: ...only with allowed lubricant from the manufacturer Maximum 1 of soap or water is allowed ATENTION Do not use grease Vaseline or oil Fixation Fix every elbow on or near the socket Exception when connect...

Страница 14: ...Burner off Gas valve closes the flame stops 11 Post Purge Burner fan purges with fresh air System fan cools the heat exchanger Minimum burn time 4 minutes The heater will always burn minimum 4 minutes...

Страница 15: ...age 6 Putting into operation and adjustment 6 1 General Prior to packaging each unit is checked in detail on safety and functioning It is adjusted to the right efficiency of combustion In general the...

Страница 16: ...rews to adjust the gas control the Offset adjuster and the Ratio adjuster The Offset adjuster is used in Low fire The Ratio adjuster is used in High fire Put the heater into operation at high fire thr...

Страница 17: ...urner fan Burner fan does not work 6 L 6 L 7 Burner fan Burner fan rotates at the wrong speed 7 L 8 9 10 11 12 Internal error Internal error 13 L 13 Pressure switch Pressure switch is closed in stand...

Страница 18: ...ltage too hot E 67 Pressure switch Too many pressure switch errors 11 E 68 Flue temp sensore Flue temperature too high 3 E 69 internal Appliance temporarily paused automatic restart will follow 13 War...

Страница 19: ...k the error code after a new power up Case 13 Internal error Power up the heater again else replace the print board Case 14 Pressure switch closed during stand by When the heater is in standby the pre...

Страница 20: ...the inspection switch off the electric power to the heater with the maintenance switch and close the manual gas valve Take out the burner complete with flange and pre mix fan by unscrewing the 6 off M...

Страница 21: ...d to be set as follows S1 switch 1 at the ON position and J14 at 1 The change of these switches need to be performed without power on the Heater otherwise these settings take no effect 9 3 Installatio...

Страница 22: ...ype XR version XR GB 4001 a Page 22 25 PE L 5 4 N 5 4 5 4 5 4 22 C L N PE L N L N PE L N L N PE L N L N 1 2 3 4 5 6 7 8 ON 1 0 1 2 3 4 5 6 7 8 ON 1 0 S1 J14 1 2 3 4 5 6 7 8 ON 1 0 1 2 3 8 1 2 3 22 C L...

Страница 23: ...N 5 6 RT N L 230 Vac L N 11 12 22 C 20K 25 C 22 C F1 20K 25 C 20K 25 C J9 1 J9 3 J9 2 J9 4 J6 1 J6 8 J6 2 J6 9 J6 3 J6 10 J6 4 J6 11 J6 5 J6 12 J6 6 J6 13 J7 1 J7 2 J7 3 J7 4 J7 5 J7 6 J7 7 J7 8 J7 9...

Страница 24: ...GA3000 GA3000 GA3000 GA3000 GA3000 GA3000 7 System fan IX4201 IX4201 IX4201 IH4206 IH4206 GX4207 8 Main board EBM 966 GY5901 GY5901 GY5901 GY5901 GY5901 GY5901 9 Pressure switch GX3932 GX3932 GX3932...

Страница 25: ...Instructions condensing Air heaters type XR version XR GB 4001 a Page 25 25 11 3 Exploded view XR40 60 11 5 6 13 8 1 2 9 12 11 14 10 7...

Отзывы: