WARNING: Do not attempt to convert this water heater for use with a different type of gas other than the type shown 

on the rating plate. Such conversion could result in hazardous operating conditions.

Gas Supply

The supplied Manual Gas Appliance Shutoff 

valve must be installed at the gas connection of 

the water heater at the time of installation (see 

diagram to the left) .
The branch gas supply line to the water heater 

should be a minimum of 3/4” black steel pipe 

or other approved gas piping material .
A ground joint union or ANSI design certified 

semi-rigid or flexible gas appliance connector 

should be installed in the gas line close to the 

water heater . The National Fuel Gas Code 

(NFGC) ANSI Z223 .1 and CAN B149 code 

mandates a manual gas shut-off valve: See 

NFGC & B149 for complete instructions .
If flexible connectors are used, the maximum 

length shall not exceed 36” (91 cm) .
If lever type gas shut offs are used, they shall 

be approved/certified gas cocks . .
Compound used on the threaded joints of the 

gas piping must be of the type resistant to the 

action of LP gas . Use compound sparingly on 

male threads only . 

A sediment trap should be installed at the 

bottom of the gas line .
Do not use excessive force (over 31 .5 ft lbs . 

[42 .7 Nm]) in tightening the pipe, particularly if 

teflon pipe compound is used, as the unit may 

be damaged .
The inlet gas pressure to the water heater must 

not exceed 10 .5” w .c . (2 .6 kPa) for natural or 

13” w .c . (3 .2 kPa) for LP gas . For purposes  

of input adjustment, the minimum inlet gas 

pressure (with main burner on) is shown on 

the water heater rating plate . If high or low gas 

pressures are present, contact your gas supplier 

for correction .

NOTICE:

 To ensure proper operation of the 

heater the gas pipe and gas meter must be sized 

correctly .
Gas piping shall be in accordance with local, 

utility company requirement and/or in the  

absence of local codes, use the latest edition of 

the National Fuel Gas Code . In Canada, the latest 

edition of CSA B149 .1 Natural Gas and Propane 

installation code .

Manual

Gas

Supply

Line

Shutoff

Manual Gas

Appliance

Shutoff

Union

Sediment Trap

Cap

(Valve)

(Supplied)

Leak Testing

The water heater and its gas connections must 

be leak tested at normal operating pressures 

before it is placed in operation .

  

 Turn on the gas shut-off valve(s) to the 

water heater .

   

Use a soapy water solution to test for 

leaks at all connections and fittings . 

Bubbles indicate a gas leak that must  

be corrected .

 

The factory connections should also be leak 

tested after the water heater is placed in 

operation .

WARNING: Never use 

an open flame to test for 

gas leaks, as property 

damage, personal injury,  

or death could result.

Pressure Testing the Gas Supply System

The water heater and its manual gas shut-

off valve must be disconnected from the gas 

supply piping system during any pressure 

testing of the system at pressures in excess  

of 1/2 psi (14” w .c . [3 .5 kPa]) .

The water heater must be isolated from the 

gas piping system by closing the manual gas 

shut-off valve during any pressure testing of 

the gas supply piping at pressures equal to or 

less than 1/2 psi (14” w .c . [3 .5 kPa]) .

WARNING: Install a gas 

pressure regulator, in the 

gas supply line, which does 

not exceed the maximum 

supply pressure.
DO NOT use an industrial 

type gas regulator.

This water heater is certified for installations 

up to 3,280 feet (1000 m) above sea level . 

The input rating of this water heater is based 

on sea level operation . At higher  

elevations, the actual input rate may be 

lower than the value listed on the rating 

label .

NOTICE: For installations above 3,280 

feet (1,000 m) elevation, contact a quaili-

fied service technician to make the proper 

altitude adjustment.  See page 31 for ad-

ditional information.
Do not install this water heater at eleva-

tions above 3,280 feet (1,000 m) without 

making the proper adjustment. Please 

contact your installer, local gas supplier, 

place of purchase or the Customer Service 

phone number as listed in this Use & Care 

Manual for more information. 

High Altitude

14

Содержание SCT150X

Страница 1: ...proper installation and adjustment of the water heater and two to the owner operator to explain the features operation safety precautions maintenance and troubleshooting of the water heater This manu...

Страница 2: ...heater You ll find many answers to common problems in the Troubleshooting Guide If you review the chart of Troubleshooting Tips first you may not need to call for service READ THIS MANUAL Your safety...

Страница 3: ...e not limited to adhesives solvents paint thinners etc and the vapors they produce are extremely dangerous DO NOT handle use or store gasoline or other flammable or combustible materials anywhere near...

Страница 4: ...achieved with the Bath USC 117 or USC2 117 remote control Only qualified service personnel should perform this adjustment Only factory authorized remote control s should be used Notice When this water...

Страница 5: ...e or LP gas must be used with great caution It is heavier than air and will collect first in lower areas making it hard to detect at nose level Before attempting to light the water heater make sure to...

Страница 6: ...ntial water heaters of a capacity greater than 52 gallons or tankless style consult the local building jurisdiction code for acceptable bracing procedures Have the installer show you the location of t...

Страница 7: ...which may result in severe burns death or property damage The water heater must be located so it is not subject to physical damage for example by moving vehicles area flooding etc The water heater sh...

