18
5.3 Temperature
Menu
The Temperature menu contains the following settings: Calibration and Units (if the Temp element
is detected when the unit is powered on) or Manual Temp and Units (if no Temp sensor is detected
at power up). Refer to the Temperature Menu chart, figure 9.
If a "Temp Error" message appears or if the "Man Temp" menu appears after the unit is powered on,
it indicates the temp element is not working properly. Refer to the Troubleshooting Section.
Calibrate
To Calibrate the Temperature, use a thermometer to measure the fluid temperature and adjust the WCT controller to
match. Once Calibrate is entered, the unit continuously displays temperature readings. Press the Up or Down arrow key
to change the value displayed to match the thermometer. You must press ENTER to activate the new calibration. You
must press the EXIT key to exit calibration.
Man Temp
This menu appears only if no temperature element is connected at power-up. Use the arrow keys to adjust the
temperature displayed to match that of the water.
Units
You may choose to display temperature in °C or °F. Press ENTER and the Up or Down Arrow keys to change the
temperature units for display.
Mode
Press ENTER and use the UP or DOWN arrow keys to select between Manual Temperature Compensation (used with
sensors that do not have a temperature measuring element in them) or Automatic Temperature Compensation. If
Automatic is selected, and the temperature element is not detected, the controller will display a Temp Error and revert
to Manual Temp Comp until the signal is restored.
Figure 9 Temperature Menu
Calibrate
Temp °F 68
Units °F
°F
Units °C
°C
Temp 68°F
Calibrate
Temp 68°F
Man Temp 68
2000 s 68° F
Temperature
Temp 68°F
Units °F
Temperature Menu
Menu wording that appears when Automatic Temperature Compensation is selected.
ENTER
EXIT
ENTER
EXIT
ENTER
EXIT
Legend
NEXT
PREV.
Menu wording that appears when Manual Temperature Compensation is selected.
Temperature Err
Possible Status Screen
Calibrate
Temp °C 20.1
Mode Man
Manual Temp Comp
Mode Man
Auto Temp Comp
Temp 68°F
Mode Manual
ENTER
EXIT
2
1
2
1