30
Watlow Series 935B User’s Manual
Configuration Menu
[``In]
Input Type
[`C_F]
Celsius/Fahrenheit
[``rL]
Input Range Low
[``rH]
Input Range High
[`Ot1]
Output 1 Function
[`Ot2]
✓
Output 2 Function
[`rts]
✓
Remote Timer Start
[dISP]
✓
Display Default
[ALtY]
Alarm Type
[AhYS]
Alarm Hysteresis
•
•
•
[tIM]
✓
Timer Function
[Strt]
✓
Start Timer
[`rdY]
✓
Timer Ready Band
[``St]
✓
Signal Time
Operations Menu
[`Aut]
Auto-tune
[tMr]
✓
Countdown Timer
[IdLE]
✓
Idle
Key Timer Information
• The timer requires Output 1 to work as either a heat or as a cool output.
• The 935B timer is a function of Output 2, a switched dc output.
• Hours: minutes (hh:mm) or minutes:seconds (mm:ss)
choices reside in Output 2
[`Ot2]
.
• Timer set-up occurs in two locations,
in the Configuration Menu and the Operations Menu.
•
,
starts the timer.
•
.
stops the timer.
•
choices set up the timer display (see p. 18).
• LED colon flashes when timer runs.
LED colon ON steadily when timer is not running.
Configuration Menu set-up includes:
• Output 1
[`Ot1]
; heat
[hEAt]
or cool
[COOL]
• Output 2
[`Ot2]
; timing interval,
hours:minutes
[thM]
, or minutes:seconds
[tMS]
• Remote Timer Start
[`rts]
choices:
1. Manual start
[`off]
2. Remote Timer Start
[tmr]
3. Front Panel Lockout
[`fpl]
• Timer (Output 2) function
[tIM]
hours: minutes or minutes:seconds
(
[thm]
or
[tms]
) can perform one of four possible actions after timing:
1. Turn ON, also called, “delay ON”
[dLon]
2. Turn off, also called, “delay off”
[dLof]
3. Toggle ON, also called, “signal ON”
[sgon]
4. Toggle off, also called, “signal off”
[sgof]
• Start timer function
[Strt]
choices:
1. Immediate start
[IMd]
2. Start once inside a ready band
[`rdy]
3. Start once inside a ready band,
acknowledging
[rdya]
with a
ß
press
4. Start immediately on control power up
[PWr]
without waiting for
Ready Band temp. or
,
press.
• Ready band width
[`rdy]
above and below set point: degrees
• Signal time
[``St]
(if applicable) duration: seconds
Operations Menu set-up includes:
• Countdown Time
[tMr]
:
hours:minutes or minutes:seconds
• Idle Set Point Type
[IdLE]
, two choices:
1. Track primary set point
2. Set an idle set point
The next page presents this information
in graphic format with additional detail.
30
15
45
0
Learn the Countdown Timer