background image

This water heater is certified for instal-
lations up to 3,280 feet (1000 m) above
sea level.  The input rating of this water
heater is based on sea level operation.
At higher elevations the actual input
rate may be lower than the value listed
on the rating label.

NOTICE: For installations above 
3,280 feet ( 1 , 0 0 0   m )   elevation, the
Altitude Chip on the PC board must be
replaced. Do not install this water
heater at elevations above 3,280 feet
(1,000 m) without installing the proper
Altitude Chip.  Please contact your in-
staller, local gas supplier, place of pur-
chase, or the Customer Service phone
number as listed in this Instruction
Manual for more information.  

WARNING: Do not attempt to convert this water heater for use with a different type of gas other than the type shown

on the rating plate. Such conversion could result in hazardous operating conditions.

Leak Testing

The water heater and its gas connections
must be leak tested at normal operating
pressures before it is placed in operation.

Turn on the gas shut-off valve(s) to
the water heater.

Use a soapy water solution to test for
leaks at all connections and fittings.
Bubbles indicate a gas leak that must
be corrected.

The factory connections should also be
leak tested after the water heater is placed
in operation.

Pressure Testing the Gas Supply System

The water heater and its manual gas shut-
off valve must be disconnected from the
gas supply piping system during any
pressure testing of the system at
pressures in excess of 1/2 psi (14” w.c.)
(3.5 kPa).

The water heater must be isolated from
the gas piping system by closing the
manual gas shut-off valve during any
pressure testing of the gas supply piping at
pressures equal to or less than 
1/2 psi (14” w.c.) (3.5 kPa).

WARNING: Never use

an open flame to test for
gas leaks, as property
damage, personal injury, or
death  could result.

WARNING: Install a

gas pressure regulator, in
the gas supply line, which
does not exceed the
maximum supply pressure.

DO NOT use an industrial
type gas regulator.

High Altitude

Gas Supply

The supplied Manual Gas Appliance Shutoff
Valve must be installed at the gas connection
of the water heater at the time of installation
(see Figure to the left).

The branch gas supply line to the water
heater should be a minimum of 3/4” black
steel pipe or other approved gas piping
material.

A ground joint union or ANSI design
certified semi-rigid or flexible gas appliance
connector should be installed in the gas line
close to the water heater. The National Fuel
Gas Code (NFGC) ANSI Z223.1 and CAN
B149 code mandates a manual gas shut-off
valve: See NFGC & B149 for complete
instructions.

If flexible connectors are used, the maximum
length shall not exceed 36” (91 cm) and must
meet the requirements in ANSI Z21.24 -
Connectors for Gas Appliances.

If lever type gas shut offs are used, they shall
be T-Handle type.

Compound used on the threaded joints of the
gas piping must be of the type resistant to the
action of LP gas. Use compound sparingly
on male threads only.

A sediment trap should be installed at the
bottom of the gas line.

Do not use excessive force (over 31.5 ft lbs.)
(42.7 Nm) in tightening the pipe, particularly
if teflon pipe compound is used, as the unit
may be damaged.

The inlet gas pressure to the water heater
must not exceed 10.5” w.c. (2.6 kPa) for
natural or 14” w.c. (3.5 kPa) for LP gas. For
purposes of input adjustment, the minimum
inlet gas pressure (with main burner on) is
shown on the water heater rating plate. If
high or low gas pressures are present, contact
your gas supplier for correction.

NOTICE:

To ensure proper operation

of the heater the gas pipe and gas meter
must be sized correctly.

Gas piping shall be in accordance with
local, utility company requirement
and/or in the absence of local codes,
use the latest edition of the National
Fuel Gas Code. In Canada the latest
edition of CSA B149.1 Natural Gas and
Propane installation code.

19

Содержание PH-28R IFSN

Страница 1: ...the water heater and two to the owner operator to explain the features operation safety precautions maintenance and troubleshooting of the water heater This manual also includes a parts list It is ver...

Страница 2: ...S MANUAL FOR YOUR RECORDS Write the model and serial numbers here You can find them on a label on the appliance Staple sales slip or cancelled check here Proof of the original purchase date is needed...

Страница 3: ...t is properly vented and has an adequate air supply for proper operation Be sure to inspect the vent terminal vent and the air intake system on the water heater for proper installation at initial star...

Страница 4: ...ature Notice The factory setting allows operating temperatures between 100 F 38 C and 120 F 49 C Temperatures of up to 140 F 60 C for Residential models and up to 180 F 82 C for Commercial models can...

Страница 5: ...P gas must be used with great caution It is heavier than air and will collect first in lower areas making it hard to detect at nose level l Before attempting to light the water heater make sure to loo...

Страница 6: ...ormation in this manual must be followed to minimize the risk of fire or explosion electric shock or to prevent property damage personal injury or loss of life FOR INSTALLATIONS IN THE STATE OF CALIFO...

Страница 7: ...lly spilled l The water heater should be installed as close as practical to the vent termination to minimize vent length and the number of elbows required for venting l The water heater should be inst...

Страница 8: ...r fire WHAT TO DO IF YOU SMELL GAS l Do not try to light any appliance l Do not touch any electrical switch do not use any phone in your building l Immediately call your gas supplier from a neighbor s...

Страница 9: ...e venting instructions in this manual before completing the installation and putting the water heater into service Additional installation information for The Commonwealth of Massachusetts is located...

Страница 10: ...nation The vent should have a 1 4 per foot DOWNWARD slope towards the vent terminal as shown above If the air intake pipe or duct is connected to the bottom of the air intake tee a condensate trap mus...