Страница 8: ...n How to Obtain Service Assistance Do not destroy this manual Please read carefully and keep in a safe place for future reference Recognize this symbol as an indication of Important Safety Information...

Страница 9: ...level 12 inches 30 cm above anticipated snow level B Clearance to window or door that may be opened 6 inches 15 cm for appliances 10 000 Btuh 3 kW 12 inches 30 cm for appliances 10 000 Btuh 3kW and 10...

Страница 10: ...accidental contact with people and pets Install outdoor water heater such that air inlet and flue outlet is above anticipated snow level 1 8 m If soffit vent is too close block off and install new ven...

Страница 11: ...of 0 66 gpm 2 5 lpm A water pressure of 40 psi 276 kPa is required to achieve maximum flow rate To maintain proper performance ensure sufficient water supply pressure The Required Water Pressure Min O...

Страница 12: ...heck Valve between the water heater and the water shutoff valve see the top left diagram The following should be addressed in regards to the HOT WATER OUTLET Connections between the water heater and p...

Страница 13: ...e relief valve and discharge line The end of the discharge line should not be threaded or concealed and should be protected from freezing No valve of any type restriction or reducer coupling should be...

Страница 14: ...of the National Fuel Gas Code In Canada the latest edition of CSA B149 1 Natural Gas and Propane installation code Manual Gas Supply Line Shutoff Manual Gas Appliance Shutoff Union Sediment Trap Cap...

Страница 15: ...nd electrical grounding must comply with local codes or in the absence of local codes with the latest edition of the National Electrical Code ANSI NFPA 70 or in Canada Canadian Electrical Code CSA C22...

Страница 16: ...r the base plate Ensure the projections in the base plate fit into the housings in the remote control Fix the control to the base plate at the bottom of the remote control using the screw provided Pro...

Страница 17: ...NTMODELONLY POURMOD LE VENTDIRECTSEULEMENT SW3 SW2 SW1 U 2 1 S 1 3 2 W W 12 3 4 I J H F W W 2 3 4 1 B R Y O W BR BK 1 2 3 4 5 6 7 8 R Y O W BR BK 1 2 3 4 5 6 7 8 C 9 R BR BK BK W BK W 1 2 3 4 Y W BK 1...

Страница 18: ...ufacturer s instructions Outdoor Models Discharge Line To Suitable Drain To Hot Water Faucet s Relief Valve Union Drain Valve 6 15 cm Air Gap Manual Gas Appliance Shut off supplied Flue Terminal Trap...

Страница 19: ...heat loss encountered with storage tank heaters This water heater does not store water making an insulation blanket unnecessary The manufacturer s warranty does not cover any damage or defect caused...

Страница 20: ...nd piping Water connections tight and free of leaks Water filter is clean and in place Materials used are as instructed in this manual Water pipes are insulated and protected from freezing C Gas Suppl...

Страница 21: ...s label 2 Turn off all electric power to the appliance 3 Do not attempt to light the burner by hand 4 Turn the Gas Shutoff Valve located on the outside of the unit clockwise to the OFF position 5 Wait...

Страница 22: ...s to the water heater If there is any difficulty in understanding or following the Operating Instructions or the Care and Cleaning section it is recommended that a qualified person or serviceman perfo...

Страница 23: ...above 112 F 44 C when a hot water faucet is in the open position Notice The factory setting allows operating temperatures between 100 F 38 C and 120 F 49 C Temperatures of 85 F 29 C and up to140 F 60...

Страница 24: ...ater heater discharges periodically this may be due to a problem in the water system Contact the water supplier or your plumbing contractor on how to correct this DO NOT plug the relief valve outlet R...

Страница 25: ...NOT scrub the appliance with a brush Use only mild soapy water other cleaners may damage the surface of the water heater DO NOT remove any label including the rating plate while cleaning or servicing...

Страница 26: ...ter may be exposed to freezing conditions even for a short period of time be sure to drain all water from the unit as instructed above Exposure to freezing conditions can occur from down draft of vent...

Страница 27: ...Valve Malfunctions if applicable Check and replace if necessary Error code displayed on remote control See instructions for Error Code and if required contact a dealer for service Not enough water de...

Страница 28: ...in Gas Line Power supply not grounded Low inlet gas pressure due to improper sizing Wrong gas type Open the Gas shutoff valve fully Contact gas utility company Fill up LP Gas container or replace with...

Страница 29: ...as noted below and number of parts desired CAUTION For your safety DO NOT attempt repair of electrical wiring gas piping burners vent connectors or other safety devices Refer repairs to qualified serv...

Страница 30: ...econds Number 120 on the display of the remote control will begin to blink While the number is blinking push the UP arrow temperature adjustment button and the Down arrow temperature adjustment button...

Страница 31: ...ay not function properly NOTICE If the water heater is installed less than 3 280 feet 1 000m no action is required How to adjust the DIP switch on the PCB for high altitude installation Check the alti...

Страница 32: ...act the Manufacturer s National Service Department at the following address 1241 Carwood Court Montgomery AL 36117 Phone 1 800 432 8373 When contacting the manufacturer the following information will...

Отзывы: