background image

27-05-19 UNI-SAN Domestic Instructions Page 11 

 

 

 
DO NOT DISCHARGE LIQUID INTO THE PUMP IF IT IS NOT OPERATING. 
 
NOTE  In the warranty period, any work not described in this manual must be carried out by Wallace Pumps Service 
Agents otherwise your warranty and the product's durability period will be invalidated. 

 
ALWAYS ensure isolation and disconnection of the power supply

 to the pump before and whilst carrying out 

any servicing work on the unit. Also ensure no liquid will flow into it during servicing. 
 

 

OCCURRENCE 

 

POSSIBLE CAUSE

 

REMEDY 

 

1. -Motor 

runs 

continuously 
without clearing 
the liquid. 
 

- Switch operated by water level 
remains in the ON position 
because : 
a. pipework is blocked; or 
b. pump is blocked; or 
 
 
 
c. tank is blocked; or 
d. check valve installed back to 
front 
e. delivery hose is kinked. 

 
 
 
-Check that the pipework is clear. 
-Turn off the power and check that the pump can 
rotate freely in both directions by turning the 
shaft at the top end of the motor with a 
screwdriver. 
-If blocked, clear the obstruction. 
- Reverse the valve. 
 
-PVC Pipes are recommended. 

 
2. 

-Pump runs but 
delivers little or no 
liquid. 
 

-Delivery head (combination of 
vertical and  horizontal pipe 
lengths, pipe bends and size) is 
too high for the unit. 
 

-Check the system against the pump operating 
parameters. Refer Section 5 (Building design). If 
the building or application design is in excess of 
the pump capability shown on the chart, call our 
office for advice. 
 
-Check that the pump is not pumping the water 
level down too low. ( Refer fault 9 below ). 

 
3. 

 
- Pump starts but 
takes over 10 
seconds to reduce 
the liquid level in 
the tank 
 ( as seen through 
the inspection lid). 

 
-Delivery line is partially blocked 
or too small. 
 
 
-Wrong type of delivery valve 
used ; eg spring poppet type  
 
-Float level switch is too long. 
 
 
-Float level switch is hung up. 
 
-Float or pressure switch is 
faulty. 
 
-Pump is not venting. 
 
 
 
 
 
 
 
 
 
 
 
 
-Tank is not venting 

 
-Unblock and/or change the pipework  to the 
minimum ID. Refer Section 5( Hydraulic 
capability ). 
 
-Always use a 25 swing check valve in a vertical 
position within 1 metre of pump. 
 
-Check that the pump is not pumping the water 
level down too low. (Refer fault 9 below). 
 
-Remove the obstruction via the inspection lid. 
 
-Replace the switch. 
 
 
-Visually check that the tank vent pipe is clear ; 
or by releasing the pipe from the tank and blow 
down it; or by removing it and flush clean. 
-Check that the vent functions: 
. Liquid should rise in the vent tube until the 
pump starts; 
.When the pump runs, little or no liquid should 
flow through the vent tube. Remove the 
inspection lid to check the return flow into the 
tank; 
.When the pump stops, the liquid in the vent 
tube should draw down to empty. 
 
-Check that the pump is not pumping the water 
level down too low. (Refer fault 9 below). 

Содержание UNI-SAN

Страница 1: ...l view and connections 2 2 Product overview 3 3 Applications 3 4 Features benefits 4 5 Overall building design and Pump hydraulic capability 4 6 Warning for your safety 5 7 List of fittings supplied r...

Страница 2: ...k except over the float switch for fixtures or appliances which have an overflow level higher than the unit Allow room for the back nut when cutting the hole Check that either the inflow liquid or the...

Страница 3: ...there is one for domestic applications and one for commercial Both units are the same dimensions and pumping performance the major differences are in the materials of construction level control and mo...

Страница 4: ...ensions and hydraulic capabilities of the unit Ascertain that the combined inflows into the unit at any time do not exceed 35 litres min Measure the overall height of the delivery pipework from the bo...

Страница 5: ...g are coloured in accordance with the following code Earth Green Yellow Neutral Blue Phase Brown 7 LIST OF FITTINGS SUPPLIED AND RECOMMENDED EXTRAS 7 1 Unpacking And Inspection Your UNI SAN package sh...

Страница 6: ...The connection to the soil and waste drain system must be carried out in accordance with the Building and Plumbing Code The connection of the unit s delivery pipe to a soil or waste pipe should be kep...

Страница 7: ...nk to the valve socket 40 50mm Waste Pipe DRAIN from Floor Waste Gully Trap plumbed as per Appendix C Figure 7c to the valve socket 50 100mm Waste Pipe VENT from WALLACE UNI SAN to approved terminatio...

Страница 8: ...BSPF Refer to Section 5 Hydraulic capability to determine the correct pipe size from this connection Slip the delivery pipe in the ends of the swing check valve supplied Check the direction of flow a...

Страница 9: ...leaned regularly The unit is not designed as a kitchen waste disposal unit or for the disposal of sewage Refer to our office for the UNI SAN model or other options 10 2 External cleaning The external...

Страница 10: ...unit or any other property caused by any un authorised modifications repairs in contravention with the Company s instructions or by use of materials or fittings not supplied by Wallace Pumps Where a c...

Страница 11: ...parameters Refer Section 5 Building design If the building or application design is in excess of the pump capability shown on the chart call our office for advice Check that the pump is not pumping th...

Страница 12: ...the pump Remove the obstruction Fit 25 mm SWING CHECK VALVE supplied installed in a vertical section of pipe as close as possible within 1 metre of the pump 7 Pump runs and makes a rattling noise Soli...

Страница 13: ...otor and pump assembly Do NOT overtighten Check the condition of the o ring Make sure it is not pinched Replace if necessary Check the pressure on the o ring Adjust the 4 nuts as per above Do NOT over...

Страница 14: ...ND OR BATH CONNECTED Install unshared UNI SAN Bottom Inlet Valve and waste trap for each OVERFLOW PROTECTION Our warranty excludes any damage caused by an overflow Because of the danger of flooding ca...

Страница 15: ...turn non clog full flow ball valve must be installed in a vertical position in the delivery line within a metre of the pump 4 an OVERFLOW PIPE should be installed to maintain the maximum 900mm height...

Отзывы: