3

warema_890012_alhb_en_v12•2022-05-01

We reserve the right to make technical modifications

Technical data

Switch actuator 4/6M  

REG/AP

Min.

Typ.

Max.

Unit

Supply

Operating voltage (SELV)

20

24

28

V DC

Current consumption

55

90

160*

mA

* If more than 8 permanently active outputs are used, the power sup-

ply must be laid out for a maximum current requirement of 160 mA.

Motor output, floating**
Alternating current

207

230

253

V AC

Switching capacity per output  

at 230 V AC/cos φ = 0.6

500

VA

DC voltage

11

24

30

V DC

Current capacity (DC)

3

A

Light output, floating**

230 V AC bulbs

700

W

230 V AC halogen lamps

800

VA

LV halogen lamps with 

electronic transformer

700

VA

Fluorescent lamps with conven-

tional ballast

700

VA

Fluorescent lamps with  

electronic ballast

1000

VA

** The total power of all 4 outputs per fuse must not exceed 

1000 VA.

Inputs, local operating elements (general purpose)

Local voltage active

8

24

36

V DC

Local current active

1

1.5

2

mA

Local voltage inactive

-0.5

0

4

V DC

Dimensions

DIN rail-mounted housing 

(REG)

See Fig. 2

Surface-mounted housing (AP)

See Fig. 4

Degree of protection/safety class

Degree of protection AP/REG

IP30

Safety class

I

Miscellaneous

Conformity

available at 

www.warema.de/ce

The device meets the EMC directives for use in residential and 

commercial areas.

Ambient conditions

Operating temperature

0

20

50

°C

Storage temperature

0

20

50

°C

Humidity (non-condensing)

10

40

85

%H

rel

Pollution degree

2

Connection

Screw terminals

0.2...2.5 mm²

Spring-loaded terminals

0.6...0.8 mm ø

Article numbers

Switch actuator 6M REG

1002 652

Switch actuator 6M AP

1002 704

Switch actuator 4M REG

1002 655

Switch actuator 4M AP

1002 703

Pull relief set

1002 236

WAREMA Renkhoff SE

Hans-Wilhelm-Renkhoff-Strasse 2

97828 Marktheidenfeld, Germany

60 mm

95 mm

90 mm

210 mm / 157 mm *

* 6M: 

  12 MW / 210 mm

  4M:

    9 MW / 157 mm

    

60 mm

Fig. 2 

 DIN rail-mounted housing dimensions

Remove the terminal covers: 

Insert a suitable screwdriver 

into the notch.

Fig. 3 

Detaching the terminal covers

210 mm**

158 mm

119 mm

 184 mm*

132 mm

*  6M: 184 mm

   4M: 132 mm

** 6M: 210 mm

   4M: 158 mm

180 mm

60 mm

3 ‒ 4 mm

Fig. 4 

 Surface-type housing dimensions