SEP.QE_SEPCOM_SIP-BED-EASY--.M.A3.0722.EN Issue: A3
07.22
4.0 SETTING THE OPERATING PANEL & USE
QE SEPCOM SIP BED EASY
It is recommended to set the local date and time upon each new installation in order to correctly display the
alarm history on the menu. Follow the steps below:
1.
Enter the PLC main screen
2.
Place two fingers in the top-right and bottom-left corners of the screen, being careful not to touch any key.
3.
Tap the two corners of the screen quickly and alternately until a new screen appears on the monitor
4.
Tap on the “System” folder
5.
Tap on “Date/time”
6.
Type the local date and time by tapping in the corresponding areas of the screen and entering the values
using the numeric keypad that pops-up.
7.
Tap “Enter” when finished.
8.
Tap “OK” to confirm the values set.
9.
Rap “RUN” to enable changes
The PLC will automatically return to the main screen.
This key (no password required) displays the log of alarms active on the system.
4.4 How to change time and date
4.5 Alarms