24
Section 5:
Electrical Installation
DMC Controller Specifications
Ambient temperature
5°C to 50°C (35°F to 122°F)
Input voltage range (24VDC DMC Controller)
24VDC
Power Rating 16W (Max)
Protection class
IP65
A circuit breaker or switch must be installed near the dryer. This should be easy to reach and shall be certified according
to EN60947-1 and EN60947-3. The switch or circuit breaker shall be marked as the disconnecting device for the dryer and
needs to be marked with on and off positions.
Output connections do not provide isolation from the mains connectors and interconnecting wiring must meet EN61010-
1:2001 requirements for reinforced insulation.
2
3
24VDC (-)
Not used
Not used
Not used
N.O.
N.O.
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Earth
1
PIN
INPUT
INPUT
OUTPUT
OUTPUT
V.F.* OUTPUT
24VDC (+)
2
3
24 VDC (+)
24 VDC (-)
1
PIN
Signal (Hyg Pin 1)
Hygrometer Pin 2
Hygrometer Pin 3
2
3
1
PIN
24VDC (+)
2
3
* Volt Free
1
PIN
12-24VDC
OUTPUT
2
24VDC (-) Remote Valve Pin 2
1
PIN
24VDC (+) Remote Valve Pin 1
INPUT
INPUT
INPUT
1
2
3
1
2
3
1
2
3
1
2
3
1
2
POWER SUPPLY
HYGROMETER
ENERGY MANAGEMENT
ALARM
REMOTE DRAIN VALVE
Section 5: Electrical Installation
24
PRODRY PD0046 - PD0360 Instruction Manual
|
Walker Filtration
|
Fig ure 5.2 : DMC C ontrolle r electrical connections
DMC Controller Specifications
Ambient temperature
1.5°C to 50°C (35°F to 122°F)
Max. relative humidity
80% up to 31°C (88°F), decreasing linearly to 50% RH at 50°C (122°F)
Input voltage range (24VDC DMC Controller)
24VDC
Power Rating 16W (Max)
Protection class
IP65
Transient over voltage
IEC 60664 Class II
Pollution degree
2, IEC 60664
A circuit breaker or switch must be installed near the dryer. This should be easy to reach and shall be certified according to
EN60947-1 and EN60947-3. The switch or circuit breaker shall be marked as the disconn ecting device for the dryer and needs
to be marked with on and positions.
Output connections do not provide isolation from the mains connect ors and interconnecting wiring must meet EN61010-1:2001
requirements for reinforced insulation.
Figure 5.2: LED Controller electrical connections
1-green
control
2-blue
3-red
1-brown
2-blue