DE
1.
Number of Chargers: Input the number of chargers including the Primary charger
2.
Maximum current per phase: It is the maximum current that can be supplied to the charging network
This value is usually the rated current of the MCB.
3.
Minimum current per charger: From 6 A to 10 A. The default value is 6 A
4.
The maximum current that can be supplied to the electrical installation.
This value is the rated current of the mains circuit breaker that protects the electrical installation..
Primary Charger Configuration
PT
1.
Number of Chargers: Input the number of chargers including the Primary charger
2.
Maximum current per phase: It is the maximum current that can be supplied to the charging network
This value is usually the rated current of the MCB.
3.
Minimum current per charger: From 6 A to 10 A. The default value is 6 A
4.
The maximum current that can be supplied to the electrical installation.
This value is the rated current of the mains circuit breaker that protects the electrical installation..
Primary Charger Configuration
NL
1.
Number of Chargers: Input the number of chargers including the Primary charger
2.
Maximum current per phase: It is the maximum current that can be supplied to the charging network
This value is usually the rated current of the MCB.
3.
Minimum current per charger: From 6 A to 10 A. The default value is 6 A
4.
The maximum current that can be supplied to the electrical installation.
This value is the rated current of the mains circuit breaker that protects the electrical installation..
Primary Charger Configuration
SV
1.
Number of Chargers: Input the number of chargers including the Primary charger
2.
Maximum current per phase: It is the maximum current that can be supplied to the charging network
This value is usually the rated current of the MCB.
3.
Minimum current per charger: From 6 A to 10 A. The default value is 6 A
4.
The maximum current that can be supplied to the electrical installation.
This value is the rated current of the mains circuit breaker that protects the electrical installation..
Primary Charger Configuration
FR
1.
Number of Chargers: Input the number of chargers including the Primary charger
2.
Maximum current per phase: It is the maximum current that can be supplied to the charging network
This value is usually the rated current of the MCB.
3.
Minimum current per charger: From 6 A to 10 A. The default value is 6 A
4.
The maximum current that can be supplied to the electrical installation.
This value is the rated current of the mains circuit breaker that protects the electrical installation..
Primary Charger Configuration
CA
1.
Number of Chargers: Input the number of chargers including the Primary charger
2.
Maximum current per phase: It is the maximum current that can be supplied to the charging network
This value is usually the rated current of the MCB.
3.
Minimum current per charger: From 6 A to 10 A. The default value is 6 A
4.
The maximum current that can be supplied to the electrical installation.
This value is the rated current of the mains circuit breaker that protects the electrical installation..
Primary Charger Configuration
IT
1.
Number of Chargers: Input the number of chargers including the Primary charger
2.
Maximum current per phase: It is the maximum current that can be supplied to the charging network
This value is usually the rated current of the MCB.
3.
Minimum current per charger: From 6 A to 10 A. The default value is 6 A
4.
The maximum current that can be supplied to the electrical installation.
This value is the rated current of the mains circuit breaker that protects the electrical installation..
Primary Charger Configuration
ES
1.
Number of Chargers: Input the number of chargers including the Primary charger
2.
Maximum current per phase: It is the maximum current that can be supplied to the charging network
This value is usually the rated current of the MCB.
3.
Minimum current per charger: From 6 A to 10 A. The default value is 6 A
4.
The maximum current that can be supplied to the electrical installation.
This value is the rated current of the mains circuit breaker that protects the electrical installation..
Primary Charger Configuration
NO
1.
Number of Chargers: Input the number of chargers including the Primary charger
2.
Maximum current per phase: It is the maximum current that can be supplied to the charging network
This value is usually the rated current of the MCB.
3.
Minimum current per charger: From 6 A to 10 A. The default value is 6 A
4.
The maximum current that can be supplied to the electrical installation.
This value is the rated current of the mains circuit breaker that protects the electrical installation..
Primary Charger Configuration
Содержание PULSAR
Страница 1: ...Manual DYNAMIC POWER SHARING...
Страница 25: ...Commander Connection with Energy Meter Carlo Gavazzi EM340 EM112 EM330 Temco SPM1 100 AC D D GND GND D D 12 V...
Страница 29: ...Copper C GND D D Temco SPM1 100 AC GND 12V D D Carlo Gavazzi EM340 EM112 EM330 Connection with Energy Meter...
Страница 32: ...Energy Meter EM 340 7 9 8 10 A T D RS485B B D RS485A GND GND EM 340 Wallbox 7 8 10 11 12 9 N N 1 2 3 4 5 6...
Страница 33: ...Energy Meter EM 112 3 4 5 6 7 8 N N 1 2 3 5 4 6 A T D RS485B B D RS485A GND GND EM 112 Wallbox...
Страница 38: ...1 2 3 4 5 6 Temco SPM1 100 AC 12 V GND RS485 RS485 CURRENT DIRECTION CABLE...
Страница 42: ...Connection between chargers Commander 2 CAN H CAN H CAN L CAN L T Connection NT Connection CAN NT T...
Страница 43: ...Connection between chargers CAN T NT Copper SB Rev B CAN H CAN H CAN L CAN L T Connection NT Connection...
Страница 46: ...CAN H CAN L T Connection Commander Connection between chargers...
Страница 47: ...1 2 3 4 5 6 7 8 9 0 Pulsar CAN L CAN H T Connection Secondary only con nection...
Страница 59: ......
Страница 60: ...support wallbox com...