5.3
Temperature (A or B) Menu
The Temperature menu contains the following settings: Calibration and Unit selection . The
Temperature menu will be indicated on the display by one of the following:
Temperature
Normal operation
Temp 70°F
Normal operation
Temp Error
Indicates that there is a problem with the temperature input. See Figure 9.
Calibrate
To Calibrate the Temperature, use a thermometer to measure the fluid temperature and adjust the WDT controller to
match. Once Calibrate is entered, the unit continuously displays temperature readings. Press the Up or Down arrow
key to change the value displayed to match the thermometer. You must press ENTER to activate the new calibration.
You must press the EXIT key to exit calibration.
Man Temp
This menu appears only if no temperature element is connected at power-up. Use the arrow keys to adjust the
temperature displayed to match that of the water.
Units
You may choose to display temperature in °C or °F. Press ENTER and the Up or Down Arrow keys to change the
temperature units for display.
Mode
Press ENTER and use the UP or DOWN arrow keys to select between Manual Temperature Compensation (used with
sensors that do not have a temperature measuring element in them) or Automatic Temperature Compensation. If
Automatic is selected, and the temperature element is not detected, the controller will display a Temp Error and revert
to Manual Temp Comp until the signal is restored.
Calibrate
Temp °F
68
Units
°F
°F
Units
°C
°C
Temp
68°F
Calibrate
Temp
68°F
Man Temp
68
2000 s
68° F
Temperature
Temp
68°F
Units
°F
ENTER
EXIT
ENTER
EXIT
ENTER
EXIT
NEXT
PREV.
Mode
Man
Manual Temp Comp
Mode
Man
Auto Temp Comp
Temp
68°F
Mode Manual
ENTER
EXIT
2
Calibrate
Temp °C
20.1
1
Possible Status Screen
Temperature Menu
Temperature Err
Legend
Menu wording that appears when Automatic Temperature Compensation is selected.
Menu wording that appears when Manual Temperature Compensation is selected.
2
1
Figure 9 Temperature Menu
16