Watlow Series 935B User’s Manual
23
Table 8 - Setting Inputs and Outputs
NOTE: Access to Configuration Menu varies with lockout function.
Input Type -
Choose sensor type.
[```J]
[```H]
[```t]
[```n]
[```E]
[```S]
[`rtd]
[`r†d]
J t/c
K t/c
T t/c
N t/c
E t/c
S t/c
1.0° RTD
0.1° RTD
Celsius/Fahrenheit -
Choose displayed unit of measure.
[``°F]
[``°C]
°F
°C
Input Range Low -
Select lowest displayable Set Point, dependent on
[``In]
.
[``In]
[``rh]
Select a value (lowest displayable set point) between
Input Type Range Low and Input Range High.
Input Range High -
Select highest displayable Set Point, dependent on
[``In]
.
[``rL]
[``In]
Select a value (highest displayable set point) between
Input Type Range High and Input Range Low.
Output 1 Function -
Choose Output 1 type.
[hEAt]
[COOL]
[ALM]
[nonE]
Heat
Cool
Alarm
None
Output 2 Function -
Choose Output 2 type (dependent on Output 1 choice).
[hEAt]
[COOL]
[ALM]
[thM]
[tMS]
[nonE]
Heat
Cool
Alarm
Timer
Timer
None
Hr./Min.
Min./Sec
Remote Timer Start -
Choose Off, Front Panel Lock, or Timer (Hrs:Min).
[`off]
[`fpl]
[tmr]
Off
Front Panel Timer
Lock
Display Default -
Choose the primary (last 2 characters) and secondary (first 2 characters) default displays. Press
ß
to toggle to the secondary display for 15 seconds.
[``Ac]
[[AcSP]] [Acti]
[tiAc]
[tiSP]
No secondary
Actual temp.
Actual temp.
Time remaining Time remaining
Actual temp.
Set pnt temp.
Time remaining Actual temp.
Set point temperature
Input Range Information
J t/c:
32
to
1382°F
or
0
to
750°C
K t/c:
-328
to
2282°F
or
-200
to
1250°C
T t/c:
-328
to
662°F
or
-200
to
350°C
N t/c:
32
to
2282°F
or
0
to
1250°C
S t/c:
32
to
2642°F
or
0
to
1450°C
E t/c:
-328
to
1470°F
or
-200
to
799°C
1° RTD (DIN):
-328
to
1292°F
or
-200
to
700°C
0.1° RTD:
-99.9
to
999.9°F
or
-99.9
to
700.0°C
Valid Output Functions
First select
Output 1:
Then select
Output 2:
Heat
None, Cool, Alarm, Timer
Cool
None, Heat, Alarm, Timer
Alarm
None, Heat, Cool
None
Heat, Cool, Alarm
• The function of Output 1 determines the options available for
Output 2.
• First select the function of Output 1. Refer to the table (right),
then select the function of Output 2.
[``In]
[`C_F]
[``rL]
[``rh]
[`rts]
[`Ot2]
[dISP]
Configuration Menu
[`Ot1]