54
Dye/Product Ratio
Enter the value for the ratio of ppb of dye to ppm of inhibitor that is in the inhibitor
product being fed.
Name
The name used to identify the transmitter may be changed.
Type
Select the type of sensor to be connected. The choice of Analog Input is only avail-
able if that type of sensor card is installed.
5.2.12
Analog Flowmeter Input
Settings
Touch the Settings icon to view or change the settings related to the sensor.
Alarms
Low-Low, Low, High and High-High Alarms limits may be set.
Deadband
This is the Alarm Deadband. For example, if the High Alarm is 7.00, and the dead-
band is 0.1, the alarm will activate at 7.01 and deactivate at 6.90.
Totalizer Alarm
Enter the high limit on the total volume of water accumulated above which an
alarm will be activated.
Reset Flow Total
Enter this menu to reset the accumulated flow total to 0. Touch Confirm to accept,
Cancel to leave the total at the previous value and go back.
Set Flow Total
This menu is used to set the total volume stored in the controller to match the regis-
ter on the flow meter. Enter the desired value.
Scheduled Reset
Choose to automatically reset the flow total, and if so, Daily, Monthly or Annually.
Reset Calibration Values
Enter this menu to reset the sensor calibration back to factory defaults.
Cal Required Alarm
To get an alarm message as a reminder to calibrate the sensor on a regular schedule,
enter the number of days between calibrations. Set it to 0 if no reminders are necessary.
Alarm Suppression
If any of the relays or digital inputs are selected, any alarms related to this input
will be suppressed if the selected relay or digital input is active. Typically this is
used to prevent alarms if there is no sample flow past the flow switch digital input.
Smoothing Factor
Increase the smoothing factor percentage to dampen the response to changes. For
example, with a 10% smoothing factor, the next reading shown will consist of an
average of 10% of the previous value and 90% of the current value.
Transmitter
Select the type of transmitter connected (2-wire loop powered, 2-wire self-pow-
ered, 3-wire, or 4-wire).
Flow Units
Select the units of measure for the water volume, between gallons, liters, cubic
meters and million of gallons (MG).
Rate Units
Select the units of measure for the flow rate time base.
Flowmeter Max
Enter the flow rate at which the meter outputs a 20 mA signal.
Input Filter
Enter the mA below which the flow rate will considered 0. Typically any meter output
below 4.02 mA is actually 0 flow.
Name
The name used to identify the sensor may be changed.
Type
Select the type of sensor to be connected.
5.2.13
DI State
Input Details
The details for this type of input include the current state with a custom message for open versus closed, alarms,
the status of the interlock, and the current type of input setting.
Settings
Touch the Settings icon to view or change the settings related to the sensor.
Open Message
The words used to describe the switch state may be customized.