22
Section 5:
Electrical Installation
Electrical Installation
PRODRY Controller power supply options
Models PD0046 - PD0360
•
The dryer is designed to operate on either AC or DC
supply voltage dependant on controller option.
•
Electrical wiring must comply with local regulations.
Voltage requirements must be confirmed to be within
the specification on the dryers rating plate.
•
Ensure only one power source is connected at any one
time and is connected to the correct socket as shown in
figures 5.1 (LED Controller) and 5.2 (DMC Controller).
•
The LED and DMC controller require a earth to be
connected within the DIN connector.
•
The cable selection must suit local installation
regulations and be appropriate to power consumption
as shown in the Controller specification tables on pages
23 and 24.
PRODRY Recommended power cable specifications
Controller Type
Number
of cores
Cross Sectional
Area / AWG
Recommended
Max. Length
Type
Standard
Compliance
24VDC DMC
3
0.75mm
2
/
18 AWG
3 Metres
SJOW for Thermoset cable types
or
SVT and SJT for Thermoplastic cable types
IEC 60227
or
IEC 60245
110/230VAC LED
3