Страница 11: ...ly inlet to the combustion air inlet to any building or other appliance 6 inches 15 cm for appliances 10 000 Btuh 3 kW 12 inches 30 cm for appliances 10 000 Btuh 3kW and 100 000 Btuh 30kW 36 inches 91...

Страница 12: ...age to the structure or exterior finish of the building Inside Corner Caulk 6 1 8 m Caulk Zone If soffit vent is too close block off and install new vent at another location Caulk Caulk Rising moistur...

Страница 13: ...ring located in the female end of the 4 7 concentric vent pipe section When fully assembled the outer female end see Figure to left will overlap the male end by approximately 1 25 4 mm Use the self t...

Страница 14: ...ale end of the air intake connection of the air intake tee Install the appliance adapter onto the appliance outlet and inlet and clamp as required Now attach other required vent and air intake materia...

Страница 15: ...nnector fitting on the water heater vent collar outlet and air intake Support vertical or horizontal runs every 5 feet 1 5 m If required use silicone sealant at the point the vent connector joins the...

Страница 16: ...ualified plumber in accordance with local codes Use approved plumbing materials only The diameter of the pipe lines should be a minimum of 3 4 To conserve energy and to prevent freezing insulate both...

Страница 17: ...er Be sure to connect the water inlet and the hot water outlet as shown on the water heater If reversed the water heater will not function Installation of unions or flexible copper connections are rec...

Страница 18: ...cer coupling should be installed in the discharge line Notice Local codes govern the installation of relief valves If local codes require that a temperature and pressure relief valve should be install...

Страница 19: ...ARNING Install a gas pressure regulator in the gas supply line which does not exceed the maximum supply pressure DO NOT use an industrial type gas regulator High Altitude Gas Supply The supplied Manua...

Страница 20: ...e control WARNING Field wiring connections and electrical grounding must comply with local codes or in the absence of local codes with the latest edition of the National Electrical Code ANSI NFPA 70 o...

Страница 21: ...s l l Connect the remote control cables to the extension cable from the water heater l l Place the remote control over the base plate Ensure the projections in the base plate fit into the housings in...

Страница 22: ...pment that carry a ground fault interrupter l An ON OFF switch must be provided and installed for the incoming 120VAC power l Wire the water heater exactly as shown below A wiring Figure is also found...

Страница 23: ...figures provided and take precedent over these instructions Water Inlet Water Outlet Drain Pressure Relief Valve Hot Water Service Valve Cold Water Service Valve Alternate Piping Arrangement 90 Elbow...

Страница 24: ...ot and Cold Pipe Insulation Installation Insulation Blankets Insulation blankets available to the general public for external use on gas water heaters are not necessary The purpose of an insulation bl...

Страница 25: ...ion and sediment trap q Approved pipe joint compound used q Soap and water solution used to check all connections and fittings for possible gas leak q Gas Company inspected installation if required D...

Страница 26: ...and all other labels on the water heater as well as the warnings printed in this manual Failure to do so can result in unsafe operation of the water heater resulting in property damage personal injur...

Страница 27: ...g valves are available for reducing point of use water temperature by mixing hot and cold water in branch water lines Contact a licensed plumber or the local plumbing authority for further information...

Страница 28: ...er heater Always remember to test the water temperature with your hand before use and remember that hotter water increases the risk of scald injury Always supervise young children or others who are in...

Страница 29: ...pection maintenance and or cleaning ensure proper operation by turning on a hot water faucet Housekeeping Before performing Housekeeping tasks to this water heater turn the unit off and disconnect the...

Страница 30: ...cleaning a vacuum cleaner can be used on the burner Proper burner pattern Care and cleaning of the water heater Vacation and Extended Shut Down If the water heater is to remain idle for an extended p...

Страница 31: ...pply cord or disconnect breaker at least 10 seconds after step 1 Open all hot water faucets Before proceeding to the next step make sure that COLD water is coming out of all hot water faucets Close th...

Страница 32: ...control The temperature may be set too low l Increase the temperature setting Mixing Valve Malfunctions if applicable l Check and replace if necessary Error code displayed on remote controller l See i...

Страница 33: ...pairs to qualified service personnel CAUTION Make certain power to water heater is OFF before removing protective cover FOR ANY REASON CAUTION Label all wires prior to disconnection when servicing con...

Страница 34: ...al number of the water heater from the rating plate Specify type of gas natural or LP as marked on the rating plate Part description as noted below and number of parts desired CAUTION For your safety...

Страница 35: ...ater shutoff valves l Check and ensure safe operation and performance of the water heater See steps below to LIMIT maximum water temperature setting to 120 49 C Follow first four bullets points listed...

Страница 36: ...n of installation the owner shall have a period of thirty 30 days to comply with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detect...

Страница 37: ...line without the use of a temperature sensor timer or a continuously operating pump All Applicable Warranty Periods will be limited to one 1 year from the Effective Date if the water heater is instal...

Страница 38: ...ter heater or component part s Paloma will not reimburse any party for these or any other fees not specifically covered in this Limited Warranty document HOW TO OBTAIN WARRANTY CLAIM ASSISTANCE Any cl...

Страница 39: ...moved or the date of purchase of the part If it was purchased separately to establish the In warranty status of the defective component part If Paloma determines that the water heater or component par...

Страница 40: ...Imported by Efficient Technology Sales LLC 5350 Joliet Street Unit 2 Denver CO 80239 USA PRINTED IN JAPAN 31 50543 01 WA 07 08...

Отзывы: