Transmission to the next phase occurs only when the temperature of the exhaust gas rises over
the smallest allowable value (50 °C).
If this phase does not occur within the allowable 1500-second interval, the pellet boiler enters
into alarm status due to the lack of ignition.
STABILIZATION CONDITION
After reaching the 50°C minimum temperature, the ignition switches off. One has to wait for the
prescribed flame stability, and a temperature rise of at least 3°C/minute. This status lasts for
approximately 180 seconds.
If this condition does not occur, the boiler enters into alarm status due to the irregular flame.
OPERATING CONDITION
The boiler switches on the room temperature fan at 90°C exhaust gas temperature.
OPERATION
The pellet boiler starts to operate.
TIMER
(setting of the timer)
With the timer function, the boiler can be programmed for a week in advance.
(Boiler IN, OFF
/ temperature settings:
comfort, normal, eco.)
To open the menu for setting the timer, press the P1 key for 3 seconds.
To activate the timer setting: "SCHALTUHR-AKTIV." (P4, P5, P6 keys).