25 

5.7 

Bio1 and Bio2 Menus 

These menus are only available on the WCT410 controller. The Bio 1 and Bio 2 menus are separate 
from each other but operate in exactly the same way. Each menu provides the following independent 
settings: Prog Bio Adds, Bio Pre-Bleed, Bio Lockout Time, Set Bio Mode, HOA. Bio menus may 
display the following screens:  

 

Bio 1 A 

OFF   

Indicates that the Bio 1 output is off. 

Bio 1 A 

PENDING 

Indicates that Bio 1 is ready to begin a biocide cycle but is unable to begin due to NO FLOW, 
or Bio 2 already ON. 

Bio 1 A 

PRE BLD 

Indicates that Bio 1 is in the Pre-Bleed portion of its cycle. 

Bio 1 A 

4:50 

Indicates that Bio 1 is adding and has  4 minutes and 50 seconds remaining to add, or that there 
are 4 hours and 50 minutes of Bio 1 Lockout remaining. If the Bio 1 LED is ON, the timer is 
for the Add. If the LED is OFF, the timer is for remaining lockout time. 

Bio 1 A 

NO FLOW 

Indicates that there is no biocide activity and none is pending and that there is no flow past the 
flow switch. 

 
Note: When programming the unit for the first time, it is recommended that the Biocide Add Mode be 
chosen first, then step through the rest of the Biocide Add menu indicated below and in figures 13 and 
14. This will make programming simple and logical. 
 
A number of built-in interlocks are part of the biocide feed program. When one biocide relay activates, 
the other biocide will be locked out until the first biocide finishes its control cycle. Similarly, the bleed 
relay is locked out once the biocide cycle begins (except for the pre-bleed portion of the cycle). Bear 
this in mind, especially if the biocide feed time is very long or very frequent...very little time is left in 
the day to control the conductivity. 

 

  
The inhibitor feed relay interaction is more complex.  
 

For Bleed and Feed mode 

Since the bleed relay is locked out, the feed relay will be locked out as well. 

For Feed as % Bleed 

If the bleed is adjacent to the start of the biocide cycle, or is during the pre-bleed part of the 
cycle, the feed time does not occur. 

For Feed as % Time 

The feed relay is locked out during the biocide add, the feed events are not stored in 
memory, but the feed cycle time is reset once the biocide add cycle is over, so that as soon as 
the biocide cycle is complete, one feed cycle will occur. 

For Water Contactor or Paddlewheel 
mode 

The water flow is stored in memory, up to 256 contacts, and the correct feed time is activated 
once the biocide cycle has completed. 

 
 

 

Содержание WCT400 Series

Страница 1: ...ing Tower Conductivity Controller Instruction Manual Five Boynton Road Hopping Brook Park Holliston MA 01746 USA TEL 508 429 1110 FAX 508 429 7433 WEB www walchem com WCT400 410 Controllers W A L C H...

Страница 2: ...months for electronics and 12 months for mechanical parts and electrodes from date of delivery from the factory or authorized distributor under normal use and service and otherwise when such equipmen...

Страница 3: ...Access Code 13 4 5 Startup 13 4 6 Shut Down 13 5 0 OPERATION 14 5 1 Main Menu 14 5 2 Conductivity Menu 16 5 3 Temperature Menu 18 5 4 Bleed Menu 19 5 5 Feed Menu 21 5 6 WM1 and WM2 Menus 24 5 7 Bio1...

Страница 4: ...e effect as soon as it is entered An access code is available to protect set point parameters while still allowing settings to be viewed The model WCT410 biocide outputs are scheduled on a user select...

Страница 5: ...al Internally powered Fully isolated 600 Ohm max resistive load Resolution 001 of span Accuracy 1 of reading Agency Approvals Safety UL 61010 1 2012 3rd Ed CSA C22 2 No 61010 1 2012 3rd Ed IEC 61010 1...

Страница 6: ...min 59 sec Time per Contact Mode D 1 second 59 min 59 sec Contacts by Mode D 1 contact 100 contacts Time Limit Mode D E 1 minute 99 min 59 sec Time Vol Mode E 1 second 59 min 59 sec Vol to Initiate Fe...

Страница 7: ...WCT series controller is mounted the metering pumps may be located at any distance from the controller The conductivity electrode should be placed as close to the controller as possible to a maximum...

Страница 8: ...RCULATING PUMP SOLENOID VALVE COOLING TOWER WATER METER Cooling Tower Controller www walchem com PREV NEXT ENTER EXIT FLOW FLOW FLOW SWITCH ELECTRODE SAMPLE VALVE 10 0 254 mm 1 4 POLYPRO PANEL 17 432...

Страница 9: ...TOWER SPRAY PUMP CITY WATER MAKEUP SHUTOFF VALVE A D A B F C E A Unions installed for replacement of solenoid strainer or probe B solenoid C Y strainer D PVC threaded tee probe supplied with controll...

Страница 10: ...X Y Z X VALVE X Y Z X OPTION B TO SANITARY SERVER PROBE NOTE LOCATION OF SOLENOID VALVE USING OPTION A OR OPTION B DEPENDS ON SYSTEM CONFIGURATION DETAIL OF PROBE ASSEMBLY TO CONTROLLER 1 PVC PIPE 1 N...

Страница 11: ...re power to the controller is REMOVED If your controller is prewired it is supplied with a 8 foot 18 AWG power cord with USA style plug A tool 1 Phillips driver is required to open the front panel 2 W...

Страница 12: ...Reed Switch Flow Meter Polarity not Critical IN FLOW MTR 1 FLOW MTR 2 IN IN FLOW SW 1 IN IN IN 5V BLK RED COND T T BLEED N C FEED N O N C N O L2 L2 L1 L2 N Hall Effect Flow Meter G R E E N W H I T E G...

Страница 13: ...D BLK 120V BRN 240V WHT 120V BLU 240V GRN 120V GRN YEL 240V IF MOTORIZED BALL VALVE BLK 120 BRN 240V W HT 120V BLU 240V G R N 1 2 0 V G R N Y E L 2 4 0 V Chart Recorder NOTE When connecting a motorize...

Страница 14: ...WHT 120V BLU 240V GRN 120V GRN YEL 240V GRN 120V GRN YEL 240V IF MOTORIZED BALL VALVE BLK 120V BRN 240V BLK 120V BRN 240V Chart Recorder BLK 120V BRN 240V WHT 120V BLU 240V WHT 120V BLU 240V WHT 120V...

Страница 15: ...ars at each 5 The bar graph is limited to displaying 20 above or below the set point When these limits are reached an L or H may appear at the end of the bar graph to indicate a low or high alarm The...

Страница 16: ...it see Section 5 11 for operation With the access code enabled any user can view parameter settings but not change them Note that this provides protection only against casual tampering Use a lock on...

Страница 17: ...till controlling 5 1 Main Menu The exact configuration of your WCT controller determines which menus are available as you scroll through the settings Certain menus are only available on the WCT410 con...

Страница 18: ...ation 2000 S 67 F Bio 1 OFF 2000 S 67 F Bio 2 OFF 2000 S 67 F Time Sun 3 00 2000 S 67 F Cnd Alrm Lo Alrm 2000 S 67 F 4 20mA 4 0 mA 2000 S 67 F Access Code DIS Temp Error Sensor Error No Flow Bleed Tim...

Страница 19: ...are not automatically translated from S cm to ppm If you change the units you will need to change your Bleed settings ppm C F This is the ppm Conversion Factor or multiplier This is typically 0 666 b...

Страница 20: ...Cond 1000 S Duration 2 00 Cond Wait 23 50 Cond Samp 10 00 Cond Xtnd 10 00 Conductivity Menu Possible status screens Menu choices that appear when ppm units are selected Press Enter key to enter menu P...

Страница 21: ...p Use the arrow keys to adjust the temperature displayed to match that of the water Units You may choose to display temperature in C or F Press ENTER and the Up or Down Arrow keys to change the temper...

Страница 22: ...the bleed output turns OFF Assuming that the control direction is set for normal operation High Set Point the bleed output will turn off when the conductivity drops below the set point minus the Dead...

Страница 23: ...y to exit menu Blinking fields may be edited with the adjust arrows Press Enter when modification is complete to return to Bleed Menu Level ENTER EXIT ENTER EXIT Operation NEXT PREV Bleed 1 01 15 Time...

Страница 24: ...wave flow meters The Feed menu will be indicated on the display by one of the following The A indicates that the feed is being controlled automatically Feed A OFF Indicates that the Feed output is cur...

Страница 25: ...n be disabled Feed Based on Paddlewheel Mode Time Vol This setting determines the pump on time once a given volume of water has passed through the paddlewheel sensor The volume required to initiate fe...

Страница 26: ...ed Menu choices that appear when Feed as of Time mode is selected Menu choices that appear when Feed based on Water contactor input is selected Legend Feed Lockout 99 00 TIMEOUT Feed of Bleed 10 TIMEO...

Страница 27: ...sor sends out This value is usually printed on the sensor s flow cell or in its instructions Tot Units This is used to set the units of measure for the totalizer Press ENTER then use the up and down a...

Страница 28: ...rough the rest of the Biocide Add menu indicated below and in figures 13 and 14 This will make programming simple and logical A number of built in interlocks are part of the biocide feed program When...

Страница 29: ...igher than this set point the bleed output is turned on to lower the conductivity This setting is independent of the bleed set point in the Bleed Menu There are separate Bio 1 and Bio 2 Pre Bleed sett...

Страница 30: ...it key to exit menu Blinking fields may be edited with the adjust arrows Press Enter when modification is complete Use Next and Prev keys to change days in Prog Menu choices that appear when 2 Week Bi...

Страница 31: ...ing fields may be edited with the adjust arrows Press Enter when modification is complete Use Next and Prev keys to change days in Prog Menu choices that appear when 2 Week Biocide Cycle mode is selec...

Страница 32: ...R to store or EXIT to discard If either biocide is set for a 2 or 4 week cycle you can change the current week in the cycle by changing the week number If the longest biocide cycle is 2 weeks the 3Sun...

Страница 33: ...vate If the conductivity set point is 1000 and the Low setting is 20 then the Low alarm will activate at 800 The alarm can be disabled by setting it to zero Set High This is the above the bleed set po...

Страница 34: ...ctivity setting will correspond to a 4 mA output from the controller Set 20mA Pt This conductivity setting will correspond to a 20mA output from the controller Calibrate This will provide fixed 4mA an...

Страница 35: ...Indicates that the access code is disabled No access code is required to change any setting Access Code REQ Indicates that the access code is required to alter settings Access Code OK Indicates that...

Страница 36: ...into the USB port on the front panel of the controller Press the Enter key to download the file from the controller to the disk The file name for the Current Datalog will be Datalog serial number dat...

Страница 37: ...the stick into the USB port on the front panel of the controller Press the Enter key to import the configuration file from the stick to the controller The file name must have an ini extension in its n...

Страница 38: ...he file import process If the file was successfully imported from the USB disk the controller will display Transfer Success The controller will automatically reboot and come up with the new software i...

Страница 39: ...mpare with the reading in step 1 above If the variance in readings is greater than 5 increase the frequency of electrode cleaning If there is less than 5 change in the reading the electrode was not di...

Страница 40: ...on a false pH or conductivity reading Possible Cause Correction Action Green or white electrode wire disconnected Reconnect Faulty electrode Replace electrode Revert to manual temperature compensation...

Страница 41: ...ated Possible Cause Corrective Action No flow Check recirculating pump valves etc Faulty flow switch cable Check for open circuit Disconnect flow switch and short the input with a piece of wire If no...

Страница 42: ...e check the electrode connections to the terminal strip refer to Figure 3 Make sure that the correct colors go to the correct terminals and that the connections are tight Restore power and see if the...

Страница 43: ...P panel 5 ft 1 5m cable 4 High pressure electrode up to 300 psi 20 ft 6 1m cable 5 High pressure electrode flow switch manifold on PP panel 5 ft 1 5m cable 6 PP SS electrode tee 20 ft 6 1m cable 7 PP...

Отзывы: