5.4.
Connect the Input and Output Cables
The control unit has input and output sockets in the lower panel of the unit.
Refer to
Figure 2
for the illustration of the lower panel.
Figure 2.Connectors in the WDC100 control unit
Item
No.
Description
Function
1
Output to WC Flush Valve
Opens WC Flush Valve
2
Output to Shower Valve
Opens Shower Valve
3
Output to Basin or bath Valve Cold Opens Basin/bath Valve Cold
4
Output to Basin or bath Valve Hot
Opens Basin/bath Valve Hot
A
Input from WC Flush Piezo touch
button
User input (Piezo button or IR sensor) for
WC Flush
B
Input from Shower Piezo touch
button
User input (Piezo button or IR sensor) for
Shower
C
Input from Basin or bath Cold
touch button
User input (Piezo button or IR sensor) for
Basin/bath Cold
D
Input from Basin or bath Hot
touch button
User input (Piezo button or IR sensor) for
Basin/bath Hot
E
Auxiliary 1
Auxiliary input set to Remote L.O.
F
Auxiliary 2
Auxiliary input set to Remote Flush
G
Auxiliary 3
Auxiliary input set to Half Flush
IN
Left RJ45 Socket
Ethernet Input
OUT
Right RJ45 Socket
Ethernet Output
Auxiliary Inputs, E, F, and G are used when it is necessary to:
Lockout or disable the basin/bath, shower and WC from a remote switch.
Remotely flush the WC pan.
Activate a reduced flush for the WC pan with an additional touch button or IR sensor.
Clear lock outs.
Purge.
Connect a hygiene purge water flow sensor.
Table 2. Legend for Figure 2